Console Installation
Mounting the Console
8
Mounting the Console
Install 1/2-inch I.P.S. (14 mm) metal conduit between the console and the power panel as shown in Figure 3 for
international installations or Figure 4 for U.S. installations.
Figure 3. Recommended Mounting of Console - International Installations
Legend for numbered boxes
1
2A neon spur
2
To an external alarm (i.e., forecourt alarm)
3
1000 mm, maximum
4
Communication cable.
5
5A neon spur
6
From an independent power supply at the distribution panel, run three 2.5 mm
2
- minimum standard color coded wires; live,
neutral, and earth, to the fused spur. Run one 4 mm
2
- minimum wire, color coded green/yellow, from the earth bus bar at the
distribution panel direct to the console location. Leave enough free cable for connection to the console.
7
1000 mm, maximum
8
Probe field cables.
9
1500 mm, maximum
consoles\tls2\mnt.eps