 VPS Installation

Vapor Vent Stack Installation - Wired VPS

15

15

Vapor Vent Stack Installation - Wired VPS

Installation of the VPS on the vapor vent stack is only allowed at facilities equipped with a

 

Veeder-Root Vapor Polisher or Franklin Fueling System Healy Clean Air Separator.

1.

Before installing this device, perform all required safety procedures to gain access inside the vapor vent 

stack.

2.

The VPS is installed in the vent line for the tank/tanks being monitored.

3.

Locate a suitable port in an existing Schedule 40 piping fitting (tee, cross, etc.) or plumb a suitable Schedule 

40 pipe fitting (tee, cross, etc.) into the vapor vent stack line (maximum length of copper tubing limited by 

dimension in Figure

 

10).

4.

Install the VPS (item 1 in Table 2) vertically onto the center of the composite panel (item 3 in Table 2) using a 

2-inch conduit clamp, rubber shim, and necessary bolts, nuts, and washers included in the kit. Be sure the 

 symbol on the panel is facing upwards (see Figure

 

11). Wrap the rubber shim (item 22 in Table 2) around 

the sensor before inserting it into the clamp. Also make sure the VPS cable outlet is facing up and the 

pressure sensing port tube in the base of the VPS is facing down. Locate the VPS in the clamp, but leave the 

conduit clamp screw somewhat loose for later height adjustment.

5.

Install two169CA-4-4 male elbows (item 4 in Table 2) into each end of the 3-way calibration valve (item 11 in 

Table 2) as shown (see Figure

 

11).

6.

Install one 68CA-4-4 male connector (item 5 in Table 2) into the center port of the 3-way calibration valve, 

and then directly attach it to the VPS inlet port (see Figure 7).

7.

Screw the 59CA-4 plug (item 6 in Table 2) onto the left port’s male elbow (see Figure

 

11).

8.

Install the two plastic enclosure mounting plates to the back of the enclosure. Use the four short flat-head 

screws included in the enclosure hardware bag.

9.

Install the composite panel into the enclosure (item 2 in Table 2) such that the VPS cable outlet is facing up 

and the pressure sensing port tube in the base of the sensor is facing down. The 

 symbol on the panel 

should be facing upward. Use the four short screws included in the enclosure hardware bag.

10. Make sure that the white flanged porous vent (factory installed - item 17 in Table 2) is still securely installed 

into the hole in the bottom of the enclosure (see Figure

 

11).

11. Insert the S-bend ¼" OD copper tube (item 9 in Table 2) into the right-side male elbow of the 3-way 

calibration valve, but do not fully tighten the compression nut (see Figure

 

11).

12. Locate the 62CABH-4 bulkhead union (item 7 in Table 2) and remove the compression nut and the 

adjustable nut then place a large washer (item 8 in Table 2) against the fixed, integral body nut. Slide the 

compression nut that was removed onto the bottom portion of the S-bend tube.

13. Partially insert the bulkhead union into the bottom center hole in the enclosure. Slide a large washer over the 

body, and thread the adjustable nut back onto the body.

14. Insert the bottom portion of the S-bend tube into the bulkhead union and fully tighten the bulkhead union 

adjustable nut against the large washer and enclosure wall. Adjust the VPS vertically in the shim/ conduit 

clamp to make sure the S-bend tube is fully inserted into the union and male elbow.

15. Fully tighten the compression nuts to connect the S-bend tube to the union and to the male elbow. Tighten 

the sensor conduit clamp screw to secure the sensor in its final vertical position (see Figure

 

11).

16. Mount the plastic enclosure onto the vapor vent stack or suitable rigid structure ABOVE the vapor vent stack 

port using two conduit clamps (for 2" or 3" pipe), bolts, nuts, and washers included, or use other customer 

supplied suitable mounting hardware (Example: Unistrut®). Leave the mounting hardware somewhat loose for 

later enclosure height adjustment (see Figure

 

10).

17. Measure, fabricate, and install customer supplied pipe and pipe fittings between the vapor vent stack port 

and within a few inches of the bulkhead union in the bottom of the enclosure.

Содержание TLS-3 Series

Страница 1: ...Manual No 577013 797 Revision P Installation Guide Vapor Pressure Sensor TLS 450PLUS TLS 3XX Consoles...

Страница 2: ...signed Bill of Lading BOL to Veeder Root Customer Service at 800 234 5350 3 Veeder Root will file the claim with the carrier and replace the damaged missing product at no charge to the customer Custom...

Страница 3: ...stall in Horizontal Access Fitting or Vapor Return Line ISD Installation with Air Flow Meter Below Shear Valve 11 Figure 5 Example VPS Installation Below Vertical Access Fitting or Vapor Return Line I...

Страница 4: ...ded safety practices identified by OSHA and your employer Review and comply with all the safety warnings in this an any related documents and any other Federal State or Local requirements Warranty Reg...

Страница 5: ...Install Setup Operation Manual TLS 350 For Sites With TLS 450PLUS Consoles 577014 073 TLS 450PLUS Site Prep and Installation Manual 577014 484 Veeder Root ISD For TLS 450PLUS Consoles Install Manual V...

Страница 6: ...dress practices not related to physical injury WARNING This product is to be installed and operated in the highly combustible environment of a gasoline dispenser where flammable liquids and explosive...

Страница 7: ...ified yellow Gas TFE plumbing tape Intrinsically safe devices must be installed in accordance with Article 504 of the National Electrical Code ANSI NFPA 70 for installation in the United States or Sec...

Страница 8: ...S bend 333006 001 10 1 Tube copper 1 4 OD x 8 length 333018 001 11 1 Ball valve 3 way 1 4 576008 649 12 1 Hub conduit liquid tight 1 2 zinc 576010 715 13 3 Conduit clamp 2 steel std duty 514100 478 1...

Страница 9: ...m and necessary bolts nuts and washers from the included Universal Sensor Mounting kit Wrap the rubber shim item 10 in Table 1 around the sensor before inserting it into the clamp The VPS sensor must...

Страница 10: ...VPS wiring with wire nuts see Figure 6 For Wireless installations skip Steps 11 13 The VPS sensor connects to a TLS RF transmitter not to field wiring from the TLS Console see manual 577013 964 for in...

Страница 11: ...enser 2 or 3 common main vapor return line Pressure Sensor Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of...

Страница 12: ...2 or 3 common main vapor return line Pressure Sensor Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of dispe...

Страница 13: ...Wrap rubber shim from kit around sensor before inserting in clamp Pressure sensing port Cable Vapor return line shear valve Cord grip Base of dispenser cabinet 797 9 eps Pitch to drain 1 4 vertical p...

Страница 14: ...sensor before inserting in clamp Pressure sensing port Pitch to drain 1 4 vertical per 12 horizontal 12 4 11 2 2 2 2 3 2 1 10 OR Seal off customer supplied Conduit to TLS Console Cable Cord grip Flow...

Страница 15: ...ng port 3 1 10 Seal off customer supplied Conduit to TLS Console Cable Cable Cord grip Flow Meter and Pressure Sensor wiring can share the same conduit to console Observe polarity Required Y fitting f...

Страница 16: ...wn in A bend pak along long length 3 As shown in B firmly squeeze the RED SIDE of the resin forcing it through the center seal and into BLACK SIDE 4 Mix thoroughly to a uniform color by squeezing cont...

Страница 17: ...4 Figure 8 Direct Wired VPS Connects to Available TLS 450PLUS USM Module Position Figure 9 Direct Wired VPS Connects to Available TLS 3XX Smart Sensor Interface Module Position For wireless configurat...

Страница 18: ...e item 2 in Table 2 such that the VPS cable outlet is facing up and the pressure sensing port tube in the base of the sensor is facing down The symbol on the panel should be facing upward Use the four...

Страница 19: ...of the tube up and estimate the length needed to loop from the bottom of the drying tube over to the vent port off center of the VPS Cut the Tygon tubing at the estimated length approximately a foot...

Страница 20: ...VPS Installation Vapor Vent Stack Installation Wired VPS 1717 Figure 10 Locating Direct Wired VPS Sensor Enclosure on Vapor Vent Stack...

Страница 21: ...VPS Installation Vapor Vent Stack Installation Wired VPS 18 Figure 11 Direct Wired VPS Sensor Installed in Vapor Vent Stack Enclosure...

Страница 22: ......

Отзывы: