7
Troubleshooting Guide
HydrX Quick Help - ATG Control
Section 5 - HydrX System Alarm Troubleshooting
get it to align with the bottom of the filter compartment. Once aligned, press the filter down to seat it fully (reference manual
577014-473 for correct filter installation).
7. Turn off the submersible pump power, close STP adapter ball valve and then remove, inspect, and clean or replace the
siphon cartridge on the top of the HydrX manifold (refer to Manual 577014-478 for Siphon Cartridge servicing instructions)
8. Inspect the drain valve to ensure it is not stuck open.
TROUBLESHOOTING TIPS
Accessing FCC Manual Control
1. Go to the Self Diag. screen on the FCC as follows:
a. Touch and hold the upper left corner of the FCC display status bar (about 3 seconds) until the Maintenance screen
appears (see Figure 5).
b. When the Maintenance screen appears touch the
System Mode
button (see Figure 6).
c. On the System Mode Top Page screen, touch the
Main Menu
button (see Figure 7.
d. On the Main Menu screen touch the
Self Diag
button (see Figure 10)
Figure 10. Main Menu Screen
e. On the Self Diag screen touch the
I/O
button (see Figure 11)
Figure 11. Self Diag. Screen
f. On the I/O screen touch the
IN OUT
button (see Figure 12)
Figure 12. I/O Screen