background image

 

 

TLC3-FCR-2T-U Engineering Manual

 

 

Doc: 70-00-0203, V3.0 Date: 20121119 

© Vector Controls GmbH, Switzerland

mailto:[email protected]

 

Page 6 

Subject to alteration 

Operation with OPR-1 

The deluxe version may be alternatively operated with an infrared remote 

controller.  
 
1.

 

Mode indication, Auto, Dry, Cool, Fan, Heat 

2.

 

2-digit display of setpoint 

3.

 

Fan indication 

4.

 

4-digit display of current time or delayed switching time 

5.

 

Economy button: Toggles Economy/Comfort mode 

6.

 

Mode button, changes operation modes 

7.

 

UP/DOWN Button: Set point adjustment buttons 

8.

 

FAN Button: Changes fan speed, low – medium – high or Auto 

9.

 

Boost button, activates full output for 5 Minutes 

10.

 

Time related buttons: Timer, Hour, Minute 

11.

 

POWER Button: Operation mode ON – OFF 

Switching ON 

The unit is switched on by pressing the POWER button. It will start up in comfort 

mode. 

Changing between COMFORT and ECONOMY 

Pressing the SLEEP button toggles between ECONOMY and COMFORT modes. 

Switching OFF 

Pressing the POWER while the unit is on, will switch the unit off. The current time will be displayed in the LCD of OPR-1.  

Changing of set points 

Only the set points for the temperature loop may be changed. Set point range is 15 to 30 °C. 

Changing of fan speeds 

Repeatedly pressing the fan speed button steps through low, medium, high and automatic fan speeds. Automatic fan 

speed will not be activated in FAN ONLY mode.  

Boost 

Pressing the boost button activates a 5 minute boost. The output will be fully opened for the period of 5 minutes 

independent of demand. This may be used to change stale air during a meeting break or when entering the room.  

Clock settings 

The remote controller contains a daytime clock. In order to set the clock, press HOUR and MINUTE button together 

until the clock starts blinking. Then set the correct time with the HOUR and MINUTE buttons. Confirm by pressing the 

TIMER button.  The clock of the OPR will set the clock of the controller.  

Delayed switching 

The unit may be delayed switched on or off using the timer button. Pressing the timer button once will display Timer 

ON if currently in OFF mode or TIMER OFF if currently in ON mode. Set the time when the unit is supposed to switch 

on or off using the HOUR and MINUTE buttons.  

Mode changes 

Repeatedly pressing the mode button may activate the following operation modes: HEAT, COOL and FAN ONLY. The 

mode change may be disabled using the UP parameters. 
 
Note:  
The remote controller is currently only available in °C mode.  

 

 

 

 

 

 

 

 

 

 

11 

Содержание TLC3-FCR-2T-U

Страница 1: ...ves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC t...

Страница 2: ...idity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004...

Страница 3: ...unting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front...

Страница 4: ...on to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode w...

Страница 5: ...ptions d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switch...

Страница 6: ...the temperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan s...

Страница 7: ...UP 01 Enable change of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 0...

Страница 8: ...FC 05 Switching Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the a...

Страница 9: ...nary output DO4 open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0...

Страница 10: ...TLC3 FCR 2T U Engineering Manual Doc 70 00 0203 V3 0 Date 20121119 Vector Controls GmbH Switzerlandmailto info vectorcontrols com Page 10 Subject to alteration Notes...

Отзывы: