TLC3-FCR-2T-U Engineering Manual

 

 

Doc: 70-00-0203, V3.0 Date: 20121119 

© Vector Controls GmbH, Switzerland

mailto:[email protected]

 

Page 10 

Subject to alteration 

Notes: 

Содержание TLC3-FCR-2T-U

Страница 1: ...ves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC t...

Страница 2: ...idity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004...

Страница 3: ...unting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front...

Страница 4: ...on to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode w...

Страница 5: ...ptions d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switch...

Страница 6: ...the temperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan s...

Страница 7: ...UP 01 Enable change of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 0...

Страница 8: ...FC 05 Switching Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the a...

Страница 9: ...nary output DO4 open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0...

Страница 10: ...TLC3 FCR 2T U Engineering Manual Doc 70 00 0203 V3 0 Date 20121119 Vector Controls GmbH Switzerlandmailto info vectorcontrols com Page 10 Subject to alteration Notes...