background image

 

 

TLC3-FCR-2T-U Engineering Manual

 

 

Doc: 70-00-0203, V3.0 Date: 20121119 

© Vector Controls GmbH, Switzerland

mailto:[email protected]

 

Page 5 

Subject to alteration 

Manual heat – cool change 

To manually change heating or cooling mode press the OPTION key for more than 2 seconds. Access to manual heat – 

cool change may be disabled by parameters. 

For standard models: Press OPTION > 2 sec. SEL and H-C is displayed.  
For deluxe models: Press OPTION > 2 sec. SEL and current time is displayed.  
 

Press UP key twice. SEL and H-C is displayed. 

Press OPTION again to toggle Heating, Cooling and Fan only modes.  

SEL 
  H-C 

 

Clock operation  

The deluxe model contains a quartz clock with battery back-up. Up to 4 time schedules with each 4 mode changes 

based on time and day of the week may be programmed. A blinking clock indicates that the time has not been setor if 

the unit was without power for longer than 48 hours. The time needs to be set to allow time schedules to operate. 

 

Clock setup 

Press OPTION > 2 sec. SEL and current time displayed 
Press OPTION< 2 sec. to change time, 

Minutes blink: UP/DOWN to changes, OPTION to save, 
Hours blink: UP/DOWN to changes, OPTION to save, 

Press OPTION to save time, 

DAY1 blinks: UP/DOWN to change, OPTION to save 

SEL 
  00:00 
  DAY1 (Mon) 

 

Creating time schedules 

Step 1: Selection and enabling of time schedules 

Press OPTION > 2 sec. SEL and current time displayed 
Press UP:  

SEL and PRO displayed, clock symbol blinks 

Press OPTION:  

PRO1 shows with 1 blinking. UP/DOWN select time schedule group 

Press OPTION 

OFF/ ON blinks, UP/DOWN to change, OPTION to save 

SEL 
  PRO 

 

Pro1-Pro4 
  OFF/ON 

 

Step 2: Select weekdays 

This time schedule will be active during the selected weekdays  
Press UP/DOWNto step through available options:  

d1-7, d1-6, d1-5, d6-7, day1, day2, day3, day4, day5, day6, day7 
Day 1 stands for Monday, day 2 for Tuesday and so forth 

Press OPTION to save day selection 

 

Pro1 
d1-7

 

Step 3: Selected action of first switching event  

One bar on the right side indicates the first switching event 
Press UP/DOWN to select action for first switching event: 

No =   switching eventnot active 
OFF =   switches unit off, Reset (UP17) active if switched to ON manually.  

Eco =   sets operation mode to On and Economy (Not occupied),  
 

reset (UP17) active if set to comfort manually 

On =   sets operation mode to On and Comfort (Occupied) 
Uni =   University mode, Reset (UP17) not active if manually activated 

Press OPTION to select switching time of first event 

Pr01 
    no 

 
 

 Step 4: Selected time of first switching event  

Press UP/DOWN to select switching time: 

Select switching time 00:00 to 23:45 in 15-minute steps  

Press OPTION to complete and select action of second switching event 

Pr01 
   08:00

 

Step 5: Select actions and time of switching event 2 - 4  

Repeat Step 3 and Step 4 for the remaining switching events.  

If a switching event is not needed, set it to “no” 
The bars on the right side indicate number of switching event 

After completing the 4

th

 switching event, the process returns to the selection of the time schedule on step 1.  

Pr01 
   08:00

 

 

 

UNI: University mode: This switching mode is used for rooms such as lecture rooms and auditoriums that might 

be occupied during a certain time. During this time the reset is not active. The unit will not start itself when UNI 

mode is active. It still needs to be manually activated. This is to avoid unnecessary heating or cooling of such 

rooms while they are not occupied.  

 

A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined. 

See chapter operation, advanced settings for instructions on how to set the time. 

 

Access to time schedules may be disabled with UP-04 

Содержание TLC3-FCR-2T-U

Страница 1: ...ves or 3 point on off or floating control of one 3 point valve General Description The TLC3 FCR 2T is a stand alone electronic fan coil controller with one control loop The TLC3 FCR 2 features 1 NTC t...

Страница 2: ...idity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 C 70 C 13 F 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004...

Страница 3: ...unting plate 3 Ensure that the jumpers are set correctly 4 Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate 5 Carefully lower the front...

Страница 4: ...on to operate accordingly Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 41 F All heating outputs will be fully opened Frost protection mode w...

Страница 5: ...ptions d1 7 d1 6 d1 5 d6 7 day1 day2 day3 day4 day5 day6 day7 Day 1 stands for Monday day 2 for Tuesday and so forth Press OPTION to save day selection Pro1 d1 7 Step 3 Selected action of first switch...

Страница 6: ...the temperature loop may be changed Set point range is 15 to 30 C Changing of fan speeds Repeatedly pressing the fan speed button steps through low medium high and automatic fan speeds Automatic fan s...

Страница 7: ...UP 01 Enable change of set points ON OFF ON Enabled UP 02 Enable manual control of fan speeds ON OFF ON Enabled UP 03 Enable change of heating cooling mode ON OFF W00 ON Enabled W01 OFF Disabled UP 0...

Страница 8: ...FC 05 Switching Span Heating Setting this value to 0 disables the auto fan speed function in heating mode 0 10 0 C 20 0 F 1 5 C 3 F FC 06 Switching Span Cooling Setting this value to 0 disables the a...

Страница 9: ...nary output DO4 open DO5 close 2 3 point floating output DO4 open DO5 close 0 2 0 Binary PWM FC 17 Running Time in 3 point mode 0 255 s 90 s FC 18 PWM cycle timeheating 0 disables PWM mode 0 100 min 0...

Страница 10: ...TLC3 FCR 2T U Engineering Manual Doc 70 00 0203 V3 0 Date 20121119 Vector Controls GmbH Switzerlandmailto info vectorcontrols com Page 10 Subject to alteration Notes...