Page 9 

Remote Enable: 

The unit may be remote controlled by using the external input as open contact input. Opening the binary input will 
force the unit into the OFF operation mode. The operation mode cannot be overridden by using the terminal or time 
schedules. Activating the digital input returns control of the operation mode to the terminal and time schedule.  

Occupation Sensor 

Remotely control comfort and economy mode for example with an occupation sensor or key switch. If the binary input 
is deactivated for a selectable time the unit will change to stand by mode. For a key switch, set delay time to 0.  

Heat / Cool change:  

Control heat and cool setting of your controller from a central location. Choose if heat or cool is to be active when 
contact is open. 

Auto Changeover with supply media temperature sensor:  

The external input may be used to automatically determine heating or cooling mode by measuring the temperature of 
the supply media. Connect a qualified passive sensor to the external input. Heating mode is activated once the supply 
temperature is above the heating limit. Cooling is activated when the supply temperature is below the cooling limit. 
The limits may be defined in software. Standard is 16°C (61°F) for cooling and 28°C (83°F) for heating.  

Auto Changeover with outside temperature sensor:  

The external input may be used to automatically determine heating or cooling mode by measuring the outdoor 
temperature. Connect a qualified passive sensor to the external input. Heating mode is activated once the supply 
temperature is below the heating limit. Cooling is activated when the supply temperature is above the cooling limit. 
The limits may be defined in software. Standard is 16°C (61°F) for heating and 28°C (83°F) for cooling.  

Key Card:  

The external input is connected to a key card in hotels. If input is closed the unit is in normal operation with the 
setpoint being chosen by the end user. When input is opened, the unit will change to economy mode. A preset setpoint 
defined with FC12 for heating and FC13 for cooling is used instead of the selected setpoint.  The setpoint shift feature 
is disabled.  

Содержание TLC-BCR-T

Страница 1: ...diator control chilled ceiling floor heating Simple individual room control for hotel rooms meeting rooms etc General Description The TLC BCR T is a stand alone electronic binary controller with one c...

Страница 2: ...Design and Installation The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS pl...

Страница 3: ...re sensor or open contact 6 GND Signal Ground Subject to alteration Space required in flush mounting box H x W x D 60 x 50 x 30mm 2 4 x 2 0 x 1 2 in Distance for mounting screws Horizontal and vertica...

Страница 4: ...wered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 4...

Страница 5: ...ture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually ac...

Страница 6: ...UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small digits Pressing the OPTION button will enter the clock setup The minutes ar...

Страница 7: ...the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Sett...

Страница 8: ...to reduce the startup load of large motors multiple stages will be switched on and off step by step Binary Control T Room Temperature wH Setpoint Heating Mode DZ Dead Zone QH Offset Heating wC Setpoi...

Страница 9: ...mperature of the supply media Connect a qualified passive sensor to the external input Heating mode is activated once the supply temperature is above the heating limit Cooling is activated when the su...

Страница 10: ...imum running time 0 255s 10s BC 10 Delay ON Minimum stopping time 0 255s 10s BC 11 2 pipe or 4 pipe system OFF 2 pipe ON 4 pipe system ON OFF ON BC 12 Dead zone between heating cooling set point XDZ 0...

Отзывы: