TLC-BCR-T Engineering Manual

 

 

Doc: 70-00-0083, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 7 

Setting of user parameters 

The TLC-BCR-T is an intelligent controller and can be adapted to fit perfectly into your application. The control 
operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.  
The parameters may only be accessed by entering a code. There are two levels of parameters: User operation 
parameters for access control settings and Expert parameters for control functions and unit setup. The codes for user 
levels and expert levels are different. Only control experts should be given the control parameter code.  
The parameters can be changed as follows: 

1.

 

Press UP and DOWN button simultaneously for three seconds. The display shows the software version in the 

large digits and the product code in the small digits.  

2.

 

Pressing the OPTION button will indicate CODE on the small digits and 000 on the large digits. 

3.

 

The code for accessing the user parameters is 009 

4.

 

Select this using UP or DOWN buttons. 

5.

 

Press OPTION button after selecting the correct code.  

6.

 

Once logged in, the parameter is displayed immediately. 

7.

 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. The 

MIN and MAX symbols show up and indicate that the parameter may be modified now. Use UP or DOWN 
buttons to adjust the value. 

8.

 

After you are done, press OPTION or POWER in order to return to the parameter selection level.  

9.

 

Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button 

is pressed for more than 5 minutes. 

User Parameters 

Parameter Description 

Setting 

Range Factory 

Setting 

UP 00 

Enable change of operation modes  

ON, OFF 

ON (Enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (Enabled) 

UP 02 

Parameter not used 

ON, OFF 

ON (Enabled) 

UP 03 

Enable change of heating/cooling mode 

ON, OFF 

W00: ON (Enabled) 
W01: OFF (Disabled) 

UP 04 

Enable access to Time programs 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure:  
0 = Switched OFF, 1 = Switched ON, 2 = state before power failure 

0, 1, 2 

UP 06 

Enable Economy functionality 

ON, OFF 

ON (Economy ) 

UP 07 

Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibration value of temperature sensor . This value is calibrated at 
manufacturing of the thermostat. If required it is possible to shift 
the temperature –10° to +10° in 0.1° K steps.  

-10…10 0 

UP 09 

Enable frost protection 

ON, OFF 

W00 = ON  

(Frost Protection) 

W01 = OFF 

(No Frost Protection) 

UP 10 

Select contents of Large LCD display in standard mode: 

00 = OFF 
01 = Setpoint 
02 = Temperature Sensor 
03 = Output State 
04 = Clock 
05 = Alternate Temperature Sensor 

0…5 02 

 

Temperature 

UP 11 

Select contents of small LCD display in standard mode 
(use table of UP 10) 

0…5 04 

Deluxe: 

 

show clock 

01 Standard:  

show setpoint 

UP 12 

Deluxe only 

Clock display type:  
OFF  = Show 24hour clock 
ON   = Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 13 

Deluxe only 

Reset timer for override mode: Only available for deluxe version 

= Reset of override mode is not active.  

1…255 = delay in minutes to switch off device if ON/Economy 

mode is activated while the unit is scheduled to be in OFF 
mode 

0…255 60 

(Min) 

 
 

 

Subject to alteration 

Содержание TLC-BCR-T

Страница 1: ...diator control chilled ceiling floor heating Simple individual room control for hotel rooms meeting rooms etc General Description The TLC BCR T is a stand alone electronic binary controller with one c...

Страница 2: ...Design and Installation The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS pl...

Страница 3: ...re sensor or open contact 6 GND Signal Ground Subject to alteration Space required in flush mounting box H x W x D 60 x 50 x 30mm 2 4 x 2 0 x 1 2 in Distance for mounting screws Horizontal and vertica...

Страница 4: ...wered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 4...

Страница 5: ...ture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually ac...

Страница 6: ...UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small digits Pressing the OPTION button will enter the clock setup The minutes ar...

Страница 7: ...the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Sett...

Страница 8: ...to reduce the startup load of large motors multiple stages will be switched on and off step by step Binary Control T Room Temperature wH Setpoint Heating Mode DZ Dead Zone QH Offset Heating wC Setpoi...

Страница 9: ...mperature of the supply media Connect a qualified passive sensor to the external input Heating mode is activated once the supply temperature is above the heating limit Cooling is activated when the su...

Страница 10: ...imum running time 0 255s 10s BC 10 Delay ON Minimum stopping time 0 255s 10s BC 11 2 pipe or 4 pipe system OFF 2 pipe ON 4 pipe system ON OFF ON BC 12 Dead zone between heating cooling set point XDZ 0...

Отзывы: