TLC-BCR-T Engineering Manual

 

 

Doc: 70-00-0083, Date: 20081219 

© 2008 Vector Controls Ltd. 

Page 4 

Display and Operation 

The operation terminal uses an LCD display and four operation buttons.  

 

Legend: 

1.

 

4-digit display of current value, time,  
control parameter or set point. 

2.

 

Unit of displayed value, °C, °F, % or none 

3.

 

Indication of active binary stage 

4.

 

4-digit display of current value, time, control 
parameter or set point. 

5.

 

Operation modes: 

Comfort mode, 

 Economy mode, , OFF Energy Hold Off  

6.

 

Symbols:  

Heating Active 

Cooling Active 

Schedule Set 

Manual Override 

Frost Protection 

 

 

 

 

 

7.

 

Buttons for operating the controller 

POWER button: Pressing the button less than 2 sec toggles Economy and comfort modes. Pressing 
the button for more than 2 seconds switches the unit off.  

UP and DOWN buttons: change setpoints and parameters

  

OPTION button: used for changing fan speed and accessing advanced setup. Acts as Enter in 
parameter changing menu. 

8.

 

Activation of heating or cooling coil is indicated by the blinking of the respective symbol in the lower left 
corner of the display. 

Power Failure 

All the parameters and set points are memorized and don’t need to be reentered. Depending on UP05 the unit will 
remain switched off, switch on automatically or return to the operation mode it was in before the power failure.  
The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor. The time 
does not need to be re-entered after a power failure.  

Frost Protection 

The controller will enter frost protection mode if the room temperature drops below 5°C (41°F). All heating outputs will 
be fully opened. Frost protection mode will be left once the temperature reaches 10°C  (50°F). Frost protection display 
will remain until a button is pressed. Frost protection can be enabled/disabled using user parameter UP-09 

Operation Modes 

 

Comfort: The unit is in full operation mode. All the control functions are operating according to their setpoints. 

The unit displays occupied mode.  

 

Economy: The set point is shifted according to parameters FC-04. The heating parameter is shifted down and 

cooling parameter up. The unit displays unoccupied mode. Fan speeds are limited to maximum medium fan 
speed. Economy operation may be disabled with UP-06.  

 

Energy Hold Off (EHO): The unit is switched off. All outputs are off. The temperature will still be monitored in 

order to activate the unit in case of frost. (If frost protection is enabled). Off and current time is displayed.  

Activation of operation modes 

 

Via operation terminal 

 

Clock: (Deluxe version only) Operation modes may automatically be switched according to daytime and 
weekday. The clock symbol will be indicated if time programs are activated.  

 

Infrared Remote Controller: (Deluxe version only) use OPR-1 to control the unit remotely 

 

Via external contact (comfort/economy) 

Note: Time programs will not operate, if operation mode is set to OFF by remote control or if time is not set.  

2

 

3

 

4

 

7

 

1

 

6

 

5

 

Содержание TLC-BCR-T

Страница 1: ...diator control chilled ceiling floor heating Simple individual room control for hotel rooms meeting rooms etc General Description The TLC BCR T is a stand alone electronic binary controller with one c...

Страница 2: ...Design and Installation The unit consists of three parts 1 The mounting plate made of galvanized steel 2 The power case made of fire proof ABS plastic 3 The front part made of white fire proof ABS pl...

Страница 3: ...re sensor or open contact 6 GND Signal Ground Subject to alteration Space required in flush mounting box H x W x D 60 x 50 x 30mm 2 4 x 2 0 x 1 2 in Distance for mounting screws Horizontal and vertica...

Страница 4: ...wered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter frost protection mode if the room temperature drops below 5 C 4...

Страница 5: ...ture rooms and auditoriums that might be occupied during a certain time During this time the reset is not active The unit will not start itself when UNI mode is active It still needs to be manually ac...

Страница 6: ...UP 03 Clock Setup and Time Schedule only available on Deluxe versions Clock Setup The current time is displayed in the small digits Pressing the OPTION button will enter the clock setup The minutes ar...

Страница 7: ...the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User Parameters Parameter Description Setting Range Factory Sett...

Страница 8: ...to reduce the startup load of large motors multiple stages will be switched on and off step by step Binary Control T Room Temperature wH Setpoint Heating Mode DZ Dead Zone QH Offset Heating wC Setpoi...

Страница 9: ...mperature of the supply media Connect a qualified passive sensor to the external input Heating mode is activated once the supply temperature is above the heating limit Cooling is activated when the su...

Страница 10: ...imum running time 0 255s 10s BC 10 Delay ON Minimum stopping time 0 255s 10s BC 11 2 pipe or 4 pipe system OFF 2 pipe ON 4 pipe system ON OFF ON BC 12 Dead zone between heating cooling set point XDZ 0...