Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

 

Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

 

Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

Doc: 70-00-0384A V1.0 20160523 

© Vector Controls GmbH, Switzerland 

Subject to alterations 

TCI-W13-U-H, TCI-W23-U-H wall mounted universal controller 
with internal temperature and humidity sensor 

General description 

The TCI-W is a stand-alone wall mounted electronic universal controller with two autonomous control loops. 
Each control loop may use up to 2 PID sequences and 6 binary sequences. The TCI-W13 features 
1 independent control loop, 1 universal input, 1 binary relay output and 2 analog outputs, the TCI-W23 offers 
2 independent control loops, 1 universal input, 1 passive input, 1 binary relay output and 2 analog outputs. A 
detailed configuration is possible by following a simple setup routine. The TCI can be configured using the 
standard operation terminal. No special tool or software is required. 

Ordering, name convention 

TCI-W23-U  

Optional functions and housing 

  │ │││ └─────

 

Housing 

U = 2 x 4” type housing, blank = square housing 

  │ ││└─────── 

In-/outputs:  

1 = 1UI, 1DOR, 2AO, 2 = 1UI, 1Passive In, 1DOR, 2AO 

  │ │└──────── 

Control loops: 

1 = 1 control loop, 2 = 2 control loops 

  │ └─────────  

Mounting:  

W = Wall mounted 

  └──────────── 

Series indication 

TCI 

 

Item name 

Item code 

Loop 

Int. 

temp. 

Int. 

humidity 

UI 

TI 

DO 

relays 

AO 

Option 

TCI-W11 

40-10 0073 

Standard 

TCI-W11-H 

40-10 0162 

RH Sensor 3% 

TCI-W22 

40-10 0075 

Schedules 

TCI-W22-H 

40-10 0077 

RH Sensor 3% 

TCI-W13-U 

40-10 0174 

Standard 

TCI-W13-U-H  40-10 0175 

RH Sensor 3% 

TCI-W23-U 

40-10 0176 

Schedules 

TCI-W23-U-H  40-10 0177 

RH Sensor 3% 

Accessories 

AES1-HT-A2 

40-50 0067 

 

 

 

 

 

RH Sensor 2% 

AES1-HT-A3 

40-50 0068 

 

 

 

 

 

RH Sensor 3% 

AES1-HT-A5 

40-50 0069 

 

 

 

 

 

RH Sensor 5% 

Selection of actuators and sensors 

Temperature sensors: Use only our approved NTC sensors to achieve maximum accuracy.  Recommended 
is SDB-Tn10 as duct sensor, SRA-Tn10 as room sensor.  

Modulating actuators: Choose actuators with an input signal type of 0...10 VDC or 4...20 mA. Minimum and 
maximum signal limitations may be set in software. 

Binary auxiliary devices: E.g. pumps, fans, on/off valves, humidifiers, etc.  Do not directly connect devices 
that exceed the maximum limits as described under technical data. Observe startup current on inductive 
loads. 

Jumper configuration 

Jumpers are mounted vertically only.  
 

1. 

AO - Selection of output signal type:  

o

 

Left position: voltage output (0…10 V), 

factory default

 

o

 

Right position: current output (0…20 mA) 

 

2. 

AI - Selection of input signal type:  

o

 

Left position: voltage input (0…10 V), 

factory default

 

o

 

Middle position: current input (0…20 mA)  

o

 

Right position: RT or dry-contact input 

 

Mounting location 

  Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of 

average temperature. 

  Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

  Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

  Location of mounting is less critical if external temperature sensors are used. 

Installation 

1. 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2. 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding 
screw is facing to the ground. Make sure the mounting screw heads do not stand out more than 

mm (0.2”) off the surface of the mounting plate.  

3. 

Ensure that the jumpers are set correctly.  

4. 

Slide the two latches located on the top of the front part into the hooks at the upper side of the 
mounting plate.  

5. 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue 
pressing in a gentle way until the front part is fully connected. While inserting the connectors, a 
slight resistance can be felt. This is normal. Do not use excessive force!  

6. 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the 
front part to the mounting plate. This screw is located on the front lower side of the unit. There is no 
need to tighten the screw too much. 

Technical specification 

Warning! 

This device is intended to be used for comfort applications. Where a device failure endangers human life 

and/or property, it is the responsibility of the owner, designer and installer to add additional safety devices to prevent 
or detect a system failure caused by such a device failure. The manufacturer of this device cannot be held liable for 
any damage caused by such a failure.  
Failure to follow specifications and local regulations may endanger life, cause equipment damage and void warranty. 
 

Power supply 

Operating voltage 

24 VAC 50/60 Hz ± 10% 

 

Power consumption 

max. 3 VA 

 

Electrical connection 

Terminal connectors,  
wire 0.34…2.5 mm

2

 (AWG 22

…13) 

 

Clock backup 

24 hours (deluxe version only) 

Signal inputs 

Analog inputs 

Input signal 
Resolution 
Impedance 

UI1, UI2 
DC 0...

10V or 0…20mA 

39 mV or 0.078 mA 
Voltage: 98kΩ  current: 240Ω 

 

Temperature inputs 

Range 
 
Resolution 
Accuracy 

RT internal, external (Sxx-Tn10 sensor) 
Int. NTC: 0…50 °C (32…122 °F) 
Ext. NTC: -

40…140 °C (-40…284 °F) 

0.1 K 
-

40…0 °C (-40…32 °F): 0.5 K 

0…50 °C (32…122 °F): 0.2 K 
50…100 °C (122…212 °F): 0.5 K 
> 100 °C (> 212 °F): 1 K 

 

Humidity sensor AES-HT-Ax: 

Range 
Measuring accuracy 
Hysteresis 
Repeatability 
Stability 

Capacity sensor 
0…100% RH 
See figure below 

 1% 

 0.1% 

< 0.5% / year 

Signal outputs 

Analog outputs 

Output signal 
Resolution 
Maximum load 

AO1  
DC 0...

10V or 0…20mA 

39 mV, 0.078 mA 
Voltage: 

 5

kΩ current: 

25

0Ω 

 

Relays outputs 

Type of disconnection  
AC voltage 
DC voltage 

 
Micro-interruption 
0…48 VAC, 2(1.2)A max. Observe local regulations 
0…30 VDC, 2A max.  

 

Insulation strength 

between relays contacts and system 
electronics:

 

 
 
2000VAC to EN 60730-1

 

Environment 

Operation 

Climatic conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3K5 
0…50 °C (32…122 °F) 
<95% RH non-condensing 

 

Transport & Storage 

Climatic conditions 
Temperature 
Humidity 
Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3K3 and class 1K3 
-

25…70 °C (-13…158 °F) 

<95%RH non-condensing 
class 2M2 

Standards 

 

conform according to  
EMC Standard  
EMEI Standard 73/23/EEC 

EN 61000-6-1/ EN 61000-6-3 

 

Product standards 

Automatic electrical controls for 
household and similar use 
special requirement on temperature 
dependent controls 

 
EN 60730-1 
 
EN 60730-2-9 

 

Degree of protection 

IP30 to EN 60529 

 

Pollution class 

II (EN 60 730-1) 

 

Safety class 

II (IEC 60536) if voltage on DO > 48V 
III (IEC 60536) if voltage on DO < 48V 

 

Overvoltage category 

I (EN 60730-1) 

Housing 

Materials:  

Cover, back part 

 

Mounting plate 

Fire proof ABS plastic (UL94 class V-0) 
Galvanized Steel 

General 

Dimensions (H x W x D) 

Front part: 

112 x 73 x 15 mm (4.4” x 2.9” x 0.6”) 

Power case: ø 58 x 32 mm (ø 2.3” x 1.3”) 

 

Weight (including package) 

TCI-W13-U-H = 260g (8.1 oz)  
TCI-W23-U-H = 270g (9.5 oz) 

Power failure 

Upon power-interruption, all parameters and set points 
are memorized in non-volatile memory, and therefore 
do not have to be re-entered. 

Error messages 

Err1:

 

An assigned input is not enabled or 
missing. All control loops, functions and 
outputs tied to this input will be disabled. 
Verify input connections, jumper 
settings and parameter settings for the 
input involved.  

Err3:

 

A function refers to a disabled input. 
Disable the function or enable the input.  

Err4:

 

Internal failure. Product must be replaced. 

 

Wiring diagram 

Warning: Live electrical components! 

During installation, testing, servicing and troubleshooting of Vector Controls products, it may be necessary to 
work with live electrical components. Have a qualified licensed electrician or other individual who has been 
properly trained in handling live electrical components perform these tasks. Failure to follow all electrical 
safety precautions when exposed to live electrical components could result in death or serious injury.

 

 

Description 

G0 

Power supply:  

0V, -24VDC; common for power supply, analog in- and outputs 

Power supply:  

24VAC, +24VDC 

X

U1

 

Universal input: 

NTC 10kΩ @ 25°C (77 °F) or open contact,  

 

 

0…10VDC or 0…20 mA (selectable by jumper) 

X

T2

 

Passive input: 

NTC 10kΩ @ 25°C (77 °F) or open contact 

Y

B1

 

Binary output: 

Potential free relays contacts (see technical specification) 

Y

M1

, X

M2

 

Analog outputs:  

0…10 V or 0…20 mA (selectable by jumper) 

X

T1

 

Internal temperature input 

X

H1

 

Internal humidity input if AES-HT is inserted 

 

Dimensions mm (inch) 

 

A O  

 

U I  

 0

…1

0V

 

 0

…2

0mA

 

   0

…1

0V

 

 0

…2

0mA

 

 R

T

 o

co

n

ta

ct

 

 

 

 

 

 

 

X

H1 

X

T1 

0V (COM) 

24V AC/DC 
 

TCI-W13-U-H 

G0 

0

…48VAC, 0…30VDC 


Q13 

1    5  

G0   Y1 

Y

M1

 

  1       7 
  G0    X1 

X

U1 

Y

B1

 

Q14      

0V AC 

1    6  

G0   Y2 

Y

M2

 

  1       8 
  G0    X2 

X

H1 

X

T1 

0V (COM) 

24V AC/DC 
 

TCI-W23-U-H 

G0 

0

…48 VAC, 0…30VDC 


Q13 

1    5  

G0   Y1 

Y

M1

 

  1       7 
  G0    X1 

X

U1 

Y

B1

 

Q14      

0V AC 

X

T2 

1    6  

G0   Y2 

Y

M2

 

Figure 1: Max RH-tolerance at 25 °C (77 °F) per 
sensor type 

Relative humidity accuracy 

 %RH 

 %RH 

10  20  30  40 

100 

90 

50  60  70  80 

±1 

±0 

±2 

±3 

±4 

±5 

AES-HT-A2 

AES-HT-A3 

AES-HT-A5 