Controller configuration 

Proceed in the following steps in order to adapt the controller to its application: 
1. 

Set jumpers for inputs and outputs 

2. 

Connect power supply and inputs 

3. 

Program input parameters 

4. 

Program control parameters 

5. 

Program output parameters 

6. 

Test function of unit 

7. 

Switch off power 

8. 

Connect outputs 

9. 

Test control loop 

10. 

Set user settings 

Configuration parameters for firmware version 1.0 

The TCI-Wx3 can be adapted to wide variety of applications. The adaptation is done with parameters. The 
parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware revision. It is therefore important to use 
a matching product version and parameter set. The firmware version is marked on the package box of your 
product. In order to identify the firmware version of an installed controller, press UP and DOWN keys 
simultaneously for three seconds: The display will indicate the firmware version in the upper large digits and 
the revision in the lower small digits. Press the LEFT key to return to normal operation. 

Changing the parameters 

 

1. 

Press UP and DOWN button simultaneously for three seconds. The display will indicate the 
firmware version in the upper large digits and the revision in the lower small digits. Press the 
RIGHT or POWER key to start login 

2. 

CODE is shown in small display.  

3. 

The code for accessing the user parameters is 0009, for control parameters it is 0241 

4. 

Select this using UP or DOWN buttons. 

5. 

Press the RIGHT or POWER button after selecting the correct code.  

6. 

Once logged in the parameter group can be selected with the UP and DOWN key. Enter the 
group with the RIGHT or POWER key.  

7. 

Once the group is selected, the parameter is displayed immediately 

8. 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the 
RIGHT button. Arrows 8 to 10 show up and indicate that the parameter may be modified 
now. Use UP or DOWN buttons to adjust the value. 

9. 

After you are done, press RIGHT or POWER in order to save the new value of the 
parameter and return to the selection level. Pressing LEFT key will discard the value and 
return to the selection menu without saving.  

10. 

Press the LEFT key again so as to leave the parameter menu and return to the group 
selection. Press LEFT key again while in the group selection to return to normal operation.  

11. 

The unit will return to normal operation if no key is pressed for more than 5 minutes. 

User parameters (password 09) 

Parameter  Description 

Range 

Default 

UP 00 

Enable access to operation modes 

ON, OFF 

ON 

UP 01 

Enable access to set points 

ON, OFF 

ON 

UP 02 

Enable manual control in cascade or fan control mode 

ON, OFF 

ON 

UP 03 

Enable change of heating/cooling mode for 2 pipe systems 

ON, OFF 

ON 

UP 04 

Enable access to time programs: 

ON, OFF 

ON 

UP 05 

State after power failure:  
0= off,  1= on,  2= state before power failure 

0, 1, 2 

UP 06 

Enable economy (unoccupied) mode.  
Shift the set point to a lower temperature in winter or higher 
temperature in summer in order to save energy. Economy mode 
may be activated through the POWER button, or with the external 
input (typically for key card switches in hotel rooms or motion 
detectors for meeting rooms.) 

ON, OFF 

OFF 

UP 07 

Celsius or Fahrenheit: ON= Fahrenheit,  OFF= Celsius 

ON, OFF 

OFF (Celsius) 

UP 08 

Show standard display while no key is pressed 

ON, OFF 

ON 

UP 09 

Select contents of large LCD display in standard mode: 

0…5 

00 = OFF 
01 = Input 
02 = Set point 

03 = Analog output  
04 = Binary output 
05 = Clock 

 

 

UP 10 

Select ID of contents of upper digit display 

0…4 

 

Input: 
1= 1T 
2=1H 
3= 1U 
4= 2T 

Set point: 
1= Lp1 
2= Lp2 

Analog or 
floating output: 
1 = AO1 
2 = AO2 

Binary output: 
1 = DO1 
 
 

 

 

UP 11 

Select contents of lower digit display in standard mode 

0…5 

TCI-W13 = 2  
TCI-W23 = 5 

UP 12 

Select ID of contents of lower digit display 

0…4 

UP 13 

Select analog output for display in vertical bar 
00 = OFF 
01 = AO1  
02 = AO2 
03 = Output lp1 
04 = Output lp2 

0…4 

UP 14 

Display heating/cooling state in standard display mode 

ON, OFF 

OFF 

UP 15 

ON =  Alarms blink after being active and need to be confirmed 
OFF=  Alarms are only shown when they are active 

ON, OFF 

ON 

UP 16 

(TCI-W23) 

Clock display type:  OFF = 24-hr,  ON = 12-hr(AM/PM) 

ON, OFF 

OFF 

UP 17 

(TCI-W23) 

Reset timer for manual override of time schedule:  
0=  Not active  
1...255= delay in minutes in case the controller is manually 
switched on in scheduled off or economy mode. The controller will 
return to scheduled function after expiration of this delay.  

0…255 

60 (min) 