Universal controller TCI-W13-U-H/TCI-W23-U-H
Universal controller TCI-W13-U-H/TCI-W23-U-H
Universal controller TCI-W13-U-H/TCI-W23-U-H
Doc: 70-00-0384A V1.0 20160523
© Vector Controls GmbH, Switzerland
Subject to alterations
Controller configuration
Proceed in the following steps in order to adapt the controller to its application:
1.
Set jumpers for inputs and outputs
2.
Connect power supply and inputs
3.
Program input parameters
4.
Program control parameters
5.
Program output parameters
6.
Test function of unit
7.
Switch off power
8.
Connect outputs
9.
Test control loop
10.
Set user settings
Configuration parameters for firmware version 1.0
The TCI-Wx3 can be adapted to wide variety of applications. The adaptation is done with parameters. The
parameters can be changed on the unit without the need of additional equipment.
Identifying the firmware version
The parameters and functionality of controller depend on its firmware revision. It is therefore important to use
a matching product version and parameter set. The firmware version is marked on the package box of your
product. In order to identify the firmware version of an installed controller, press UP and DOWN keys
simultaneously for three seconds: The display will indicate the firmware version in the upper large digits and
the revision in the lower small digits. Press the LEFT key to return to normal operation.
Changing the parameters
1.
Press UP and DOWN button simultaneously for three seconds. The display will indicate the
firmware version in the upper large digits and the revision in the lower small digits. Press the
RIGHT or POWER key to start login
2.
CODE is shown in small display.
3.
The code for accessing the user parameters is 0009, for control parameters it is 0241
4.
Select this using UP or DOWN buttons.
5.
Press the RIGHT or POWER button after selecting the correct code.
6.
Once logged in the parameter group can be selected with the UP and DOWN key. Enter the
group with the RIGHT or POWER key.
7.
Once the group is selected, the parameter is displayed immediately
8.
Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the
RIGHT button. Arrows 8 to 10 show up and indicate that the parameter may be modified
now. Use UP or DOWN buttons to adjust the value.
9.
After you are done, press RIGHT or POWER in order to save the new value of the
parameter and return to the selection level. Pressing LEFT key will discard the value and
return to the selection menu without saving.
10.
Press the LEFT key again so as to leave the parameter menu and return to the group
selection. Press LEFT key again while in the group selection to return to normal operation.
11.
The unit will return to normal operation if no key is pressed for more than 5 minutes.
User parameters (password 09)
Parameter Description
Range
Default
UP 00
Enable access to operation modes
ON, OFF
ON
UP 01
Enable access to set points
ON, OFF
ON
UP 02
Enable manual control in cascade or fan control mode
ON, OFF
ON
UP 03
Enable change of heating/cooling mode for 2 pipe systems
ON, OFF
ON
UP 04
Enable access to time programs:
ON, OFF
ON
UP 05
State after power failure:
0= off, 1= on, 2= state before power failure
0, 1, 2
2
UP 06
Enable economy (unoccupied) mode.
Shift the set point to a lower temperature in winter or higher
temperature in summer in order to save energy. Economy mode
may be activated through the POWER button, or with the external
input (typically for key card switches in hotel rooms or motion
detectors for meeting rooms.)
ON, OFF
OFF
UP 07
Celsius or Fahrenheit: ON= Fahrenheit, OFF= Celsius
ON, OFF
OFF (Celsius)
UP 08
Show standard display while no key is pressed
ON, OFF
ON
UP 09
Select contents of large LCD display in standard mode:
0…5
1
00 = OFF
01 = Input
02 = Set point
03 = Analog output
04 = Binary output
05 = Clock
UP 10
Select ID of contents of upper digit display
0…4
2
Input:
1= 1T
2=1H
3= 1U
4= 2T
Set point:
1= Lp1
2= Lp2
Analog or
floating output:
1 = AO1
2 = AO2
Binary output:
1 = DO1
UP 11
Select contents of lower digit display in standard mode
0…5
TCI-W13 = 2
TCI-W23 = 5
UP 12
Select ID of contents of lower digit display
0…4
1
UP 13
Select analog output for display in vertical bar
00 = OFF
01 = AO1
02 = AO2
03 = Output lp1
04 = Output lp2
0…4
3
UP 14
Display heating/cooling state in standard display mode
ON, OFF
OFF
UP 15
ON = Alarms blink after being active and need to be confirmed
OFF= Alarms are only shown when they are active
ON, OFF
ON
UP 16
(TCI-W23)
Clock display type: OFF = 24-hr, ON = 12-hr(AM/PM)
ON, OFF
OFF
UP 17
(TCI-W23)
Reset timer for manual override of time schedule:
0= Not active
1...255= delay in minutes in case the controller is manually
switched on in scheduled off or economy mode. The controller will
return to scheduled function after expiration of this delay.
0…255
60 (min)