background image

 

 

Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

 

Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

 

Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

Doc: 70-00-0384A V1.0 20160523 

© Vector Controls GmbH, Switzerland 

Subject to alterations 

Control parameters (password 241) 

Warning! Only experts should change these settings! The parameters are grouped according to 
control modules. After completing the logging in, a control module must be selected before 
accessing the parameters.  

Module 

Description 

UI 

Input configuration: 1T, 1H, 1U, 2T 

LP 

Control loops Lp1, Lp2 

AO 

Analog output configuration, AO1, AO2 

DO 

Binary output configuration, do1 

FU 

Special functions 

Internal input configuration (TI1) 

Parameter  Description 

Range 

Standard 

1t 00 

Enable internal sensor 

ON, OFF 

OFF 

1t 01 

Display minimum value 

-

50…205 

1t 02 

Display maximum value 

-

50…205 

100 

1t 03 

Sensor sampling rate(control speed decrease as rate 
increases) 

0…100 

10 

1t 04 

Sensor calibration 

-

10.0…10.0 

1t 05 

Alarm 1 low limit (1T), alarm 3 low limit (1H) 

OFF, ON 

OFF 

1t 06 

Alarm 1/3 low limit values 

-

50…205 °C 

5°C (41°F) 

1t 07 

Alarm 2high limit (1T), alarm 4high limit (1H) 

OFF, ON 

OFF 

1t 08 

Alarm 2/4 high limit values 

-

50…205 °C 

50°C (122°F) 

1t 09 

Hysteresis alarm 1, 2, 3, 4 

0…100 °C 

5°C (10°F) 

1t 10 

Calculate a range of inputs (0= not active):  
1= average,  2= minimum,  3= maximum 

0...3 

Internal input configuration (HI1) 

Parameter  Description 

Range 

Standard 

1H00 

Enable internal sensor 

ON, OFF 

ON 

1H01 

Display minimum value 

-

50…205 

1H02 

Display maximum value 

-

50…205 

100 

1H03 

Sensor sampling rate(control speed decrease as rate 
increases) 

0…100 

10 

1H04 

Sensor calibration 

-

10.0…10.0 

1H05 

Alarm 1 low limit (1T), alarm 3 low limit (1H) 

OFF, ON 

OFF 

1H06 

Alarm 1/3 low limit values 

0…100% 

5% 

1H07 

Alarm 2high limit (1T), alarm 4high limit (1H) 

OFF, ON 

OFF 

1H08 

Alarm 2/4 high limit values 

0…100% 

95% 

1H09 

Hysteresis alarm 1, 2, 3, 4 

0…100% 

5% 

1H10 

Calculate a range of inputs (0= not active):  
1= average,  2= minimum,  3= maximum 

0...3 

External input configuration (UI1, TI2) 

Parameter 

Description 

Range 

Standard 

1u 00 

2t 00 

Signal type (0= not active): 
1= 0...10V or 0...20mA or open contact, 2= 2...10 V or 
4…20 mA, 3= NTC temperature sensor 

0...3 

1u 01 

2t 01 

Display minimum value 

-

50…205 

1u 02 

2t 02 

Display maximum value 

-

50…205 

100 

1u 03 

2t 03 

Analog input display range:  
0= x0.1,  1= x1,  2= x10,  3 = x100 

0...2 

1u 04 

2t 04 

Analog input unit of measure:   
0= no unit,  1= %,  2= °C /°F,  3= Pa 

0...3 

1u 05 

2t 05 

Sensor sampling rate  
(control speed decrease as rate increases) 

0…100 

10 

1u 06 

2t 06 

Sensor calibration  

Range dep 

1u 07 

2t 07 

Alarm 5 low limit (1u), alarm 7 low limit (2t) 

OFF, ON 

OFF 

1u 08 

2t 08 

Alarm 5 low limit value (1u), alarm 7 low limit value (2t) 

-

50…205 °C 

5°C (41°F) 

 1u 09 

2t 09 

Alarm 6 high limit (1u), alarm 8 high limit (2t) 

OFF, ON 

OFF 

1u 10 

2t 10 

Alarm 6 high limit value 1u), alarm 8 high limit value (2t) 

-

50…205 °C  50°C (122°F) 

1u 11 

2t 11 

Hysteresis alarm 5 and 6 (1u), alarms 7 and 8 (2t) 

0…100 °C 

5°C (10°F) 

1u 12 

2t 12 

Calculate a range of inputs (0=not active):  
1= average, 2= minimum, 3= maximum, 4= differential 

0...4 

LP: Control parameters (1L) 

Parameter  Description 

Range 

Standard 

1L 00 

Select loop control input (0= loop disabled): 
1= 1T,  2= 1H,  3= 1U,  4= 2T 

0...4 

1L 01 

Minimum set point limit heating 

per input 

10% 

1L 02 

Maximum set point limit heating 

per input 

90% 

1L 03 

Minimum set point limit cooling 

per input 

10% 

1L 04 

Maximum set point limit cooling 

per input 

90% 

1L 05 

Enable set point compensation (0= disabled) 
1= winter compensation,  2= summer compensation,  3= winter 
and summer 

0...3 

1L 06 

Loop input special (0= normal): 
1= combine loop 1 and loop 2   
2= cascade with reverse sequence of primary loop 
3= cascade with direct sequence primary loop 
4= cascade with both reverse and direct sequence of  
primary loop  

0...4 

1L 07 

Economy mode set point shift: (Function depends on 1L25) 
The comfort (occupied) set point is shifted by the value set with 
parameter. Reduces the heating set point and increases the 
cooling set point.  

per input 

10% 

1L 08 

Dead zone between heating and cooling set points 
The dead zone span lies between the heating and the cooling set 
point. The output is off while the measured value is within the 
dead zone span. A negative dead zone is not possible. 

per input 

5% 

1L 09 

Offset for heating PI sequence 

per input 

1L 10 

Offset for cooling PI sequence 

per input 

1L 11 

P-band heating  

per input 

10% 

1L 12 

P-band cooling  

per input 

10% 

1L 13 

Integral gain heating (0.1 steps) 
low= slow reaction,  high= fast reaction 

0...25.5 

0.0 

1L 14 

Integral gain cooling (0.1 steps) 

0...25.5 

0.0 

1L 15 

Measuring interval integral (seconds) 
low= fast reaction, high value= slow reaction 

0...255 

1L 16 

Action of stages: 
0= cumulative: stage 1 stays on when 2 on comes on 
1= single: stage 1 turns off when 2 on comes on 
2= digital: stage 1 only, stage 2 only, then stage 1 plus 2  

0...2 

1L 17 

Offset for heating/reverse binary sequences 

per input 

0% 

1L 18 

Offset for cooling/direct binary sequences 

per input 

0% 

1L 19 

Switching span heating 

per input 

10% 

1L 20 

Switching span cooling 

per input 

10% 

1L 21 

Switching hysteresis 

per input 

5% 

1L 22 

Switching delay  

0...255s 

30s 

1L 23 

Activation of reverse/direct (heat/cool) sequence 
OFF= activates based on demand 
ON = follows heat/cool state of controller 

ON/OFF 

OFF 

1L 24 

Delay for heat /cool changeover when L23=OFF 

0...255 min 

5 min 

1L 25 

Fixed set point in standby mode  
OFF = Standby set point shift applies 
ON = In standby mode use minimum set point limit as set point in 
heating mode or maximum set point limit in cooling mode 

ON, OFF 

OFF 

1L 26 

Set point compensation range, the maximum range the set point 
is shifted.  
0 = Temperature setback: the set point is shifted towards set point 
limit 

Acc input 

0.0 °C 

LP: Control parameters (2L) 

Parameter  Description 

Range 

Standard 

2L 00 

Select loop control input (0= loop disabled): 
1= 1T,  2= 1H,  3= 1U,  4= 2T 

0...4 

2L 01 

Minimum set point limit heating 

per input 

10°C(50°F) 

2L 02 

Maximum set point limit heating 

per input 

28°C(82°F) 

2L 03 

Minimum set point limit cooling 

per input 

18°C(64°F) 

2L 04 

Maximum set point limit cooling 

per input 

34°C(93°F) 

2L 05 

Enable set point compensation (0= disabled) 
1= winter compensation,  2= summer compensation,  3= winter 
and summer 

0...3 

2L 06 

Loop input special (0= normal): 
1= combine loop 1 and loop 2   
2= cascade with reverse sequence of primary loop 
3= cascade with direct sequence primary loop 
4= cascade with both reverse and direct sequence of  
primary loop  

0...4 

2L 07 

Economy mode set point shift: (Function depends on 2L25) 
The comfort (occupied) set point is shifted by the value set with 
parameter. Reduces the heating set point and increases the 
cooling set point.  

per input 

5.0°C(10°F) 

2L 08 

Dead zone between heating and cooling set points 
The dead zone span lies between the heating and the cooling set 
point. The output is off while the measured value is within the 
dead zone span. A negative dead zone is not possible. 

per input 

1.0°C (2°F) 

2L 09 

Offset for heating PI sequence 

per input 

2L 10 

Offset for cooling PI sequence 

per input 

2L 11 

P-band heating  

per input 

2.0°C(4.0°F) 

2L 12 

P-band cooling  

per input 

2.0°C (4.0°F) 

2L 13 

Integral gain heating (0.1 steps) 
low= slow reaction,  high= fast reaction 

0...25.5 

0.0 

2L 14 

Integral gain cooling (0.1 steps) 

0...25.5 

0.0 

2L 15 

Measuring interval integral (seconds) 
low= fast reaction, high value= slow reaction 

0...255 

2L 16 

Action of stages: 
0=  cumulative: stage 1 stays on when 2 on comes on 
1=  single: stage 1 turns off when 2 on comes on 
2=  digital: stage 1 only, stage 2 only, then stage 1 plus 2  

0...2 

2L 17 

Offset for heating/reverse binary sequences 

per input 

0.0°C (0.0°F) 

2L 18 

Offset for cooling/direct binary sequences 

per input 

0.0°C (0.0°F) 

2L 19 

Switching span heating 

per input 

1.0°C (2.0°F) 

2L 20 

Switching span cooling 

per input 

1.0°C (2.0°F) 

2L 21 

Switching hysteresis 

per input 

0.5°C (1.0°F) 

2L 22 

Switching delay  

0...255 

10 

2L 23 

Activation of reverse/direct (heat/cool) sequence 
OFF=  activates based on demand 
ON =  follows heat/cool state of controller 

ON, OFF 

OFF 

2L 24 

Delay for heat /cool changeover when L23=OFF 

0...255 min 

5 min 

2L 25 

Fixed set point in standby mode  
OFF = Standby set point shift applies 
ON = In standby mode use minimum set point limit as set point 
 in heating mode or maximum set point limit in cooling mode 

ON, OFF 

OFF 

2L 26 

Set point compensation range, the maximum range the set point 
is shifted.  
0 = Temperature setback: the set point is shifted towards  
set point limit 

Acc input 

0.0°C 

Отзывы: