Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

 

Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

 

Universal controller TCI-W13-U-H/TCI-W23-U-H 

 

Doc: 70-00-0384A V1.0 20160523 

© Vector Controls GmbH, Switzerland 

Subject to alterations 

Analog output (1A, 2A) 

Parameter  Description 

Range 

Standard 

1A 00 

Select control loop or special function (0= OFF): 

1= LP1,   
2= LP2 
3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 
4= Manual positioning or time schedule controlled 
(0

…100%) 

5= Transmit value of an input 

0...5 

1A 01 

When 1A00=1 configure output:

 

0= Heating/reverse  
1= Cooling/direct

 

2= Heating and cooling (2 pipe)

 

3= Transmit set point

 

When 1A00 = 4 manual positioning or time schedule controlled 

0 = Time schedule controlled only 
1 = Manual positioning and time schedule controlled 

When 1A00=5, select input (0= function disabled): 

1= 1T, 2= 1H,  3= 1U,  4= 2T

 

0...4 

1A 02 

Type of output signal: OFF= 0...10V, 0...20mA,  ON= 2...10V, 
4...20mA 

ON, OFF

 

OFF 

(0...10V, 

0

…20 mA)

 

1A 03 

Minimum limitation of output signal default and in loop heating 
mode 

0...100%

 

0

 

1A 04 

Maximum limitation of output signal default and in loop heating 
mode 

0...100%

 

100%

 

1A 05 

Minimum limitation of output signal in loop cooling mode 

0...100%

 

0%

 

1A 06 

Maximum limitation of output signal in loop cooling mode  

0...100%

 

100%

 

1A 07 

Choose alarm to set output to 100% (output 0% on conflicting 
alarms) 
 



 

Alarm: 1 2 3 4 5 6 7 8 

Selection 



 

1A 08 

Choose alarm to set output to 0%. (output 0% on conflicting 
alarms) 
 



 

Alarm: 1 2 3 4 5 6 7 8 

Selection 



 

1A 09 

Transmit value (1A00=5): minimum input value 

Acc input 

1A 10 

Transmit value (1A00=5): maximum input value 

Acc input 

Binary output 

– binary control 

Parameter  Description 

Range 

Standard 

1d 00 

Enable digital or PWM output 
OFF= 1d is a digital output 
ON = 1d is a PWM output 

ON, OFF 

OFF 

1d 01 

Select control loop or special function (0= OFF) 

1= LP1  
2= LP2 
3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 
4= Manual positioning (on/off) 
5= State functions 

0…5 

1d 02 

When 1d01=1, configure output: 

0= Stage 1 heating/reverse 
1= Stage 1 cooling/direct

 

2= Stage 1 heating and cooling, reverse and direct

 

3= Stage 2 heating/reverse

 

4= Stage 2 cooling/direct

 

5= Stage 2 heating and cooling, reverse and direct

 

If 1d01 = 4 Manual positioning or time schedule controlled 

0 = Time schedule controlled only 
1 = Manual positioning and time schedule controlled 

When 1d01=5, select state functions:  

0= ON if controller operation state is ON 
1= ON while demand on any output 
2= ON while controller in heating mode and  
operation state ON 
3= ON while controller in cooling mode and operation state ON 

0…5 

1d 03 

Switch-off delay (time output active with no more demand) 
Delay is in seconds or minutes depending on d09 

0...255s 

90s 

1d 04 

Switch-on delay (time demand active before output on) 
In state mode 1d01=5 outputs disabled during switch-on delay 
Delay is in seconds or minutes depending on d09 

0...255s 

5s 

1d 05 

Activate PWM, set cycle time, seconds (>0 activates, 0 deactivates) 

0...1275 

1d 06 

Choose alarm to set output to ON (output OFF on conflicting alarms) 
 



 

Alarm: 1 2 3 4 5 6 7 8 

Selection 



 

1d 07 

Choose alarm to set output to OFF (output OFF on conflicting 
alarms) 
 



 

Alarm: 1 2 3 4 5 6 7 8 

Selection 



 

1d 08 

Display fan symbol while active 

ON, OFF 

OFF 

1d 09 

Binary switching delays in minutes or seconds 
OFF = delays are in seconds, ON = delays are in minutes 

ON, OFF 

OFF 

Special functions 

– SP compensation 

Parameter  Description 

Range 

Standard 

Fu 00 

Select compensation input (0= function disabled):  
1= 1T,  2= 1H,  3= 1U,  4= 2T 

0…4 

Fu 01 

Winter compensation set point setback 
OFF= shift toward control loop heating set point minimum  
ON=  shift toward control loop heating set point maximum 

ON, OFF 

OFF 

Fu 02 

Winter compensation lower limit value 

– end shift  

Range acc input 

5°C 

Fu 03 

Winter compensation upper limit value 

– start shift 

Range acc input 

20°C 

Fu 04 

Summer compensation se tpoint setback 
OFF= shift toward control loop cooling set point minimum 
ON=  shift toward control loop cooling set point maximum 

ON, OFF 

ON 

Fu 05 

Summer compensation lower limit value 

– start shift 

Range acc input 

35°C 

Fu 06 

Summer compensation upper limit value 

– end shift  

Range acc input 

40°C 

Fu 07 

Show hot/cool symbol while compensation active 

ON, OFF 

OFF 

Special functions 

– remote control comfort – economy 

Fu 08 

Select comfort/economy changeover input (0= disabled):  
1= 1T,  2= 1H,  3= 1U,  4= 2T 

0…4 

Fu 09 

Economy activation delay (seconds) 

0...1275 

300 

Fu 10 

Input limit 1 

Range acc input 

10 

Fu 11 

Input limit 2 

Range acc input 

90 

Special functions 

– remote control enable – disable 

Fu 12 

Select enable

–disable input (0=function disabled):  

1= 1T,  2= 1H,  3= 1U,  4= 2T 

0…4 

FU 13 

Manual override permitted (without waiting for delay).  

This function allows starting the controller; although the 
enable conditions are not met. The controller will switch off 
again if the running conditions are not met until the disable 
delay is expired.  

ON, OFF 

OFF 

Fu 14 

Enable delay (seconds) 

0...1275 

Fu 15 

Disable delay (seconds) 

0...1275 

300 

Fu 16 

Range of limits:  

OFF = When limit 2 is greater than limit 1, enable when 

input value is greater than limit 2,disable when input 
value is less than limit 1.  
When limit 2 is less than limit 1, enable when input 
value less than limit 1, disable when input value is 
greater than limit 2. 

ON = When limit 2 is greater than limit 1enable when input 

value is between limit 1 and limit 2.  
When limit 2 is less than limit 1, enable when input 
value below limit 2 or above limit 1 

ON, OFF 

OFF 

Fu 17 

Input limit 1 

Range acc input 

10 

Fu 18 

Input limit 2 

Range acc input 

90 

Fu 19 

Disable in case of alarms 

Selection 



 

Special functions 

– remote heat / cool (reverse / direct) change 

Fu 20 

Select heat/cool changeover input (0=function disabled):  
1= 1T,  2= 1H,  3= 1U,  4= 2T,   
5= h/c status loop 1,  6= h/c status loop 2 

0…6 

Fu 21 

Cooling activation delay (seconds)  

0...1275 

300 

Fu 22 

Input limit 1 

Range acc input 

20 

Fu 23 

Input limit 2 

Range acc input 

40 

 