Universal controller TCI-W13-U-H/TCI-W23-U-H
Universal controller TCI-W13-U-H/TCI-W23-U-H
Universal controller TCI-W13-U-H/TCI-W23-U-H
Doc: 70-00-0384A V1.0 20160523
© Vector Controls GmbH, Switzerland
Subject to alterations
Analog output (1A, 2A)
Parameter Description
Range
Standard
1A 00
Select control loop or special function (0= OFF):
1= LP1,
2= LP2
3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct)
4= Manual positioning or time schedule controlled
(0
…100%)
5= Transmit value of an input
0...5
1
1A 01
When 1A00=1 configure output:
0= Heating/reverse
1= Cooling/direct
2= Heating and cooling (2 pipe)
3= Transmit set point
When 1A00 = 4 manual positioning or time schedule controlled
0 = Time schedule controlled only
1 = Manual positioning and time schedule controlled
When 1A00=5, select input (0= function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2T
0...4
0
1A 02
Type of output signal: OFF= 0...10V, 0...20mA, ON= 2...10V,
4...20mA
ON, OFF
OFF
(0...10V,
0
…20 mA)
1A 03
Minimum limitation of output signal default and in loop heating
mode
0...100%
0
1A 04
Maximum limitation of output signal default and in loop heating
mode
0...100%
100%
1A 05
Minimum limitation of output signal in loop cooling mode
0...100%
0%
1A 06
Maximum limitation of output signal in loop cooling mode
0...100%
100%
1A 07
Choose alarm to set output to 100% (output 0% on conflicting
alarms)
Alarm: 1 2 3 4 5 6 7 8
Selection
1A 08
Choose alarm to set output to 0%. (output 0% on conflicting
alarms)
Alarm: 1 2 3 4 5 6 7 8
Selection
1A 09
Transmit value (1A00=5): minimum input value
Acc input
-
1A 10
Transmit value (1A00=5): maximum input value
Acc input
-
Binary output
– binary control
Parameter Description
Range
Standard
1d 00
Enable digital or PWM output
OFF= 1d is a digital output
ON = 1d is a PWM output
ON, OFF
OFF
1d 01
Select control loop or special function (0= OFF)
1= LP1
2= LP2
3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct)
4= Manual positioning (on/off)
5= State functions
0…5
0
1d 02
When 1d01=1, configure output:
0= Stage 1 heating/reverse
1= Stage 1 cooling/direct
2= Stage 1 heating and cooling, reverse and direct
3= Stage 2 heating/reverse
4= Stage 2 cooling/direct
5= Stage 2 heating and cooling, reverse and direct
If 1d01 = 4 Manual positioning or time schedule controlled
0 = Time schedule controlled only
1 = Manual positioning and time schedule controlled
When 1d01=5, select state functions:
0= ON if controller operation state is ON
1= ON while demand on any output
2= ON while controller in heating mode and
operation state ON
3= ON while controller in cooling mode and operation state ON
0…5
0
1d 03
Switch-off delay (time output active with no more demand)
Delay is in seconds or minutes depending on d09
0...255s
90s
1d 04
Switch-on delay (time demand active before output on)
In state mode 1d01=5 outputs disabled during switch-on delay
Delay is in seconds or minutes depending on d09
0...255s
5s
1d 05
Activate PWM, set cycle time, seconds (>0 activates, 0 deactivates)
0...1275
0
1d 06
Choose alarm to set output to ON (output OFF on conflicting alarms)
Alarm: 1 2 3 4 5 6 7 8
Selection
1d 07
Choose alarm to set output to OFF (output OFF on conflicting
alarms)
Alarm: 1 2 3 4 5 6 7 8
Selection
1d 08
Display fan symbol while active
ON, OFF
OFF
1d 09
Binary switching delays in minutes or seconds
OFF = delays are in seconds, ON = delays are in minutes
ON, OFF
OFF
Special functions
– SP compensation
Parameter Description
Range
Standard
Fu 00
Select compensation input (0= function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2T
0…4
0
Fu 01
Winter compensation set point setback
OFF= shift toward control loop heating set point minimum
ON= shift toward control loop heating set point maximum
ON, OFF
OFF
Fu 02
Winter compensation lower limit value
– end shift
Range acc input
5°C
Fu 03
Winter compensation upper limit value
– start shift
Range acc input
20°C
Fu 04
Summer compensation se tpoint setback
OFF= shift toward control loop cooling set point minimum
ON= shift toward control loop cooling set point maximum
ON, OFF
ON
Fu 05
Summer compensation lower limit value
– start shift
Range acc input
35°C
Fu 06
Summer compensation upper limit value
– end shift
Range acc input
40°C
Fu 07
Show hot/cool symbol while compensation active
ON, OFF
OFF
Special functions
– remote control comfort – economy
Fu 08
Select comfort/economy changeover input (0= disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2T
0…4
0
Fu 09
Economy activation delay (seconds)
0...1275
300
Fu 10
Input limit 1
Range acc input
10
Fu 11
Input limit 2
Range acc input
90
Special functions
– remote control enable – disable
Fu 12
Select enable
–disable input (0=function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2T
0…4
0
FU 13
Manual override permitted (without waiting for delay).
This function allows starting the controller; although the
enable conditions are not met. The controller will switch off
again if the running conditions are not met until the disable
delay is expired.
ON, OFF
OFF
Fu 14
Enable delay (seconds)
0...1275
0
Fu 15
Disable delay (seconds)
0...1275
300
Fu 16
Range of limits:
OFF = When limit 2 is greater than limit 1, enable when
input value is greater than limit 2,disable when input
value is less than limit 1.
When limit 2 is less than limit 1, enable when input
value less than limit 1, disable when input value is
greater than limit 2.
ON = When limit 2 is greater than limit 1enable when input
value is between limit 1 and limit 2.
When limit 2 is less than limit 1, enable when input
value below limit 2 or above limit 1
ON, OFF
OFF
Fu 17
Input limit 1
Range acc input
10
Fu 18
Input limit 2
Range acc input
90
Fu 19
Disable in case of alarms
Selection
Special functions
– remote heat / cool (reverse / direct) change
Fu 20
Select heat/cool changeover input (0=function disabled):
1= 1T, 2= 1H, 3= 1U, 4= 2T,
5= h/c status loop 1, 6= h/c status loop 2
0…6
0
Fu 21
Cooling activation delay (seconds)
0...1275
300
Fu 22
Input limit 1
Range acc input
20
Fu 23
Input limit 2
Range acc input
40