X2-O
PERATIONS
M
ANUAL
T
OUCH
D
ISPLAY
Doc: 70-07-0951A, 20220504
© Vector Controls LLC, USA
Page 13-18
Subjects to alteration
www.vectorcontrols.com
V
ECTOR
5.3.3
Set annual time schedules (holidays)
Overview
This section describes how to set an annual holiday.
While a holiday schedule is active, the controller will be in the
OFF
-mode!
Other weekly schedules will still be active. It will still be possible to manually override the controller while in holiday
mode.
Up to 12 annual holidays can be programmed (Pr01 to Pr12).
Holiday schedules have priority over weekly schedules.
Requirements
Time scheduler is enabled (see chapter 5.3.1).
Procedure
1.
Press the (
) button longer than 2 seconds.
➔
SEL
and the actual
Date
and
Time
are displayed alternatingly.
2.
Press the ( ) button briefly to go to the scheduler submenu.
➔
PRO
and
SEL
is displayed.
3.
Press the (
) button: Schedule status indicates whether it is
OFF
or
ON
.
4.
Press the ( /
/
) button to change the status.
➔
When scheduler is ON,
is displayed.
5.
Press the ( ) or ( ) button to select between programs
Pr 01
…
Pr 12.
6.
Press the (
) button and assign one of the following functions to the
program with the ( ) ( ) button:
no
= Switching time not activated
OP
= Operating mode ON (Occupied), ECO (Unoccupied) or OFF
(protective operation)
LP
= Setpoint of a control loop (setting range 0-100%, °C/°F,
Pascal)
AO
= Positioning of the analog output (output must be in
manual mode!)
FAN = Fan control (fan stages from FSP0-3 and Auto)
do
= Positioning of the digital output (output must be in manual
mode!)
Hday
= Annual time schedule (holiday)
1 bar indicates setting step 1 is executed.
For setting "OP", "LP", "AO", "FAN" and
"do" see chapter 5.3.2.