background image

Commissioning

The units operate by extracting warm, stale air from kitchens, WCs, bathrooms etc, and passing it into a heat
exchanger and out to the atmosphere.  Another fan draws in cool, fresh air and passes it through the same 
heat exchanger, where it is heated by the outgoing, stale air.

When the unit is set up and running, the minimum setting on the speed control switch must relate to the 
designed volume air flow.  The variable air flow from minimum to maximum allows the unit to extract a greater
volume to cope with any increase in the build up of condensation or foul air, ie cooking etc.

Before starting the commissioning procedure, refer to the design drawing for correct air flows.

N.B

extract  and  supply  air  volumes  will  not  always  be  equal.    When  setting  up,  therefore,  the  extract  system

should be the datum.
Installation of the appliance 

MUST

be carried out by a qualified and suitably competent person and should be car-

ried out in clean, dry conditions where dust and humidity are at minimal levels.  It should only be installed after other
building works have been completed and the building in which it is installed cleaned. Failure to comply with any of the
above points will have an impact on the validity of the guarantee.

Commissioning procedure

Ensure that the exhaust and supply grilles or valves are open.

Turn the electrical supply ON and set the fan speed control to TRICKLE.  

Check the air flows at the grilles or valves, and adjust to suit the design figures by turning the centre of the 
valve clockwise to decrease the airflow, and anticlockwise to increase the airflow.

If the airflow is still not correct proceed as follows:
-

turn the electrical supply OFF

-

remove the electrical access cover

-

locate the trickle speed adjustment (see Wiring Diagrams) and adjust as required.  

-

turn the electrical supply ON.

Re-measure the air flows at the grilles or valves as detailed above, and repeat the procedure until the correct
air flows are achieved.

Adjust the Boost Speed to requirement and ensure that the air flows increase when the boost switch is acti
vated.

Cleaning and Maintenance
WARNINg: The unit uses a 230V  supply and contains rotating mechanical parts.
• Before carrying out any maintenance or cleaning operations the mains electrical supply MUST be dis-

connected

.

The air filters and heat exchanger of the Vectaire WHHR100/90DC should be cleaned regularly by a
suitably qualified person (the frequency of cleaning will vary depending on the installation environment). Filters
should be replaced after a maximum of 3 cleaning cycles.

Filter and Heat Exchanger access:

Remove the  centre screw and the four corner screws located on the larger access panel

Completely remove the panel

To clean the filters and heat exchanger:

Remove the access panel

Slide out the filters that are fitted either side of the heat exchanger as shown. 

Clean the filters carefully using a vacuum cleaner. 

Carefully remove any dust from the face of the heat exchanger using a vacuum cleaner.

Never use water or any other fluids to clean the heat exchanger.

Return the heat exchanger and filters to their original position.

Replace the front cover and ensure it is securely located at the top before tightening all screws.

Power to the unit can now be restored.

Filter Replacement

Filters should be replaced annually or after a maximum of 3 cleaning cycles.
Replacement filters are available from Vectaire - call us on +44 (0) 1494 522333 or via

Page 5

WHHR 100/90 DC Ins 2 11_Layout 1  01/03/2011  14:52  Page 5

Содержание WHHR100/90DC

Страница 1: ...provides low level continuous ventil ation in a kitchen and up to six wet rooms extracting moist polluted air and replacing it with fresh filtered air recovering up to 79 of the heat from the outgoing flow The user can to boost to maximum performance when required The slimline WHHR100 90DC is easily installed in the loft or roof void or a cupboard The noise level and running costs are extremely lo...

Страница 2: ...profile unit only 200mm deep casing manufactured from gal vanised sheet with an epoxy finish thermo acoustic lining in poly propylene to prevent thermal bridging to outside low energy DC brushless motor for optimum combination of high performance low noise levels and low energy consumption impellers are single width single inlet direct drive and backward curved for higher efficiency operates in te...

Страница 3: ...oms 100 variable 0 91 78 Kitchen 4 additional wet rooms 100 variable 0 99 78 Kitchen 5 additional wet rooms 100 variable 1 22 78 Kitchen 6 additional wet rooms 100 variable 1 39 77 Figures from BRE test results RESULTS for Approved Document F Exhaust Terminal Configuration Fan Speed Setting Total Exhaust Flow Rate l sec Total Supply Flow Rate l sec Kitchen 1 additional wet room 100 variable 15 0 1...

Страница 4: ...ation with Heat Recovery MVHR WHHR100 90DC Technical Characteristics Performance Dimensions 300 250 200 150 100 50 0 Available Pressure Pa 0 10 20 30 40 50 60 70 80 litres second Speed Watts dB A 3m Max Speed 104 42 7 73 40 6 53 37 5 39 34 4 28 31 3 21 27 2 15 22 1 11 16 curves are for guidance only Dimensions mm Page 15 ...

Страница 5: ...R100 90DC Whole House Heat Recovery Unit with Low Energy DC Motor for domestic and commercial use Installation Operating and Maintenance Instructions WHHR 100 90 DC Ins 2 11_Layout 1 01 03 2011 14 52 Page 1 ...

Страница 6: ... energy and saving heat already generated The heat recovery unit will generally be installed in the loft of a house or the void above the ceiling in an apartment but may be installed in a cupboard and will be connected by hidden ductwork to vents sited in the ceilings of the rooms which require ventilation Each unit is commissioned individually allowing its performance to be tailored to suit the p...

Страница 7: ...e condensation drain must be fitted and if insulated use the equivalent of at least 25mm of insulating material with a thermal conductivity of 0 04 W mK Care should be taken to ensure that ducting is free from blockages before switching on the unit as this may invalidate your guarantee External grilles should be located a minimum of 600mm from any flue outlet in accordance with all Regulations The...

Страница 8: ...insulated with the equivalent of at least 25mm of insulating material with a thermal conductivity of 0 04 W mK The drain must incorporate a U bend to prevent air penetration The pipe must drain into the normal household drainage system The unit must be tilted towards the side carryng the condensation exit point It should be installed horizontally with a 3º tilt towards the condensation drain used ...

Страница 9: ...turn the electrical supply OFF remove the electrical access cover locate the trickle speed adjustment see Wiring Diagrams and adjust as required turn the electrical supply ON Re measure the air flows at the grilles or valves as detailed above and repeat the procedure until the correct air flows are achieved Adjust the Boost Speed to requirement and ensure that the air flows increase when the boost...

Страница 10: ...incoln Road Cressex Business Park High Wycombe Buckinghamshire HP12 3RH Tel 44 0 1494 522333 Fax 44 0 1494 522337 Email sales vectaire co uk WHHR100 90DCFeb1011 E O E WHHR 100 90 DC Ins 2 11_Layout 1 01 03 2011 14 53 Page 6 ...

Отзывы: