SELV with Cord
ES1003CLV - 3 Speed with Cord
ES100H2CLV - Humidity Control with Cord
SELV with Cord removed
ES1003CLV - 3 Speed with Cord removed
ES100H2CLV - Humidity Control - Cord removed
SELV Products
All SELV (safety extra low voltage) products must
be installed to conform to IEC 60364.
• Connection between the fan and the mains
supply must be by means of a safety isolating
transformer of the appropriate power rating
• The transformer should be connected to the
mains supply via a double pole safety switch
with a contact opening of at least 3mm
• The transformer will operate only one fan
• The transformer must
not
be installed in
Zones 1 or 2, but
should
be installed as close
as possible to the fan within Zone 3
• The cable used to connect the transformer to
the fan must be Class II, with a section area of
at least 1.5mm
2
and a maximum length of 10m
• If the fan is a humidity control model, it must
be installed using the transformer supplied for
that product.
The ES1003 fans are
designed to run con-
tinuously at one of 2 lower speeds fixed at
installation using the jumper switch. The
SELV models have 3 pins on the jumper
switch (rather than 2 as on the 230v models)
and are supplied ready for Speed 1 - lower
speed. Installer can change to Speed 2 if
required. The user can boost the fan speed
to its maximum performance by using cord
or remote switch (when installing with
remote switch, pullcord switch must be left
in "off" position and cord removed).