25
The following rules must be observed when modifying the parameter values in User for
lithium battery.
-Over Voltage Disconnect Voltage>Over charging protection voltage (Protection Circuit
Modules(BMS))+0.2V
※
;
-
Over Voltage Disconnect Voltage>Over Voltage Reconnect Voltage
=
Charging Limit
Voltage ≥ Equalize Charging Voltage
=
Boost Charging Voltage ≥ Float
Charging
Voltage>Boost Reconnect Charging Voltage;
-
Low Voltage Reconnect Voltage>Low Voltage Discon
nect Voltage ≥ Discharging Limit
Voltage;
-
Under Voltage Warning Reconnect Voltage>Under Voltage Warning Voltage≥
Discharging Limit Voltage;
-
Boost Reconnect Charging voltage> Low Voltage Reconnect Voltage;
-
Low Voltage Disconnect Voltage ≥ Over
discharging protection voltage (BMS)+0.2V
※
.
WARNING:
The voltage parameters of lithium battery can be set, but you must refer to the voltage
parameters of lithium battery BMS.