5
ENV-L
Mounting
1. The distances indicated in the above drawing are the minimum measurements. Distances less than the indicated can cause a fire.
2. The heater's switch box must always face upwards.
3. The heater may not be covered or manipulated, to avoid overheating, fire or electric shock.
Specification
Maintenance
Normally, no maintenance is required, with the exception of periodic tests of functionality and cleaning.
Overheating
The heater is thermally protected by an overheating protection with manual reset, placed on the cover's exterior.
Troubleshooting
- Troubleshooting with the fan connected to main supply voltage must be performed by a qualified electrician.
- If the over heating protection has tripped the reason for it must be examined and corrected before the protection is reset.
- Make sure the terminal blocks are connected to the correct supply voltage.
- Make sure the fuse in the terminal box, with connection number 2, is intact.
The fuse must have rated current up to 10A, with slow blow fuse characteristics and dimensions 5x20mm.
- Make sure that the external thermostat and the switch are working as intended and that it is properly connected.
Type
ENV-L 2
ENV-L 3
ENV-L 5
ENV-L 9
ENV-L 15
Rated voltage
230 V~
230 V~
400V3N~
400V3N~
400V3N~
Rated output (kW)
2
3
5
9
15
Reduced power (kW)
1
1.5
3.3
6
7.5
Rated current (A)
8.7
13.0
7.2
13.0
21.7
B (mm)
60
60
60
80
80
W (mm)
232
232
232
307
307
H (mm)
318
318
318
402
402
D (mm)
215
215
215
282
282