2
* Setting internal parameters.
Next to the adjustment of the setpoint, internal settings can be made like differential, sensor offset,
setpoint range and the functions of the thermostat.
Push the
DOWN
key more than 10 seconds, to enter the 'Internal Programming Menu'. In the left
display the upper and lower segment are blinking. Over the
UP
and
DOWN
keys the required
parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the
SET
key. Pushing
the
UP
or
DOWN
key to change the value of this parameter.
If after 20 seconds no key is pushed, the
ALFANET 71
changes to the normal operation mode.
* Adjustment sensors.
Sensor-1 can be adjusted by using the Sensor Offset parameter 06 and Sensor-2 can be adjusted
by using the Sensor Offset parameter 07. Indicates a Sensor e.g. 2°C to much, the according
Sensor Offset has to be decreased with 2°C.
* Error messages.
In the display of the
ALFANET 71
the following error messages can appear:
LO
- Minimum alarm.
Solution E1,E2:
HI
- Maximum alarm.
- Check if the sensor is connected correctly.
E1
- Sensor-1 failure.
- Check sensor (1000
Ω at 25°C).
E2
- Sensor-2 failure.
- Replace sensor.
EEE
- Settings are lost.
Solution EEE:
- Reprogram the settings.
-L-
- In case of sensor short-circuit the display alternates between error-code
E..
and
-L-
, as indication for a short-circuit sensor.
-H-
- In case of open-circuit sensor the display alternates between error-code
E..
and
-H-
, as indication for a open circuit sensor.
Reset Alarm.
When a error-messages appears it can be resetted by pushing the
SET
key. The
function of this key depends on parameter P37.
* Technical details.
Type
: ALFANET 71 Thermostat
Range
: -50/+50,0°C, above -10°C display per 0,1°C
Supply
: 12Vac 50/60Hz (-5/+10%)
Display
: 3-digit 7-segment display
Relays
: Ry1= SPST(NO)
250V/8A (cos
φ=1) of 250V/5A (cos φ=0.4)
Ry2= SPST(NO)
250V/8A (cos
φ=1) of 250V/5A (cos φ=0.4)
Ry3= SPDT(NO/NC)
250V/8A (cos
φ=1) of 250V/5A (cos φ=0.4)
Relays have one common (C).
Control
: By push buttons on front.
Front
: Polycarbonate IP65
Sensors
: 2x SM 811/2m (PTC 1000
Ω/25°C).
Communication
: RS485-Network (2-wire shielded cable min. 0,75mm
2
)
Dimensions
: 35 x 77 x 71,5mm (HWD)
Panel cutout
: 28 x 70mm (HW)
Accuracy
: ± 0,5% of the range.
- Provided with memory protection during power failure.
- Connections with screw terminals on the back side.
- Equipped with sensor failure detection.
- Special versions on request available.