* Defrost control.

The automatic defrost is started by the defrost cycle time (P07) and stopped by the maximum defrost
time  (P08)  or  sooner  by  reaching  the  maximum  defrost  temperature  (P09).  Further  has  the

ALFA(NET)-45

 additional parameters to control defrost;

Parameter 24 = 0:

Function defrost with a fixed defrost cycle time.
With parameter 7 as the chosen cycle time.

Parameter 24 = 1:

Function defrost based on total compressor running hours.

 

The defrost is started when the compressor has run for parameter 7 hours after the last defrost.

Parameter 25 = 1:

The temperature readout on the display is locked during defrost cycle.

Parameter 26 = 1:

After power-up the 

ALFA(NET)-45

 starts with defrost after running thru the defrost delay time

of parameter 14. While running down the delay the 

ALFA(NET)-45

 can cool, after this delay the

defrost is started.

Parameter 21 = 1:

On hot gas systems the compressor is switched on during defrost. After defrost the dripping-off
time  of  parameter  12  is  started.  During  this  time  the  defrost  and  compressor  relay  are
deactivated, so the condenser can drip off it’s water.

Содержание ALFA-45

Страница 1: ...it is shown how sensors and power supply are to be connected After connecting the ALFA NET 45 to the power supply a self test is started As this test has finished the measured temperature of the produ...

Страница 2: ...t cycle the defrost can by manually stopped by pushing the UP key and than the SET key while the UP key is hold Start defrost If there is no defrost cycle the defrost can be started manually by pushin...

Страница 3: ...er P26 1 Startup delay after power failure Offset defrost sensor Fan off delay if parameter P22 1 Readout defrost sensor 1 15 C 50 50 C 50 50 C 15 15 C 0 3 0 99 1 99 Hours 0 99 Minutes 99 99 C 99 99 C...

Страница 4: ...e of the following parameters is set to 1 the fan can be stopped Parameter 19 1 Fan switch differential active The fan is only active when the defrost temperature is parameter 13 C lower then the meas...

Страница 5: ...st is started when the compressor has run for parameter 7 hours after the last defrost Parameter 25 1 The temperature readout on the display is locked during defrost cycle Parameter 26 1 After power u...

Страница 6: ...play of the ALFA NET 45 the following error messages can appear E1 Product sensor error Fatal error display shows E1 and all relays are deactivated accept when parameter 24 is 1 then the compressor an...

Страница 7: ...se see Product sticker Max used power 6 2 VA Fuse No internal fuse present Product sensor SM 811 2m Defrost sensor SM 811 2m Relay Compressor SPST 250V 16A C NO cos phi 1 Relay Defrost SPST 250V 8A C...

Страница 8: ...8 Dimensions CPU unit Dimensions SUPPLY unit Connections...

Отзывы: