* Parameters ALFA(NET)-45.

PARA-
METER

DESCRIPTION PARAMETER

RANGE

STANDARD
VALUE

01
02
03
04

05

06

07
08
09
10
11
12
13
14

15

16
17
18

Switching differential
Minimum setpoint setting
Maximum setpoint setting
Offset product sensor

Compressor start-up protection
 0 = start-up delay in seconds
 1 = start-up delay in minutes
 2 = delay between switch off and
     switch on in minutes
 3 = delay between switch on and
     switch on in minutes
Compressor start-up time
 belonging to parameter 05

Defrost interval
Maximum defrost time
End of defrost temperature
Fan on temperature (P20=1)
Fan delay time (P20=1)
Drain time in min.
Switching differential fan (P19=1)
Defrost delay after power failure if 
 parameter P26=1
Startup delay after power failure

Offset defrost sensor
Fan-off delay if parameter P22=1
Readout defrost sensor

1..15

C

-50..+50

C

-50..+50

C

-15..+15

C

0..3

0..99

1..99 Hours
0..99 Minutes
-99..+99

C

-99.+99

C

0..99 Minutes
0..99 Minutes
0..99

C

0..99 Minutes

0..99 Minutes

-15..+15

C

0..99 Minutes
temp. in 

C

3

-50

+50

0

0

10

12
15

2
2
0
0
2
0

0

0
0

-

19
20

21
22
23

24
25
26

Fan switch differential active
Fan off while defrost active

Compressor on at defrost
Compressor off -> Fan off
Compressor on at product sensor failure

Defrost cycle time based on compressor running time
Temperature display locked during defrost cycle
Start with defrost after power failure

0=No, 1=Yes
0=No, 1=Yes

0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes

0=No, 1=Yes
0=No, 1=Yes
0=No, 1=Yes

0
0

0
0
0

0
0
0

90
95
96
97
98
99

Network number
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

1..250
-
-
-
-
-

1

-
-
-
-
-

Содержание ALFA-45

Страница 1: ...it is shown how sensors and power supply are to be connected After connecting the ALFA NET 45 to the power supply a self test is started As this test has finished the measured temperature of the produ...

Страница 2: ...t cycle the defrost can by manually stopped by pushing the UP key and than the SET key while the UP key is hold Start defrost If there is no defrost cycle the defrost can be started manually by pushin...

Страница 3: ...er P26 1 Startup delay after power failure Offset defrost sensor Fan off delay if parameter P22 1 Readout defrost sensor 1 15 C 50 50 C 50 50 C 15 15 C 0 3 0 99 1 99 Hours 0 99 Minutes 99 99 C 99 99 C...

Страница 4: ...e of the following parameters is set to 1 the fan can be stopped Parameter 19 1 Fan switch differential active The fan is only active when the defrost temperature is parameter 13 C lower then the meas...

Страница 5: ...st is started when the compressor has run for parameter 7 hours after the last defrost Parameter 25 1 The temperature readout on the display is locked during defrost cycle Parameter 26 1 After power u...