background image

4

* Compressor control.

The compressor relay activates when the product sensor measures a higher temperature than the
se switching differential (parameter 1), and deactivates when the temperature descents below
setpoint. 
There are 4 different modes off delay on the compressor possible with parameter 05 as shown below;

Parameter 05 = 0 :

The compressor relay has a start-up delay of "parameter 6" seconds.

Parameter 05 = 1:

The compressor relay has a start-up delay of "parameter 6" minutes.

Parameter 05 = 2 :

After switching off the compressor waits at least "parameter 6" minutes before switching on
again.

Parameter 05 = 3 :

In between the switching-on points the compressor waits at least "parameter 6" minutes.

Next options for Compressor control are available.

Parameter 15 :

A compressor on delay after power failure of  "parameter 15" minutes.

Parameter 23 =1:

The compressor relay activates at product sensor failure.

* Fan control.

The 

ALFA(NET)-45

 has several parameters for fan control. Normally the fan is always active, accept

for one of the following parameters is set to 1, the fan can be stopped.

Parameter 19 = 1 (Fan switch differential active):

The  fan  is  only  active  when  the  defrost  temperature  is  "parameter  13" 

C  lower  then  the

measurement of the product temperature. As there are no further conditions to switch the fan
off. (e.g. Parameter 13 = 2

C and the product sensor measures 10

C, than the fan is only active

as the defrost sensor measures 10

-2

=8

C or less.) 

Parameter 20 = 1 (Fan off on defrost cycle):

The fan is switched off during defrost and to prevent blowing in hot air in the cabin after defrost
and the dripping-off time, there are two conditions which can be set;
1: The  fan  is  blocked  until  the  defrost  sensor  measures  a  temperature  lower  than  the

temperature setting of parameter 10.

2: The  fan  is  blocked  until  the  defrost-delay-time  of  parameter  11  has  stopped.  Unless  the

defrost  sensor  has  reached  the  temperature  setting  of  parameter  10.  When  the  defrost
sensor is broken (Failure E2) the 

ALFA(NET)-45

 runs down the entire time of parameter 11.

Parameter 22 = 1 (Compressor off -> Fan off):

The fan deactivates as the compressor deactivates, with a delay of "parameter 17" minutes.
Provided that there are no other conditions to deactivates the fan.

Содержание ALFA-45

Страница 1: ...it is shown how sensors and power supply are to be connected After connecting the ALFA NET 45 to the power supply a self test is started As this test has finished the measured temperature of the produ...

Страница 2: ...t cycle the defrost can by manually stopped by pushing the UP key and than the SET key while the UP key is hold Start defrost If there is no defrost cycle the defrost can be started manually by pushin...

Страница 3: ...er P26 1 Startup delay after power failure Offset defrost sensor Fan off delay if parameter P22 1 Readout defrost sensor 1 15 C 50 50 C 50 50 C 15 15 C 0 3 0 99 1 99 Hours 0 99 Minutes 99 99 C 99 99 C...

Страница 4: ...e of the following parameters is set to 1 the fan can be stopped Parameter 19 1 Fan switch differential active The fan is only active when the defrost temperature is parameter 13 C lower then the meas...

Страница 5: ...st is started when the compressor has run for parameter 7 hours after the last defrost Parameter 25 1 The temperature readout on the display is locked during defrost cycle Parameter 26 1 After power u...

Страница 6: ...play of the ALFA NET 45 the following error messages can appear E1 Product sensor error Fatal error display shows E1 and all relays are deactivated accept when parameter 24 is 1 then the compressor an...

Страница 7: ...se see Product sticker Max used power 6 2 VA Fuse No internal fuse present Product sensor SM 811 2m Defrost sensor SM 811 2m Relay Compressor SPST 250V 16A C NO cos phi 1 Relay Defrost SPST 250V 8A C...

Страница 8: ...8 Dimensions CPU unit Dimensions SUPPLY unit Connections...

Отзывы: