PROBA 5
Doc.nr: 190356
Version: 1.0
Page
62
6.6.11 Temperature sensors settings
No.
Explanation
3001
Sensor 1 type.
Use this parameter to indicate what type of sensor is connected.
Info sensors are not used for control functions and are only used for display.
The function of the sensor can only be changed on the PROBA web page. See also “5.1.3 PROBA 5 Compact temperature
config” on page 24
3003
The offset value of the sensor compensates the deviation of the sensor.
3004
Which alarm should be activated if an absolute alarm occurs?
3005
Which alarm should be activated if a relative alarm occurs?
3011 .. 3035
Parameters 3001 .. 3005 are valid for sensor 1.
Parameters 3011 .. 3035 have the same functions but now for sensor 2 .. 4.
6.6.12 Other sensors settings
No.
Explanation
3131
Position of decimal point in displayed value. Use no decimal point or set decimal point after 1st, 2nd or 3rd digit:
No decimal point : 0000
After 1st digit
: 000.0
After 2nd digit
: 00.00
After 3rd digit
: 0.000
3132
Because the analogue inputs can be used for nearly each possible range, it is necessary to configure the input to the
range of the sensor which will be used. This should be done entering the right value for each input value.
3133
At this parameter the measured value which generates a 0V or 0mA signal should be entered.
3134
Same as P3132 but now with a 0,2V, 2V or 4mA signal.
3135
Same as P3132 but now with a 0,4V, 4V or 8mA signal.
3136
Same as P3132 but now with a 0,6V, 6V or 12mA signal.
3137
Same as P3132 but now with a 1V, 10V or 20mA signal.
Example:
If a humidity sensor is connected and this sensor has an output from 0-1Vdc according to 0-100% RH, the following
values should be entered:
P3132 – 0
P3133 – 20
P3134 – 40
P3135 – 60
P3136 – 80
P3137 – 100
3138
Offset value of the sensor. With this parameter the deviation of the sensor can be compensated.
3141 .. 3168
Parameters 3131 .. 3138 are used for sensor 1.
Parameters 3141 .. 3168 have the same functions but now for sensors 2 .. 4.
3149
The CO2 sensor can be readout through Modbus instead of a analogue signal. The required address can be set with this
parameter
3171
The CO2 sensor can be connected to a analogue input, through an analyser or through modbus
3172
The O2 sensor can be connected to a analogue input, through an analyser or through modbus
Содержание 907.000401
Страница 11: ...Page 11 PROBA 5 Doc nr 190356 Version 1 0 3 2 PROBA 5 Compact internal view Fig 3 Internal view PROBA 5 Compact...
Страница 13: ...Page 13 PROBA 5 Doc nr 190356 Version 1 0 Fig 4 Processor board 805 000057 4 2 Processor board...
Страница 15: ...Page 15 PROBA 5 Doc nr 190356 Version 1 0 4 4 Relays board Fig 6 Relay circuit board 805 000074...
Страница 22: ...PROBA 5 Doc nr 190356 Version 1 0 Page 22 Fig 9 Web page Controller config PROBA 5 Compact config...
Страница 65: ...Page 65 PROBA 5 Doc nr 190356 Version 1 0 Fig 34 PI control graph...
Страница 67: ...Page 67 PROBA 5 Doc nr 190356 Version 1 0...