WATER TEMPERATURE CONTROLS 

A periodic inspection of the operating controls, heat exchanger and 
wiring should be made by qualified service personnel. 
Temperature of the water should be tested periodically at the faucet to 
be sure thermostat is working properly.  

 

TEMPERATURE ADJUSTMENT 

The water heater is delivered with either a TPI thermostat or an ETC101 
thermostat. Both have a factory set temperature setting of 120

F and 

differential setting of 10

F. Any temperature adjustment of the thermostat 

must be made by qualified service personnel, as shown below. 

WARNING:

 

See SERVICE INFORMATION Water Temperature 

Regulation, regarding safe water temperature before proceeding. 
Hot water can cause scalding injuries. 
1. 

Shut off or disconnect all electrical supply to heater. 

2. 

Remove cover to Thermostat. 

3. 

Adjust right side lever to the desired temperature. Moving lever down 
will decrease temperature. 

(See Thermostat Diagram 1). 

NOTE:

 

Markings on slide are approximate. Check temperature 

at faucet to ensure safe operating temperature. 

4. 

Adjust left side lever to the desired differential. The thermostat will 
call for heat when the tank temperature has fallen to the set 
differential degrees below the Temperature set point. 

5. 

Reattach cover. 

6. 

Reconnect electrical supply. 

7. 

Check faucet temperature to verify desired temperature is achieved.

 

 

In order to set the temperature above 140

F {

NOT RECOMMENDED

you must remove the SCALD DANGER label attached to the 
temperature slide. 

Caution: Do not increase temperature above 140° without a properly 
installed mixing valve in the system 

– See Water Temperature 

Regulation and SCALD WARNING.  

 

Indicator LED operation: 

The thermostat has an indicator LED at the top of the case. 

(See 

Thermostat Diagram 1 or Inside Cover of thermostat) 

When thermostat is calling for heat, the Indicator LED will blink green.  
When thermostat is satisfied, the Indicator LED will be solid green. 
If the thermostat detects no probe, the Indicator LED will flash Red. Ensure 
connections are tight.  

 
 
 
 

Содержание TOP PERFORMER PLUS

Страница 1: ...Operation and Installation Manual TOP PERFORMER PLUS Indirect Fired Water Heater Limited Warranty and Tank Replacement...

Страница 2: ...heaters will absorb less than 200 000 BTU hr when domestic water outlet temperature is 194 F and boiler water supply temperature is 240 F Listed outputs are based on ASME Section VIII Interpretation V...

Страница 3: ...ere is risk of property damage and personal injury inherent in the use of any hot water system The Company cannot supervise the installation and therefore makes it a specific condition of the warranty...

Страница 4: ...Diagram 5 ___________________________________________ 13 FIGURE 1_____________________________________________________ 14 FIGURE 2_____________________________________________________ 14 FIGURE 3____...

Страница 5: ...foundation in a clean dry location nearest the boiler The heater should be protected from freezing and water lines should be insulated to reduce energy and water waste Leave sufficient headroom to ser...

Страница 6: ...he requirements for Relief Valves and Automatic Gas Shutoff for Hot Water Supply Systems ANSI Z21 22 1971 This valve must be marked with maximum set pressure not to exceed the marked maximum allowable...

Страница 7: ...the other Thread the bolt into the nut and tighten in proper order See Figure 4 NOTE Be sure to place bolts in all of the openings WARNING Plastic o ring housing must be installed properly See Figure...

Страница 8: ...Supply Line from the boiler to the HX in fitting and Boiler Return Line to the boiler to the HX Out fitting H FILLING THE HEATER Check that the temperature and pressure relief valve has been properly...

Страница 9: ...ect 24VAC Power From the the switching relay board or from a step down transformer to the screws to the right of the Probe Connector See Thermostat Diagram 5 K TPI WIRING CONTROLS NOTE THE TPI THERMOS...

Страница 10: ...oper installation will present potential hazard to life and property Check to be sure that proper relief valve requirements are met T P installed as shown in Figures 1 and 2 See Figure 3 for S70DTPP 3...

Страница 11: ...trol temperature properly without any notice and therefore should be tested periodically for your protection DANGER IF YOU DISCOVER EXTREME HOT WATER COMING FROM THE FAUCET IMMEDIATELY SHUT OFF THE MA...

Страница 12: ...ee Thermostat Diagram 1 NOTE Markings on slide are approximate Check temperature at faucet to ensure safe operating temperature 4 Adjust left side lever to the desired differential The thermostat will...

Страница 13: ...ger Consists of two copper tubes one inside the other wound into a coil The outer tube is soldered into the brass fitting that mates into the tank The inner tube is soldered into the brass fitting tha...

Страница 14: ...11 Thermostat Diagram 1 Thermostat Diagram 2...

Страница 15: ...12 Thermostat Diagram 3 ETC101 Low Voltage Only Red Circuit Board TPI Green Circuit Board OUTPUT CONTACTS 24V IN...

Страница 16: ...and push wires Down into holes in top of connector This can also be done one side at a time 4 C Tug on each wire to make sure they are secure Wires Buttons Thermostat Diagram 5 Typical Wiring Wiring w...

Страница 17: ...14 FIGURE 1 Installation Diagram Using Zone Valves FIGURE 2 Installation Diagram Using Separate Circulator...

Страница 18: ...15 FIGURE 3 S70DTPP Installation Diagram Using a Single Tank S70DTPP Installation Diagram Including One Hotstow Storage Tank...

Страница 19: ...16 FIGURE 4...

Страница 20: ...If neither action has solved your problem please have your plumbing contractor contact us for assistance CUSTOMER RELATIONS DEPARTMENT General vaughncorp com 978 462 6683 VAUGHN THERMAL CORPORATION 26...

Страница 21: ...ANUFACTURED DATE INDICATED BY THE SERIAL NUMBER ON THE TOP PERFORMER COVERAGE Replacement policy covers only the storage tank for leaks caused by the corrosive effects of water under normal and proper...

Страница 22: ...and limitations 1 The Top Performer must be correctly installed according to the installation manual provided with the unit and all applicable local and national codes 2 The unit must be operated wit...

Страница 23: ...n should be noted At time of installation and retained for Future reference Model No Serial No Date Installed Dealer s Name Address City State Zip 26 Old Elm Street P O Box 5431 Salisbury MA 01952 543...

Страница 24: ...Warranty on newly purchased tanks Not available on replacement tanks may be purchased by completing and returning this form to Vaughn Thermal Corporation along with a payment of 199 within 30 days of...

Отзывы: