3.11.3 RS485 network topology
Note:
In the picture above, the general network topology of RS485 is shown. N nodes are connected in a multipoint RS485
network. A termination resistance is necessary on both ends of the line to eliminate reflections. Use 120
Ω
resistors (R)
on both ends. The RS485 network must be designed as one line with multiple drops, not as a star.
3.11.4 Connection cable drawing
Half duplex
Full duplex
R-
R+
T-
T+
120
Ω
R
11
24
13
12
HOST
R 120
Ω
R+
R-
T+
T-
Valve
Twisted pair
cable
Twisted pair
cable
Wiring:
T+ to R+
T- to R-
R+ to T+
R- to T-
11
Valve
24
12
13
R-
R+
T-
T+
120
Ω
R
HOST
R 120
Ω
T+
T-
R+
R-
Twisted pair
cable
Wiring:
T+ to T+
T- to T-