3.10.2.4 Valve
speed
adjustment
Valve speed effects:
•
Response time
Default value is 1000. Adjustment range is from 1 to 1000.
This parameter effects valve plate actuating speed.
Speed adjustment is effective for PRESSURE CONTROL and POSITION CONTROL.
Note: Normally best pressure control response is achieved with max. valve speed. In particular applications it may be of
advantage to have a slower valve response.
Note: OPEN and CLOSE are always done with max. speed.
Adjustment procedure:
1. Use optimal gain factor, sensor delay time and setpoint ramp according to preceding tuning steps.
2. Open
valve.
3. Control a typical pressure / flow situation.
4. Repeat from step 2 with slower valve speed until required response is achieved.
Local operation
:
(‘Control View’, ‘Control Performance Analyzer’ or
‘Service Box 2‘)
Remote operation
:
(Refer to chapter «setup commands» for details)
Go to ‘Setup / Control Parameter’ menu. Select valve
speed.
Send VALVE SPEED
3.11 RS232 interface
3.11.1 Settings
The factory default setting of the RS232 interface might be changed to fit the application by using the Control View
software, the Control Performance Analyzer software or the Service Box 2.