6

Illustrations may differ from the actual product 

Allowing for printing errors and errors on proofs

  The installation must comply with the applicable 

regulations and standards.

Install the boiler horizontally with vertical pipe connections, allow-
ing air to escape.
The boiler must be installed indoors in a cellar or on the ground 
floor.
The ambient temperature must not exceed 30°C.
The applicable regulations state that an installation inspection 
must be carried out on a boiler system with an unvented expan-
sion vessel, before it is put into operation. The inspection must 
be documented and carried out by a person qualified for the 
task. A further inspection is required if the boiler or the expan-
sion vessel is replaced.
The boiler is fitted with adjustable base bolts, which can be 
adjusted to level the boiler.

  Do not drill into the cover panels of the boiler

– the residues may harm the electronics.

Siting the boiler

The boiler is approved for installation directly on the floor under the 

High Current Regulations [Starkströmsföreskrifterna]. Wall brackets 

are available as accessories.

Cables and pipework

The cables and pipes must be arranged so it is possible to remove 

the front and top covers after installation.
Low current cables must not be laid parallel to high current cables 

as induction may affect the signal carried by the low current cables.

Safety/supply pipe

If the safety pipe is not connected to an open expansion vessel, it 

is essential for the safety pipe to be equipped with automatic bleed 

valve. Otherwise, air can collect at the top of the tank, damaging the 

immersion heaters.
The safety pipe to the safety valve or the open expansion vessel is 

connected to the supply pipe.

Water quality

Mains water quality is usually classified in terms of its hygiene. 

Water that is high quality from the point of view of hygiene is not 

necessarily suitable for use in a heating system. To avoid problems, 

the water should be analysed from a technical point of view. Any dif-

ferences from standard values should be corrected.
If the volume of the heating system is small, the boiler and heating 

system can be filled with water that is not classified as high qual-

ity boiler water. When the water is heated, some of the oxygen and 

carbon dioxide is carried to the expansion vessel or to bleed valves. 

The rest will react with the metals in the system. This corrosion usu-

ally becomes less important because the same water is circulating, 

which quickly loses its oxygen. It is important to make the system 

watertight so that no new, oxygen-rich water has to be added, and 

to ensure that the water is not oxygenated during installation.

In large systems it is virtually impossible to prevent leaks and oxy-

genation. In such systems, an oxygen-demanding agent can be add-

ed so there is always a slight surplus in the system. These agents 

often contain anti-corrosive additives.

Water quality, based on suitable mains water:

The alkalinity should exceed 60 mg/l to avoid corrosion.

Carbon dioxide contents exceeding 25 mg/l increase the risk of cor-

rosion.

Sulphate contents exceeding 100 mg/l may hasten corrosion, and 

if the sulphate content is higher than the alkalinity, there is a risk 

of copper corrosion.

Hard water produces scale and is not suitable in heating systems.

Very soft water can cause corrosion.

Chloride contents exceeding 100 mg/l make the water aggressive, 

especially combined with lime scale.

Low pH values can cause corrosion – the pH value should be be-

tween 7.5 and 8.5.

The occurrence of carbon dioxide combined with a low pH value 

and hardness value makes the water aggressive.

Frost protection

If the water is mixed with ethylene glycol, make sure it contains ap-

propriate concentrations of anticorrosive additive. When ethylene 

glycol decomposes, one of the by-products is carbon dioxide, which 

increases the risk of corrosion.

Flow requirement

The boiler must have a constant and sufficiently strong flow in order 

to work properly. 

If the flow through the boiler is too slow, the following problems may 

be caused:
-  The difference between the temperature setting and the actual 

temperature achieved in the boiler increases.

-  Erratic operation, which increases wear on the boiler contactors, 

with a consequent reduction in service life.

If the flow is too fast, the following problems may be caused: 

-  Vibrations in the immersion heaters, resulting in noise and reduced 

service life.

-  Unnecessary wear to the system components.

Recommended flow
EP 26 E: 

recommended: 

0.65 l/sec, 

t = 10 °C

   

min: 

0.25 l/sec, 

t = 25 °C

   

max: 

2 l/sec, 

t = 3 °C

EP 42 E: 

recommended: 

1 l/sec, 

t = 10 °C

   

min: 

0.4 l/sec, 

t = 25 °C

   

max: 

2 l/sec, 

t = 5 °C

The boilers can handle zero flow for safety, but for correct running 

and to avoid unnecessary wear, follow the flow recommendations. 

The higher the operating temperature and the greater the required 

temperature accuracy, the higher the flow you should select.

HVAC installation

  From the point of view of safety, the boiler can 

handle zero flow – in other words it is designed so 

it is not damaged if forced circulation stops, for ex-

ample if a valve is closed or a pump stops working, 

leaving just natural circulation. 

The system does not need to be fitted with redun-

dant circulation pumps or a flow switch.

Содержание EP E Series

Страница 1: ...Installation operation and care EP E Series 7 stage electric boilers EP 26E and EP 42E 2011 03 21 utg xxxxxx Ers tter 08 05...

Страница 2: ...tures 4 Technical data 5 HVAC installation 6 Siting the boiler Cables and pipework Safety supply pipe Waterquality Frostprotection Flow requirement HVAC installation 7 Pressure drop diagram Direction...

Страница 3: ...s are shown in bold Numberofpower stages 7 6 5 4 1 2 ON ON OFF OFF ON OFF ON OFF Cirkulationpump 3 OFF ON eco summer mode continuous operation Main fuse EP42 EP26 1 3 125A 100A 80A 63A 50A 35A ON ON O...

Страница 4: ...onnected power according to the current heating requirement The power can be limited to four power stages For safety the boiler can handle zero flow in other words it does not need to be fitted with a...

Страница 5: ...thread 34 Drain valve R15 35 Opening cover for electrical connections 36 Cable bushing 37 Adjustable base bolts EP 26 E EP 42 E Power 26 25 42 kW Current 37 9 61 A Power stage 3 75 6 kW Current stage...

Страница 6: ...e the system watertight so that no new oxygen rich water has to be added and to ensure that the water is not oxygenated during installation In large systems it is virtually impossible to prevent leaks...

Страница 7: ...ted statistical pressure on the suction side Closed expansion system 2 5 bar 100 kW and 110 C The safety and venting valves are mounted on the boiler safety pipe 2 5 bar 100 kW and 110 C The safety va...

Страница 8: ...tallation Electrical installation must be in accordance with the applicable regulations under the supervision of an authorised installer The boiler and water heater must be filled with water before el...

Страница 9: ...wer The temperature control within the boiler itself takes precedence so the boiler temperature setting should be slightly higher than neces sary for the system The boiler Power status light will flas...

Страница 10: ...g 8 PCB 9 Indicator for power group one 10 Indicator for power group two 11 Indicator for power group three Wiring diagram EP 26 E 12 Alarm overheat protection triggered 13 Alarm relay 14 Control swit...

Страница 11: ...eat protection triggered 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 2 3 4 5 6 9 7 8 11 10 12 13 14 15 16 17 18 19 20 21 1 22 23 40 13 Alarm relay 14 Control switch 15 Control fuse 16 Overheat protection power...

Страница 12: ...f the power can be connected immediately after a loss of power lasting longer than three minutes The remaining power is delayed by an hour To test the boiler after it has been without power for exampl...

Страница 13: ...ondition Ask the installer to demonstrate the settings and functions so you know exactly how to operate and care for the system Check the water pressure air may remain in the system for a while after...

Страница 14: ...mited Check the setting see page 8 Number of power stages The boilers is being controlled by a 0 10 V signal The boiler temperature setting is too low Outdoor temperature compensa tion is connected th...

Страница 15: ...ock 3 pole 1 1 16 00 06 End plate 1 1 16 00 09 Jumper 2 pole 6mm 1 1 16 00 11 Jumper 4 pole 6mm 1 1 16 00 12 End support 2 2 16 00 13 Bar bracket 1 1 40 16 00 18 Neutral terminal NPF 35 1 6 6 40 16 00...

Страница 16: ...4644 226358 291 94 Kristianstad www varmebaronen se Sweden info varmebaronen se V rmebaronen AB retains the right to change the specification of included components without prior notice as part of it...

Отзывы: