MVS-1C
Page 3
General installation guidelines
-
It is recommended to install the unit in a hallway to limit the MVS-1C exposure to
noxious gases.
-
In order to avoid condensation problems inside the MVS-1C, it is recommended to
install the module on an inside wall. If it is not possible, use spacers to have an air
gap between the wall and the controller.
-
The MVS-1C should be installed in easy-access location but away from damaging
elements (heat, cold, water, direct sunlight…).
-
Do not install the MVS-1C near high-voltage equipment, power supply or
transformer.
-
When installing the mounting plates onto the back of the enclosure, makes sure to
use a regular screw driver (DO NOT use a drill or electric screw driver) to screw the
tap screws into the plastic holes.
Wiring Procedure
1. Open the MVS-1C controller enclosure.
2. Verify the technical specifications to know which wire to use.
3. Connect the equipment to the 2 black terminal block identified as FAN as shown
in figure 1.
4. Connect the power source to the 2 black terminal block identified as LINE as
shown in figure 1.
5. Make sure that the voltage selector switch is set to the correct voltage before
powering up the MVS-1C (refer to figure 2 for the location of the switch).
6. Power up the MVS-1C controller. Verify that the controller operates correctly.
7.
Close the MVS-1C enclosure. Don’t forget to put a security screw or a padlock.