Page 39
SYMPTOM
CAUSE
REMEDY
Temperature
probe reads
LO
−
Temperature is
below -6°F (-21°C)
−
Probe is disconnected
or defective
−
Check all
connections. If the
problem persists,
and the temperature
is within normal
range, replace the
probe.
Temperature
probe reads
HI
−
Temperature is above
168°F (76°C)
−
Probe is short
circuited or defective
−
Check all
connections. If the
problem persists,
and the temperature
is within normal
range, replace the
probe.
Temperature
average
reads
Err
−
Temperature readings
of the probes used in
the average are too
different and the
control is unable to
calculate a proper
average
−
Make sure all the
probes are working
properly. If so,
contact your local
distributor
Displays are
blank
−
Voltage selector
setting is inaccurate
−
IC-610 is not powered
−
Ten pin flat cable
between the main and
the top boards of the
IC-610 is
disconnected
−
Make sure the
control is powered
−
Make sure the line
voltage selector
switch is properly
set
−
Make sure the 10
pin flat cable is
connected
Display
reads
88888
and
Err
continuously
−
Configuration memory
integrity has been
compromised
−
Download the
configuration once
again (refer to
chapter 3)
TROUBLESHOOTING
www.monitrol.com
Содержание IC-610
Страница 1: ...IC 610 USER S MANUAL www monitrol com ...
Страница 10: ...Page 10 IC 610 Intelligent Control CHAPTER 2 INSTALLATION www monitrol com ...
Страница 11: ...Page 11 www monitrol com ...
Страница 17: ...Page 17 Figure 4 IC 610 Main Board for board 1059 D www monitrol com ...
Страница 25: ...Page 25 www monitrol com ...
Страница 26: ...Page 26 IC 610 Intelligent Control CHAPTER 3 USER S GUIDE www monitrol com ...
Страница 28: ...Page 28 IC 610 Intelligent Control CHAPTER 3 USER S GUIDE www monitrol com ...
Страница 38: ...Page 38 IC 610 Intelligent Control APPENDIX www monitrol com ...
Страница 42: ...Page 42 IC 610 Intelligent Control www monitrol com ...
Страница 44: ...MAV IC 610 Ver 4 2 Rev 04 07 2001 www monitrol com ...