Installation.

Positioning the Vapac

Do’s

Do

 mount the unit as close to the steam distribution pipe(s)

as possible.

Do

 mount the unit at a height convenient for reading the

display window.

Do

 ensure adequate  side access to the electrical section

(min 1000 mm).

Do

 ensure adequate service access to the front of the unit

(min 1000 mm).

Do

 ensure adequate service access below the unit (min 300

mm).

Do

 ensure that the holes above the  airgap between the

electrical and the steam sections remain unobstructed to
allow a free flow of air.

Do

 use the marking on the side of the carton as a template

to mark the mounting hole positions.

Do

 remove the cylinder, if necessary, to access the

mounting holes in the back of the steam section.

Do

 use M6 projecting type wall bolts or equivalent to mount

the unit in position.

Do

 mount units with RDU’s so that steam pipe discharge is

above head height.

Do

 leave minimum 150mm between the top of an RDU and

the ceiling.

Don’ts

Don’t

 mount the unit close to sources of strong  electro-

magnetic emissions e.g. variable speed lift motor drives,
kVa transformers etc.

Don’t

 mount the unit in an unventilated enclosure.

Don’t

 mount in a position requiring ladder access to the

unit.

Don’t

 mount the unit behind a false ceiling or other situation

where an unusual malfunction (e.g. water leak) would
cause damage.

Don’t

 mount the unit in an area which will be hosed down.

Don’t

 install the unit where the ambient temperature can

exceed 35oC.

Don’t

 mount the unit inside a cold-room or other place

where temperature and humidity conditions can cause
condensation on electrical components.

Don’t

 mount the unit where the sound of a contactor

opening/closing and water flow in a pipe would be
unacceptable e.g. libraries, private apartments, etc.

Don’t

 position an RDU to discharge directly over

exspensive equipment, desks or stored materials.

Dimensions in mm and Service Weight in Kg.

Positioning and Dimensions of the Vapac

Fig 1

Mounting Hole Positions.

Fig 2

Steam Outlet Positions

Microvap model

V4

VP4

V8

VP8

V15

VP15

V30

VP30

V40

VP40

V40L

VP40L

V60

VL60

V80

VP80

A

500

630

675

800

800

800

800

800

B

380

380

435

538

538

645

645

857

C

263

263

298

384

384

500

500

384

D

182

182

182

-

-

-

-

-

F

159

159

175

206

206

266

266

212

G

112

112

136

190

190

195

195

175

H

-

-

-

-

-

110

110

350

K

38

38

38

38

38

38

38

38

L

478

478

516

643

643

643

643

643

M

165

165

203

305

305

406

406

610

N

38

38

38

47

47

47

47

47

UNIT Kg.

25

25

30

55

55

90

90

97

RDU Kg.

8

8

12

-

-

-

-

-

RDU & 

Transformer

9.5

9.5

16.5

-

-

-

-

-

Fig

 3

Содержание MICROVAP V4

Страница 1: ...Directives This product will meet the requirements of the Low Voltage Safety Directive 73 23 EEC and the EMC Directive 89 336 EEC when installed in accordance with the instructions contained in this m...

Страница 2: ...vice or exchange hazardous Make sure steam line s have adequate slope min 12 for condensate drainage and use condensate separators if the pipe is lower than the unit Provide adequate support to preven...

Страница 3: ...n t mount in a position requiring ladder access to the unit Don t mount the unit behind a false ceiling or other situation where an unusual malfunction e g water leak would cause damage Don t mount th...

Страница 4: ...pipes horizontal mounted must discharge vertically upward Notes Con t 4 Vertical mounted steam pipe must discharge horizontally facing upstream airflow 5 If the total pressure within the duct air flow...

Страница 5: ...o a condensate separator Always provide a continuous slope Do provide adequate support to prevent sagging a fit pipe clips every 30 50cm or b support straight lengths on cable trays or in heat resista...

Страница 6: ...ally close to the unit a ground earth stud is positioned on the underside of the cabinet Drain capacity per cylinder pump discharge rate of max 16 8 l min at 50 Hz Power supply 17 2 l min at 60 Hz Do...

Страница 7: ...winding circuit to the position marked with the supply Voltage that is to be connected between Microvap power terminals A1 and A2 The transformer primary circuit terminal positions are clearly marked...

Страница 8: ...00V 230 380 415 and 440V and requires on site adjustment to match it to the Voltage connected to Vapac terminals A1 and A2 The transformer 8V secondary supply is not used Important The Vapac transform...

Страница 9: ...9...

Отзывы: