Plumbing Considerations.

Cold water supply.

General

The Electrode Boiler range of units is capable of
operating with a range of water quality raw mains.
The water supply should be within the following
limits :-

Hardness

50 –500 ppm

Conductivity

80 – 1000 

µ

µ

S/cm

Silica

0

Pressure of between 1 - 8 bar.

Water Supply rates
1.2 l/min

V4
V8
V15

VP4
VP8
VP15

2.5 l/min

V40
V30
V60

VP40
VP30
VP60

5.0 l/min

V80

VP80

Do’s

Do

 install a stop-valve/Shut-off valve and a strainer

close to the unit.

Do

 provide a water supply with sufficient pressure

and pipe size to ensure an adequate flow rate to
all units connected to the system.

Do

 use the water connection with nylon nut

provided.

ALL Dimensions in mm

Don'ts

Don’t

 use a wrench or other tool to tighten the water

supply connection - the nylon nut  and  rubber
washer provided, should only require tightening
by hand to effect a seal. If water seepage occurs,
undo the nut to wipe the washer clean and re-
seat it.

Drain connection

.

General

Do's
Do

 ensure metal drain and supply water pipework  is

grounded electrically close to the unit (a
ground/earth stud is positioned on the underside
of the cabinet).

Drain capacity per cylinder
= pump discharge rate of max 16.8 l/min at 50 Hz.
    Power supply                        17.2 l/min at 60 Hz.

Do’s
Do

 use copper or plastic pipe rated for 100 

o

C.

Do

 arrange to discharge drain water from the unit

into a trapped and vented drain at a position
where flash steam rising from the drain line vent
will not pose a problem for the Vapac or other
equipment.

Do

 provide adequate fall for the drain pipework to

alow free flow of water drained from each unit.

Do

 ensure drain line pipe size will accommodate

water being drained at the same time from all the
Vapac units which are connected to it.

Microvap Model

V4
VP4

V8
VP8

V15
VP15

V30
VP30

V40
VP40

V40-L
VP40-L

V60
V60

V80
VP80

A
B
C
D

58

200

-
-

58

200

-
-

79

198

-
-

133
248

-
-

133
248

-
-

193
312

-
-

193
312

-
-

118
237
468
587

  A
  B
  C
  D
  E
  K
  L
  M
  N

F
G
H     S   V

KEY: -

A

Tundish Fill-cup

B

Steam Cylinder

C

Feed Drain Manifold

D

Drain Pump

E

Drain Trap Dish

F

Feed Solenoid Valve

G

Water Connection 

” BSP.

H

Flexible hose 

” BSP.

K

35

 Steam Hose coupling and Hose

Clips.

L

35

 copper or plastic Drain for 110°C

Water with supports.

M

Tundish

N

 U-trap side exit.

S

Optional Strainer

V

Isolation stop cock

V & VP size 4 - 60

          V & VP 80

    

Fig 7

Содержание MICROVAP V4

Страница 1: ...Directives This product will meet the requirements of the Low Voltage Safety Directive 73 23 EEC and the EMC Directive 89 336 EEC when installed in accordance with the instructions contained in this m...

Страница 2: ...vice or exchange hazardous Make sure steam line s have adequate slope min 12 for condensate drainage and use condensate separators if the pipe is lower than the unit Provide adequate support to preven...

Страница 3: ...n t mount in a position requiring ladder access to the unit Don t mount the unit behind a false ceiling or other situation where an unusual malfunction e g water leak would cause damage Don t mount th...

Страница 4: ...pipes horizontal mounted must discharge vertically upward Notes Con t 4 Vertical mounted steam pipe must discharge horizontally facing upstream airflow 5 If the total pressure within the duct air flow...

Страница 5: ...o a condensate separator Always provide a continuous slope Do provide adequate support to prevent sagging a fit pipe clips every 30 50cm or b support straight lengths on cable trays or in heat resista...

Страница 6: ...ally close to the unit a ground earth stud is positioned on the underside of the cabinet Drain capacity per cylinder pump discharge rate of max 16 8 l min at 50 Hz Power supply 17 2 l min at 60 Hz Do...

Страница 7: ...winding circuit to the position marked with the supply Voltage that is to be connected between Microvap power terminals A1 and A2 The transformer primary circuit terminal positions are clearly marked...

Страница 8: ...00V 230 380 415 and 440V and requires on site adjustment to match it to the Voltage connected to Vapac terminals A1 and A2 The transformer 8V secondary supply is not used Important The Vapac transform...

Страница 9: ...9...

Отзывы: