Positioning the steam pipes

General

Steam pipes should be positioned as shown below,
allowing a minimum rate of fall back to the unit of
12% to allow the free flow of condensate back to the
unit. If the above fall is not possible, then
condensate separators must be fitted as shown in
figure 1.
The position of the steam pipe or multipipe in a air-
conditioning system relative to other items such as
bends, filters, heat exchangers, etc., is critical. The
steam pipe must not be located closer to such item,
than the entrainment distance, and must be decided
by the design engineer responsible for the project.

Do's
Do

 obtain project engineer's instruction/drawing for

chosen location of pipe

Do

 obtain project engineer's instruction/drawing for

pipe position relative to the top & bottom of the
duct (or sides if airflow is vertical).

Do

 check if alternative slope of Ø35mm pipe  has

been specified requiring rotation of pipe in its
socket before installation.

Do

 use bracket/lug on the end of Ø54mm pipes for

extra support.

Steam Hose Connection

Do's

Do

 use Vapac steam hose or  well insulated copper

pipe.

Do

 keep steam hose as short as possible (under 2m

for max efficiency).

Do

 arrange to have a vertical rise immediately over

the unit of 300mm.

Do

 use the full height available between the unit

and steam pipe to provide maximum slope (min
12-20% for condensate

to drain back to the steam cylinder (or down to a

condensate separator). Always provide a
continuous slope.

Do

 provide adequate support to prevent sagging

a) fit pipe clips every 30-50cm

    or

b) support straight lengths on cable trays

or in heat resistant plastic pipe.

Do

 ensure radius hose bends are fully supported to

prevent kinks developing when in service.

Do

 add extra insulation to steam hose for longer

runs (2m-5m) and in cold ambient conditions to
avoid excess condensate and reduction in
delivered output.

Don'ts

Don't

 allow steam hose to develop kinks or sags.

Don't

 include horizontal runs or 90

o

 elbows in the

steam line.

Steam Distribution Pipe requirement

Microvap Model

V4
V8
V15
VP4
VP8
VP15

V30
V40
VP30
VP40

V60
V80
VP60
VP80

35mm 

 Pipe    No.

54mm 

. Pipe    No.

1

-

-

1

-

2

 * Duct Pressure   Pa.

+1000

-600

+2000

-600

* For systems with a duct pressure over +1000 Pa. It may
be necessary to fit a suitably sized trap in the water feed
line between the Vapac tundish and the feed drain
manifold to ensure water can enter the cylinder when it is
empty.

35mm 

 Pipe Selection

54mm 

 Pipe Selection

Duct width

B mm

In-duct Length

L mm

Duct width

B mm

In-duct Length

L mm

320-470
470-620
620-770
770-920

920-1070

1070-1200

300
450
600
750
900

1050

700-950

950-1450

1450+

     (Kg)

650 (1.8)
900 (2.2)

1400 (3.2)

R min for 35 

 Pipe = 250mm

R min for 54 

 Pipe = 500mm

Flexible Steam
Pipe.

No Sags!

Distance to first
bend.

VAPAC
HUMIDIFIER

Flexible Steam
Pipe.

Flexible pipe coupling to
connect Steam pipe to Duct
pipe coupling length to allow
for line movement and
expansion. Coupling clamp
with Hose clips each end.

35 or 54 mm
copper or
stainless steel
steam pipe with
Insulation.

Fig 6

Содержание MICROVAP V4

Страница 1: ...Directives This product will meet the requirements of the Low Voltage Safety Directive 73 23 EEC and the EMC Directive 89 336 EEC when installed in accordance with the instructions contained in this m...

Страница 2: ...vice or exchange hazardous Make sure steam line s have adequate slope min 12 for condensate drainage and use condensate separators if the pipe is lower than the unit Provide adequate support to preven...

Страница 3: ...n t mount in a position requiring ladder access to the unit Don t mount the unit behind a false ceiling or other situation where an unusual malfunction e g water leak would cause damage Don t mount th...

Страница 4: ...pipes horizontal mounted must discharge vertically upward Notes Con t 4 Vertical mounted steam pipe must discharge horizontally facing upstream airflow 5 If the total pressure within the duct air flow...

Страница 5: ...o a condensate separator Always provide a continuous slope Do provide adequate support to prevent sagging a fit pipe clips every 30 50cm or b support straight lengths on cable trays or in heat resista...

Страница 6: ...ally close to the unit a ground earth stud is positioned on the underside of the cabinet Drain capacity per cylinder pump discharge rate of max 16 8 l min at 50 Hz Power supply 17 2 l min at 60 Hz Do...

Страница 7: ...winding circuit to the position marked with the supply Voltage that is to be connected between Microvap power terminals A1 and A2 The transformer primary circuit terminal positions are clearly marked...

Страница 8: ...00V 230 380 415 and 440V and requires on site adjustment to match it to the Voltage connected to Vapac terminals A1 and A2 The transformer 8V secondary supply is not used Important The Vapac transform...

Страница 9: ...9...

Отзывы: