Vanguard VGL850N Скачать руководство пользователя страница 6

6

105705

VENTED TYPE DECORATIVE APPLIANCE

VGL850 Series

®

VENTING
INSTALLATION

A B-type venting system must be connected
to the appliance for venting to the outside of
the building.

The following section is provided as a guide
to a standard B-type vent installation.

Standing codes requirements concerning B-
type vent installations may vary within your
state, province or local codes jurisdiction.
Therefore, it is recommended that you check
with your local building codes for specific
requirements or in absence of local codes,
follow Section 7.0 of the current National
Fuel Gas Code NFPA No. 54/ANS Z223.1
and in Canada with CAN/CGA B149 for
Category I systems using double wall B-1
vent pipe
.

This gas appliance must be vented to the
outdoors only and may not be terminated
into an attic space or into a chimney flue
servicing a solid-fuel burning appliance.

This appliance may be vented through a
manufactured chimney system or a masonry
chimney using a B-vent adapter or a chim-
ney liner system if all are listed, inspected
and approved by local codes and/or building
authorities.

The examples shown in Figure 9 are typical
of most B-vent installations and codes prac-
tices.

Example 1:

 Shows the minimum allowable

system height and lateral offset for a 60

°

degree or greater inclination. Code specifies
that offsets at 60

°

 degrees or greater are

considered horizontal and must follow the
75% percent rule for lateral to total vertical
system height. Codes also allows only one
offset in the total system when at 60

°

 de-

grees or greater. The total vertical height in
this example represents the minimum height
of 8 feet and therefore the allowable lateral
is 6 feet when the 75% percent rule applies.
If the lateral length must exceed 75% then
the system must be sized in accordance with
the Category I venting tables.

Maintain
Listed
Clearance

12' Min.

12' Min.

45

°

45

°

6'

8'

12' Min.

60

°

45

°

Position
Firestop

Position
Firestop

Position
Firestop

Listed
Vent Cap

Listed
Vent Cap

Listed
Vent Cap

Maintain
Listed
Clearance

Maintain
Listed
Clearance

Maintain
Listed
Clearance

Maintain
Listed
Clearance

Maintain
Listed
Clearance

Support Each
Lateral At
Least Every
Six (6) Feet

Maintain
Listed
Clearance

10'

EXAMPLE 3

EXAMPLE 2

EXAMPLE 1

Example 2:

 Shows a multiple offset each

at 45

°

 degrees of inclination. Multiple off-

sets are permitted if they do not exceed 60

°

degrees of inclination. The total lengths of
the two offsets are not required to meet the
75% percent allowable rule.

Example 3:

 Shows a single offset at 45

°

degrees of inclination and therefore the
lateral length at 10 feet of offset does not
have to meet the 75% percent rule.

In each case the offsets must be supported
and firestops must be positioned wherever
the vent must pass through a sub-floor,
ceiling joist or an attic overhang. The vent
pipe must terminate vertically into a listed
type vent cap and extend a sufficient height
through an approved roof flashing, roof
jack or a roof thimble. At all points the listed
clearances must be maintained.

Figure 9 - Typical B-Vent Configuration

Содержание VGL850N

Страница 1: ...mediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performe...

Страница 2: ...2 572mm 9 5 8 244mm 27 689mm 10 3 4 273mm Left Side 9 3 4 248mm Right Side 13 330mm 2 3 8 60mm 32 813mm 33 13 16 859mm HEARTH AREA DIMENSIONS TOP VIEW FRONT VIEW RIGHT SIDE VIEW FRONT INSIDE VIEW Fig...

Страница 3: ...warranty will be voided by and DESA disclaims any responsibility for the following actions A Modification of the appliance or any of the components B Use of any component part not ap proved by DESA i...

Страница 4: ...be yondanoutsidewall thiswouldalsoreduce the cutting of joists roof rafters and such Check local codes for any restrictions Projected installations can extend any distance into the room A projection...

Страница 5: ...ppliance see Figure 17 page 9 Figure 7 Rough Opening for Installing in Wall Figure 8 Rough Opening for Corner Installation 41 7 8 1061mm 15 381mm 36 1 4 921mm 59 1 4 1505mm 29 5 8 752mm 21 3 16 538mm...

Страница 6: ...vertical system height Codes also allows only one offset in the total system when at 60 de grees or greater The total vertical height in thisexamplerepresentstheminimumheight of 8 feet and therefore...

Страница 7: ...c tion see Figure 10 VENTING INSTALLATION Continued If venting horizontally through a side wall becomes necessary a listed thimble ap proved for use with B type vent must be used Check with your local...

Страница 8: ...ach the terminal wires to the battery see Figure 14 8 Replace access panel Place top of ac cess panel into opening and slide up Push bottom of access panel in and slide down to install Figure 13 Insta...

Страница 9: ...ncoming Black Iron Gas Line Flexible Gas Line 1 Provided Can Be Extended Out from 3 Sides Typical Exterior Wall Gas Shut Off Installation CAUTION Do not kink flex ible gas line DESA recommends that a...

Страница 10: ...t log piece into the notches on the right side of the front and rear logs see Figure 25 NOTICE Do not put lava rock on burner or under burner Placing lava rock on burner could cause performance proble...

Страница 11: ...s Ifthisisthecase pleaserequest help from someone else CAUTION For use with glass doorscertifiedwiththeappliance only CAUTION Do not operate theappliancewiththeglassdoor removed WARNING Children and a...

Страница 12: ...GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instru...

Страница 13: ...will not require such purging 1 When lit for the first time the appli ance will emit a slight odor for an hour or two This is due to the curing of the logs and burn in of internal paints and lubrican...

Страница 14: ...rgaspressureistoolowor gas quality is bad If so contact your local propane LP gas supplier WIRING DIAGRAM Pilot Burner Pilot Gas Line Thermopile Note Use only original replacement parts This will prot...

Страница 15: ...or sensor not gen erating sufficient voltage 1 Pilot flame may be too low causing safety pilot to drop out REMEDY 1 Check to see if you have gas supply 2 Hold regulator control valve in the PILOT posi...

Страница 16: ...lot lights turn off pilot and trigger the red button again If pilot lights an improper gas air mixture caused the improper lighting and a longer purge period is recommended If pilot will not light che...

Страница 17: ...f page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner...

Страница 18: ...485 105860 02 If in need of replacing have a qualified technician replace it GAS CONTROL VALVE Natural 14512 105861 01 Propane LP 14513 105861 02 If in need of replacing have a qualified technician re...

Страница 19: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 20: ...he responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND...

Отзывы: