8. TROUBLESHOOTING
If the unit does not work properly, reset the unit by unplugging it for one minute and then replug it. If it still not working properly,
refer to table below.
If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where
the problem occurs on the unit.
LED
SIGNAL
E
RROR
TYPE
A
CTION
U
NIT
STATUS
LED flashes GREEN
Thermistor error
Replace the entire port assembly
(fresh air from outside port)
Unit works but will defrost
frequently
LED flashes AMBER
Damper error
Go to point 7
Unit does not work
LED flashes RED
• The door is open and
the unit is not unplugged
• Exhaust motor error
• Put a magnet over the door switch or close the
door and press once on the integrated control
push button to reset the unit.
• Go to 8
Unit does not work
P
ROBLEMS
P
OSSIBLE
CAUSES
Y
OU
SOULD
TRY
THIS
1
The error code E1 is
displayed on Altitude,
Platinum or Deco-Touch wall
control screen.
• Unit not compatible with control.
• The wires may be in reverse position.
• The wires may be misconnected.
• The wires may be broken.
• Check table on page 2 for control compatibility.
• Ensure that the color coded wires have been connected to their
appropriate places.
• Ensure the wires are correctly connected.
• Inspect every wire and replace any that is damaged. If wires are
hidden into walls, test the control using a shorter wire.
2
There is no outside
temperature displayed on
Altitude or Platinum wall
control screen
__
.
• RED wire in control cable damaged or
misconnected.
NOTE: At its very start-up or after a power failure, it takes some
minutes before the outside temperature appears on screen.
The delay duration depends on which operation mode the
wall control is set. The shortest delay is obtained when the
wall control is set on MIN or MAX in VENT Mode.
• Ensure the RED wire is not damaged and properly connected.
3
Altitude, Platinum or
Deco-Touch wall control
screen alternates between
normal display and E3.
• The Altitude, Platinum or Deco-Touch
wall control may be defective.
• Replace the Altitude, Platinum or Deco-Touch wall control.
4
The wall control
does not work.
• Unit integrated control set to low or high
speed (AMBER or GREEN continuous
LED).
• Unit not compatible with control.
• The wires may be in reverse position.
• The wires may be misconnected.
• The wires may be broken.
• Defective wall control.
• Press on the integrated push button until the LED turns off.
• Check table on page 2 for control compatibility.
• Ensure that the color coded wires have been connected to their
appropriate places.
• Ensure the wires are correctly connected.
• Inspect every wire and replace any that are damaged.
• Replace the wall control.
5
Unit does not work (LED not
lit on power up).
• Unit is unplugged.
• No power to power outlet.
• The fuse may be defective.
• J10, J9, or J8 connector(s) may be
unplugged.
• The transformer may be defective
(no 9.5 VAC between J8-4 and J8-5).
• The PCB may be defective.
• Make sure the unit is plugged.
• Test the power outlet with another electrical device (e.g.: a lamp).
If it does not work, call an electrician.
• Check if fuse F1 (located on the PCB) is blown. In that case, replace
fuse F1 as per product nameplate.
• Check the connection of J10, J9, and J8 connector(s).
• With unit powered and J9 connected, check if there is about
9.5 VAC between transformer connector J8-4 and J8-5 (YELLOW
wires). If no, change the transformer.
• Unplug the unit. Disconnect the
main control and the auxiliary
control(s) (if need be). Jump
G
and
B
terminals. Plug the unit
back and wait about 10 seconds.
If the motors run on high speed and the damper opens, the circuit
board is not defective.
NO C NC I OC OL Y R G B
VE0097