8

2. INSTALLATION (

CONT

D

)

 2.6 

I

NSTALLING

 

THE

 D

UCTWORK

 

AND

 R

EGISTERS

 (

CONT

D

)

   2.6.3 

S

IMPLIFIED

 I

NSTALLATION

 (

AS

 

ILLUSTRATED

 

IN

 S

ECTION

 1.3)

 

 

There are 2 methods for connecting the unit to the furnace/air handler:

 

Method 1: Supply-return connection 

Method 2: Return-return without

 

Stale air intake:

 

•  Cut an opening into the furnace/air handler return duct not less than 10 feet (3.1 m) from the furnace/air handler (A+B).

 

•  Connect this opening to the 

Exhaust air from building

 port of the ERV.

 

Fresh air distribution:

 

•  Same instructions as for Method 1 or Method 2, Section 2.6.2.

 

For Method 2 (Return-return), make sure there is a distance of at least 3 feet (0.9 m) between the 2 connections to the 

 furnace/air 

handler.

 

NOTE: For Method 1, it is not essential to synchronize the furnace blower operation with the unit operation, but we recommend it.

    WARNING

When performing duct connections, always use approved tools and materials. Respect all corresponding laws and/or 
safety regulations. Please refer to your local building code.

!

CAUTION

When performing duct connections to the furnace supply duct, this duct must be sized to support the additional 
airflow produced by the ERV. Also, use a steel duct. For a Return-Return installation, the furnace blower must be in 
operation when the ERV is in operation.

VJ0038 

B

VJ0037 

S

TEEL

 

DUCT

M

INIMUM

 18" 

(0.5 

M

)

A+B= 

NOT

 

LESS

 

THAN

 10' (3.1 

M

)

M

INIMUM

 3' 

(0.9 

M

)

A+B= 

NOT

 

LESS

 

THAN

 10' (3.1 

M

)

CAUTION

If using Method 2, make sure the furnace/air handler blower operation is synchronized with the unit operation! See 
Section 4.

Содержание Venmar AVS 41553

Страница 1: ...ERGY STAR requirements only when used in Canada 21784 rev 01 INSTALLATION GUIDE FOR VENMAR AVS UNITS CONSTRUCTO 1 2 ERV AND V NEE 60H ERV Model no 41556 ERV with top ports Model no 41554 ERV with side...

Страница 2: ...sion cord 7 Do not install in a cooking area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicing or clean...

Страница 3: ...NSTALLING 2 EXTERIOR HOODS 10 2 9 INSTALLING THE TANDEM TRANSITION KIT 10 3 CONTROLS 11 13 3 1 INTEGRATED CONTROL 11 3 2 ELECTRICAL CONNECTION TO OPTIONAL WALL CONTROLS 12 13 3 2 1 ELECTRICAL CONNECTI...

Страница 4: ...in the lowest liveable level Homes with more than one level require at least one exhaust register at the highest level See figure at right 1 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM Stal...

Страница 5: ...H0102 2 INSTALLATION 2 1 INSPECT THE CONTENTS OF THE BOX Inspect the exterior of the unit for shipping damage Ensure that there is no damage to the door door latches power cord etc Remove and discard...

Страница 6: ...rew them from the unit Install the latches on their new locations VD0176 Latches on sides of the unit Latches in front of the unit VB0094 VO0089 VO0090 2 4 HOW TO HANG THE UNIT Hang the unit with the...

Страница 7: ...a register must be floor installed direct the airflow up the wall 2 6 2 CENTRAL DRAW POINT SYSTEM AS ILLUSTRATED IN SECTION 1 2 Stale air exhaust ductwork Same as for Fully Ducted System described on...

Страница 8: ...tions to the furnace air handler NOTE For Method 1 it is not essential to synchronize the furnace blower operation with the unit operation but we recommend it WARNING When performing duct connections...

Страница 9: ...of the double collar then pull down the vapor barrier shaded part in illustrations below over the insulation and over the outer ring of double collar Apply duct tape to the joint making an airtight se...

Страница 10: ...e grill Any exhaust from a combustion source Garbage bin and any other source of contamination VD0028 EXHAUST HOOD INTAKE HOOD TAPE AND DUCT TIE 18 457 MM 6 1 8 M 18 457 MM 18 457 MM 6 1 8 M 6 152 MM...

Страница 11: ...control If a problem occurs during the unit operation its integrated control LED 2 will blink The color of the blinking light depends on the type of error detected Refer to Section 8 TROUBLESHOOTING o...

Страница 12: ...between themselves or by touching any other components on the wall control Avoid poor wiring connections To reduce electrical interference noise potential do not run wall control wiring next to contro...

Страница 13: ...Amber light LOW speed Green ligh HIGH speed Blinking light See User Manual Sans lumi re Arr t ou contr l par contr le mural Lumi re ambre Basse vitesse Lumi re verte Haute vitesse Clignotant Voir guid...

Страница 14: ...2 9 5 V class 2 120 V neutral J9 1 J9 2 J9 3 J4 2 J9 4 Exhaust fan motor capacitor Supply fan motor capacitor J8 1 J8 2 J8 4 J8 5 K4 J12 2 J12 1 A1 Damper motor J3 2 J3 1 J2 2 J2 1 F1 J12 5 J12 4 J12...

Страница 15: ...running in defrost while balancing By waiting 10 minutes after plugging the unit in you are assured that the unit is not in a defrost cycle 2 Place the magnehelic gauge on a level surface and adjust i...

Страница 16: ...ommends to contact a certified service depot for all replacement parts and repairs NO DESCRIPTION PART NO 41554 ERV SIDE PORTS 41556 ERV TOP PORTS 41654 ERV SIDE PORTS 41656 ERV TOP PORTS 1 OVAL PORT...

Страница 17: ...l is set The shortest delay is obtained when the wall control is set on MIN or MAX in VENT Mode Ensure the RED wire is not damaged and properly connected 3 Altitude Platinum or Deco Touch wall control...

Страница 18: ...rk but exhaust motor works The supply motor may be defective The supply motor capacitor or the PCB may be defective Plug supply motor to J5 connector and exhaust motor to J4 connector If the integrate...

Отзывы: