background image

15

6. BALANCING THE UNIT

To avoid balancing, the difference between stale air ducts total length and fresh air ducts total length must not exceed 50 ft. However, even 
if the stale air ducts and fresh air ducts lengths are almost equal, your local building codes may require balancing the unit.
If the unit does not need to be balanced, shut all the pressure taps (located on the unit door) with the small plastic plugs included in the 
hardware kit.

 6.1 

W

HAT

 

YOU

 N

EED

 

TO

 B

ALANCE

 

THE

 U

NIT

 

  • A magnehelic gauge capable of measuring 0 to 0.5 inch of water (0 to 125 Pa) and 2 plastic 

tubes.

 

  •  The balancing chart located on the unit door.

 6.2 

P

RELIMINARY

 S

TAGES

 

TO

 B

ALANCE

 

THE

 U

NIT

 

  •  Seal all the unit ductwork with tape. Close all windows and doors.

 

  •  Turn off all exhaust devices such as range hood, dryer and bathroom fans.

 

  •  Make sure the integrated balancing dampers are fully open. Turn the thumb screw (

A

clockwise

 to 

manually open the dampers. Both are located on the Exhaust air to outside port and on Fresh air to 
building port.

 

  •  Make sure all filters are clean (if it is not the first time you balance the unit).

 6.3 

B

ALANCING

 P

ROCEDURE

   1.

  Set the unit to high speed.

 

 

  Make sure that the furnace/air handler blower is ON if the installation is in any way 

 

 

  connected to the ductwork of the cold air return. If not, leave furnace/air handler blower 

 

 

  OFF. If the outside temperature is below 0°C/32°F, make sure the unit is not running in 

 

 

  defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured 

 

 

  that the unit is not in a defrost cycle.)

   2.

 Place the magnehelic gauge on a level surface and adjust it to zero.

   3.

 Connect tubing from gauge to exhaust air flow pressure taps (see diagram at right).

 

 

  Be sure to connect the tubes to their appropriate high/low fittings. If the gauge drops 

 

 

  below zero, reverse the tubing connections.

 

 

  NOTE: It is suggested to start with the exhaust air flow reading because the exhaust has 

 

 

   

typically more restriction than the fresh air, especially in cases of fully ducted 

 

 

   

installations or source point ventilation. Place the magnehelic gauge upright and level. Record equivalent air flow of the 

 

 

   

reading according to the balancing chart.

   4.

 Move tubing to fresh air flow pressure taps (see diagram). Adjust the fresh air balancing damper until the fresh air flow is 

 

 

  approximately the same as the exhaust air flow. If fresh air flow is less than exhaust air flow, then go back and adjust the 

 

 

  exhaust balancing damper to equal the fresh air flow.

   5.

 Secure both dampers thumb screw in place with tape.

   6.

 Write the required air flow information on a label and stick it near the unit for future reference (date, maximum speed air flows, 

 

 

  your name, phone number and business address). 

 

 

NOTE: The unit is considered balanced even if there is a difference of ±10 cfm (or ± 5 l/s or 17 m³/h) between the two air flows.

VP0009

VJ0032 

A

Port with integrated balancing 

damper - Top view

VP0015 

1  12  12  11 
1  12  12  11 

3  13  33 23 

1  12  12  11 
1  12  12  11 

3  13  33 23 

B

ALANCING

 

C

HART

E

XHAUST

 

AIR

 

FLOW

F

RESH

AIR

 

FLOW

Содержание Venmar AVS 41553

Страница 1: ...ERGY STAR requirements only when used in Canada 21784 rev 01 INSTALLATION GUIDE FOR VENMAR AVS UNITS CONSTRUCTO 1 2 ERV AND V NEE 60H ERV Model no 41556 ERV with top ports Model no 41554 ERV with side...

Страница 2: ...sion cord 7 Do not install in a cooking area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicing or clean...

Страница 3: ...NSTALLING 2 EXTERIOR HOODS 10 2 9 INSTALLING THE TANDEM TRANSITION KIT 10 3 CONTROLS 11 13 3 1 INTEGRATED CONTROL 11 3 2 ELECTRICAL CONNECTION TO OPTIONAL WALL CONTROLS 12 13 3 2 1 ELECTRICAL CONNECTI...

Страница 4: ...in the lowest liveable level Homes with more than one level require at least one exhaust register at the highest level See figure at right 1 2 CENTRAL DRAW POINT CONNECTION TO A FORCED AIR SYSTEM Stal...

Страница 5: ...H0102 2 INSTALLATION 2 1 INSPECT THE CONTENTS OF THE BOX Inspect the exterior of the unit for shipping damage Ensure that there is no damage to the door door latches power cord etc Remove and discard...

Страница 6: ...rew them from the unit Install the latches on their new locations VD0176 Latches on sides of the unit Latches in front of the unit VB0094 VO0089 VO0090 2 4 HOW TO HANG THE UNIT Hang the unit with the...

Страница 7: ...a register must be floor installed direct the airflow up the wall 2 6 2 CENTRAL DRAW POINT SYSTEM AS ILLUSTRATED IN SECTION 1 2 Stale air exhaust ductwork Same as for Fully Ducted System described on...

Страница 8: ...tions to the furnace air handler NOTE For Method 1 it is not essential to synchronize the furnace blower operation with the unit operation but we recommend it WARNING When performing duct connections...

Страница 9: ...of the double collar then pull down the vapor barrier shaded part in illustrations below over the insulation and over the outer ring of double collar Apply duct tape to the joint making an airtight se...

Страница 10: ...e grill Any exhaust from a combustion source Garbage bin and any other source of contamination VD0028 EXHAUST HOOD INTAKE HOOD TAPE AND DUCT TIE 18 457 MM 6 1 8 M 18 457 MM 18 457 MM 6 1 8 M 6 152 MM...

Страница 11: ...control If a problem occurs during the unit operation its integrated control LED 2 will blink The color of the blinking light depends on the type of error detected Refer to Section 8 TROUBLESHOOTING o...

Страница 12: ...between themselves or by touching any other components on the wall control Avoid poor wiring connections To reduce electrical interference noise potential do not run wall control wiring next to contro...

Страница 13: ...Amber light LOW speed Green ligh HIGH speed Blinking light See User Manual Sans lumi re Arr t ou contr l par contr le mural Lumi re ambre Basse vitesse Lumi re verte Haute vitesse Clignotant Voir guid...

Страница 14: ...2 9 5 V class 2 120 V neutral J9 1 J9 2 J9 3 J4 2 J9 4 Exhaust fan motor capacitor Supply fan motor capacitor J8 1 J8 2 J8 4 J8 5 K4 J12 2 J12 1 A1 Damper motor J3 2 J3 1 J2 2 J2 1 F1 J12 5 J12 4 J12...

Страница 15: ...running in defrost while balancing By waiting 10 minutes after plugging the unit in you are assured that the unit is not in a defrost cycle 2 Place the magnehelic gauge on a level surface and adjust i...

Страница 16: ...ommends to contact a certified service depot for all replacement parts and repairs NO DESCRIPTION PART NO 41554 ERV SIDE PORTS 41556 ERV TOP PORTS 41654 ERV SIDE PORTS 41656 ERV TOP PORTS 1 OVAL PORT...

Страница 17: ...l is set The shortest delay is obtained when the wall control is set on MIN or MAX in VENT Mode Ensure the RED wire is not damaged and properly connected 3 Altitude Platinum or Deco Touch wall control...

Страница 18: ...rk but exhaust motor works The supply motor may be defective The supply motor capacitor or the PCB may be defective Plug supply motor to J5 connector and exhaust motor to J4 connector If the integrate...

Отзывы: