vanEE AI Series Скачать руководство пользователя страница 21

21

E

RROR

D

ESCRIPTION

S

OLUTION

E26

Supply motor (drive over temp)

STEP 1: Validate if the air exchanger is exposed to ambient temperatures 
within the operating limits (see p. 4)
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Replace the electronic 

assembly.

E32

Exhaust air

fl

 ow

STEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper 
system. Clean 

fi

 lters, distribution registers and outside exhaust hood. Make 

sure no non-return damper is installed in exhaust hood since it can freeze in 
winter. Inspect ducting to ensure it is not squeezed or bent. Plug the unit.
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Remove ducting of the 

supply path. On the LCD screen, select MAX to check if the unit is able to 
reach the selected 

fl

 ow. If so, review the ducting path.

If STEP 2 did not 

fi

 x the problem, perform STEP 3: On the LCD screen, select 

the MIN and MAX 

fl

 ow setting values then reset the unit. MAX 

fl

 ow value will 

display on the LCD screen. If MAX 

fl

 ow is above desired MAX 

fl

 ow, set MAX 

and MIN 

fl

 ows.

If STEP 3 did not 

fi

 x the problem, perform STEP 4: Replace the exhaust 

blower and repeat STEP 3.
If STEP 4 did not 

fi

 x the problem, perform STEP 5: Replace the electronic

assembly.

E33

Exhaust motor (drive over current)

STEP 1: Unplug/plug unit.
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Remove core and clear the 

ventilation wheel from any dirt or obstacles.
If STEP 2 did not 

fi

 x the problem, perform STEP 3: Disconnect J3 (red) and 

connect a spare blower system. If it works, replace exhaust blower.
If STEP 3 did not 

fi

 x the problem, perform STEP 4: Replace the electronic 

assembly.

E37

Exhaust motor (drive foc duration)

E38

Exhaust motor (drive speed
feedback)

E39

Exhaust motor (startup)

E34

Exhaust motor (drive over voltage)

STEP 1: Unplug/plug unit. Under and over voltage may be detected with 
severe in-house power supply 

fl

 uctuation and stop the motor for protection.

If STEP 1 did not 

fi

 x the problem, perform STEP 2: Replace the electronic 

assembly.

E35

Exhaust motor (drive under voltage)

E36

Exhaust motor (drive over temp)

STEP 1: Validate if the air exchanger is exposed to ambiant temperatures 
within the operating limits (see p. 4)
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Replace the electronic 

assembly.

E40

Outside air thermistor

STEP 1: Check if thermistor is well connected in connector J7A.
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Disconnect connector J7A 

and check if the measured resistance (thermistor connector) is within 
5 Kohms to 120 Kohms. If outside the range, replace the thermistor.
If STEP 2 did not 

fi

 x the problem, perform STEP 3: Replace the electronic 

assembly.

E41

Distribution air thermistor

STEP 1: Check if thermistor is well connected in connector J7B.
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Disconnect connector J7B 

and check if the measured resistance (thermistor connector) is within 
5 Kohms to 120 Kohms. If outside the range, replace the thermistor.
If STEP 2 did not 

fi

 x the problem, perform STEP 3: Replace the electronic 

assembly.

E42

PCBA thermistor fault

STEP 1: Replace the electronic assembly.

E43

PCBA temperature over limit

STEP 1: Validate if the air exchanger is exposed to ambiant temperatures 
within the operating limits (see p. 4)
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Replace the electronic assembly.

E50

Wall control communication lost

STEP 1: Unplug unit, inspect wires, plug unit.
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Remove wall control from 

the wall installation and test with a short cable. If it works, bring a new cable 
to the wall installation location.
If STEP 2 did not 

fi

 x the problem, perform STEP 3: Test the air exchanger with 

a spare wall control. If it works, replace the wall control.
If STEP 3 did not 

fi

 x the problem, perform STEP 4: Replace the electronic 

assembly.

E51

Wall control sensor

STEP 1: Unplug unit, inspect wires, plug unit.
If STEP 1 did not 

fi

 x the problem, perform STEP 2: Replace the wall control.

E60

Protection mode

STEP 1: Perform general inspection of the unit (dampers, core, 

fi

 lters).

8. INSTALLER’S TROUBLESHOOTING (

CONT

D

)

Содержание AI Series

Страница 1: ...50H75NT A150H75NS A160H75RT A160H75RS A160H65RT A160H65RS A160E65RT A150E75NT A150E75NS A160E75RT V110H65RT V130H65RT V130H65RS V130E65RT V150H75NT V150H75NS V160H75RT V160H75RS V160H65RT V160H65RS V1...

Страница 2: ...rematurely clogged filters turn the unit OFF during construction or renovation 2 Please read specification label on product for further information and requirements 3 Be sure to duct air outside Do no...

Страница 3: ...ALL CONTROL 11 3 2 ELECTRICAL CONNECTION TO OPTIONAL AUXILIARY WALL CONTROL 12 3 2 1 ELECTRICAL CONNECTION TO 20 40 60 OPTIONAL AUXILIARY WALL CONTROL 12 3 2 2 ELECTRICAL CONNECTION TO DRY CONTACT OPT...

Страница 4: ...th of the insulated flexible ducts to and from the unit HRV units only close to a drain If no drain is close by use a pail to collect run off Away from hot chimneys electrical panel and other fire haz...

Страница 5: ...the mounting brackets see illustration below according to stud s position Insert the provided brackets under the unit frame see illustration hereafter Fix the bracket using the screw no 8 x 3 8 Using...

Страница 6: ...air system return duct at least 10 feet away from the central forced air system A B This 10 ft distance applies only in areas where the outside temperature falls below the freezing point 0 C 32 F NOTE...

Страница 7: ...HIS CONFIGURATION DOES NOT ALLOW RECIRCULATION MODE TO OPERATE Unit should be synchronized with central forced air system operation to avoid condensation and mold growth in central forced air system d...

Страница 8: ...be to the floor drain or to an alternate drain pipe or pail IMPORTANT If using a pail to collect water place the tube end approximately 1 inside the pail in order to prevent water from being drawn bac...

Страница 9: ...transitions to the ports so as not to interfere with ports inner dampers operation A non functioning damper could freeze the unit which could cause damages CAUTION The vapor barrier should remain inta...

Страница 10: ...drainage of water that may accumulate in ducting Insulated ducts must have the same diameter as the ports to ensure proper drainage of water that may accumulate in ducts CAUTION Ducting must not be to...

Страница 11: ...nandUserGuide availableat www vanee ca or www venmar ca Always disconnect the unit before making any connections Failure to cut power could result in electrical shock or damage to the wall control or...

Страница 12: ...higher need in exhaust ventilation NOTE The auxiliary wall control can be used with a 3 wire connection by removing the LED signals This optional wiring will not allow an installation with more than 1...

Страница 13: ...Vent input if not available on the Thermostat Air Exchanger Terminal Blocks Alternate Wiring for Dry Contact Independent Installation Vent Y W C Gf G R J13 OVR LED 12V D D GND J9 External Switch or an...

Страница 14: ...ional Central Forced Air System Wiring Isolated 24VAC OVR LED 12V D D GND Main and Auxilliary Controls Wiring Thermistor R1 RT1 NTC Bridge IPM Motor 1 IPM Motor 1 F3 F2 M2 To J3 F5 F4 Central Forced A...

Страница 15: ...R OPTIONS CONFIGURATION PRESS ON OK BUTTON DURING 4 SECONDS TO MODIFY MAX CFM CONFIGURATION MAX CFM DATA WILL FLASH USE BUTTON TO INCREASE VALUE OR BUTTON TO DECREASE VALUE PRESS ON OK BUTTON TO CONFI...

Страница 16: ...djust the CFM and OK to confirm The house that flashes on the LCD screen indicates which side currently limits the airflow supply or exhaust If the airflow reached is not sufficient the installer can...

Страница 17: ...AHU MODE DISPLAY Depending on unit configuration and or installation the unit could not be able to reach desired set minimum CFM This situation could happen with installed configurations T 2 to T 5 du...

Страница 18: ...1 1 1 1 1 1 1 10 Supply blower assembly SV66141 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 11 Core ERV 65 SV66113 1 1 1 1 Core ERV 75 SV66114 1 1 1 1 Core HRV 65 SV66115 1 1 1 1 1 1 Core HRV 75 SV66116 1 1...

Страница 19: ...T 7 SERVICE PARTS CONT D REPLACEMENT PARTS AND REPAIRS In order to ensure your ventilation unit remains in good working condition you must use the manufacturer s genuine replacement parts only The man...

Страница 20: ...erform STEP 2 Open electrical compartment check if connector J6 blue is well inserted check for any loose wires If STEP 2 did not fix the problem perform STEP 3 If the damper is not moving at all unpl...

Страница 21: ...form STEP 2 Replace the electronic assembly E35 Exhaust motor drive under voltage E36 Exhaust motor drive over temp STEP 1 Validate if the air exchanger is exposed to ambiant temperatures within the o...

Страница 22: ...not fix the problem perform STEP 2 Remove ducting of the supply path On the LCD screen select MAX to check if the unit is able to reach the selected flow If so review the ducting path If STEP 2 did n...

Страница 23: ...Clean if necessary 8 Rotate the blower wheels by hand If one of the wheels does not rotate easily contact your installer 9 Reassemble the components Pay special attention to the filters by making sur...

Страница 24: ...solved contact your installer 3 Condensation inside windows under cold weather conditions Operate the unit at MAX speed during activities generating excess humidity family gatherings extra cooking et...

Страница 25: ...as defined below Building All structures zoned and or erected for the act process or art of human or animal habitation and or the storage or warehousing of goods Residential use Dwelling lodging suite...

Страница 26: ......

Страница 27: ...A160H75RT A160H75RS A160H65RT A160H65RS A160E65RT A150E75NT A150E75NS A160E75RT V110H65RT V130H65RT V130H65RS V130E65RT V150H75NT V150H75NS V160H75RT V160H75RS V160H65RT V160H65RS V160E65RT V150E75NT...

Страница 28: ...r des filtres arr ter l appareil lors de travaux de construction ou de r novation 2 Pour plus de renseignements au sujet de votre appareil veuillez lire les autocollants appos s sur celui ci 3 S assur...

Страница 29: ...E LA COMMANDE MURALE AUXILIAIRE OPTIONNELLE 12 3 2 1 BRANCHEMENT DE LA COMMANDE MURALE AUXILIAIRE OPTIONNELLE 20 40 60 12 3 2 1 BRANCHEMENT DE LA COMMANDE MURALE AUXILIAIRE OPTIONNELLE DE TYPE CONTACT...

Страница 30: ...sol s Appareils HRV proximit d un drain S il n y en a pas se servir d un seau pour r cup rer l coulement loign des chemin es chaudes du panneau des circuits lectriques et autres risques d incendie Pr...

Страница 31: ...supports voir l illustration ci dessous selon la position du des montant s Ins rer les supports fournis sous le ch ssis de l appareil voir l illustration ci contre l aide de la vis no 8 x 3 8 po insta...

Страница 32: ...retour du syst me central air puls au moins 10 pieds de celui ci A B Cette distance de 10 pieds s applique seulement dans les r gions o la temp rature ext rieure descend sous le point de cong lation...

Страница 33: ...r frais vacuation d air vici Aspiration d air frais Distribution d air frais Aspiration d air vici NOTE Pour ce type de configuration l option T 4 doit tre s lectionn e l cran ACL lors de l auto balan...

Страница 34: ...urnies attacher le boyau tel qu illustr Raccorder le boyau au drain du sous sol ou un seau IMPORTANT Si un seau est utilis pour recueillir l eau placer le bout du boyau environ 1 po du bord du seau af...

Страница 35: ...s conduits rigides l appareil au moyen d une section de 12 po de conduit flexible Pour raccorder les conduits rigides isol s l appareil c t froid l aide de conduit flexible isol suivre la proc dure la...

Страница 36: ...cumuler dans les conduits Les conduits isol s doivent avoir le m me diam tre que les bouches de l appareil pour assurer un drainage ad quat de l eau qui pourrait s accumuler dans les conduits ATTENTIO...

Страница 37: ...ncher l appareil avant d effectuer toutes connexions Le fait de ne pas d brancher l appareil pourrait causer un choc lectrique ou endommager l appareil la commande murale ou le module lectronique l in...

Страница 38: ...ation NOTE La commande murale auxiliaire peut tre utilis e avec une connexion 3 fils en enlevant les signaux LED Ce branchement optionnel ne permet pas une installation avec plus d une commande murale...

Страница 39: ...Dry contact can be used to activate Vent input if not available on the Thermostat Borniers de l changeur d air Branchement alternatif pour installation ind pendante de type contact sec Vent Y W C Gf...

Страница 40: ...tionnel syst me central air puls Isol 24VCA OVR LED 12V D D GND C blage des commandes principales et auxiliaires Thermistor R1 RT 1 CTN Pont IPM Moteur 1 IPM Moteur 1 F3 F2 M2 J 3 F5 F4 Relais syst me...

Страница 41: ...N LA PROCHAINE CONFIGURATION D OPTION S AFFICHERA APPUYER SUR LE BOUTON OK POUR CONFIRMER LA VALEUR UTILISER LE BOUTON POUR AUGMENTER LA VALEUR OU LE BOUTON POUR DIMINUER LA VALEUR LA DONN E MIN PI MI...

Страница 42: ...affichera l cran ACL Utiliser pour ajuster le pi3 min et OK pour confirmer La maison qui clignote l cran ACL indique le c t qui limite le d bit d air air frais ou air vici Si le d bit d air atteint es...

Страница 43: ...t gr e 6 3 AFFICHAGE DU MODE AHU Selon la configuration de l appareil et ou l installation l appareil pourrait ne pas tre capable d atteindre le pi3 min minimum r gl d sir Cette situation pourrait sur...

Страница 44: ...ue SV66147 Boyau 1 2 po SV00592 Non illustr VL0086 B C D E F G H I J K L M N P O Consulter la page suivante pour obtenir le num ro de pi ce correspondant au mod le de l appareil de ventilation 2 2 2 2...

Страница 45: ...REMPLACEMENT SUITE PI CES DE REMPLACEMENT ET SERVICE Pour assurer le bon fonctionnement de votre appareil vous devez toujours utiliser des pi ces d origine provenant du fabricant Les pi ces d origine...

Страница 46: ...ectrique v rifier si le connecteur J6 bleu est bien ins r v rifier s il y a des fils mal fix s Si l TAPE 2 n a pas r gl le probl me effectuer l TAPE 3 Si le volet ne bouge pas du tout d brancher J5 bl...

Страница 47: ...le probl me effectuer l TAPE 2 Remplacer l assemblage lectronique E35 Moteur vacuation sous tension E36 Moteur vacuation surchauffe TAPE 1 Valider si l changeur d air est expos des temp ratures ambia...

Страница 48: ...i l TAPE 1 n a pas r gl le probl me effectuer l TAPE 2 Enlever le conduit d alimentation l cran ACL s lectionner MAX pour v rifier si l appareil est capable d atteindre le d bit s lectionn Si c est le...

Страница 49: ...air Nettoyer au besoin 8 Faire tourner les roues des moteurs manuellement Si l une d entre elles tourne difficilement contacter votre installateur 9 Remettre les composantes en place Accorder une att...

Страница 50: ...ques froides Faire fonctionner l appareil vitesse MAX au cours d activit s produisant un exc s d humidit rassemblements familiaux pr paration de plats cuisin s etc Laisser les rideaux entrouverts pour...

Страница 51: ...ruction utilis e ou destin e tre utilis e pour abriter ou recevoir des personnes des animaux ou des choses Usage r sidentiel Habitation logement suite B timent ou partie de b timent servant ou destin...

Страница 52: ......

Отзывы: