background image

11

5. CONTROLS

5.1 I

NTEGRATED

 C

ONTROL

All units are equipped with an integrated control, located in front of the electrical compartment. Use the 
push button (

1

) to control the unit. The LED (

2

) will then show on which mode the unit is in.

 

NOTES:  1.  The integrated control 

must be turned OFF 

to use an optional main control.

 

2. If an optional auxiliary control is used, if activated, this auxiliary control will override the 

optional main control.

If a problem occurs during the unit operation, its integrated control LED (2) will blink. The color of the blinking light depends on the 
type of error detected. Refer to Section 12 Troubleshooting on pages 19 and 20 for further details.

5.1.1 B

OOT

 S

EQUENCE

The unit boot sequence is similar to a personnal computer boot sequence. Each time the unit is plugged after being unplugged, or 
after a power failure, the unit will perform a 30-second booting sequence before starting to operate. During the booting sequence, 
the integrated control LED will light GREEN (unit set in normal defrost) or AMBER (unit set in extended defrost) for 5 seconds, and 
then will shut off for 2 seconds. After that, the LED will light RED for the rest of the booting sequence. During this RED light phase, 
the unit is checking and resetting the motorized damper position. Once the motorized damper position completely set, the RED 
light turns off and the booting sequence is done.

NOTE: No command will be taken until the unit is fully booted.

5.1.2 S

ETTING

 E

XTENDED

 D

EFROST

The unit is factory set to normal defrost. In cold region, it may be necessary to setup extended defrost. During 
the first 5 seconds of booting sequence, while the integrated control LED is GREEN, press on push button until 
the LED turns AMBER (about 3 seconds).

Refer to table below to see how to operate the unit using its integrated control.

P

RESS

 

ON

 

PUSH

 

BUTTON

LED C

OLOR

R

ESULTS

O

NCE

A

MBER

U

NIT

 

IS

 

ON

 L

OW

 S

PEED

T

WICE

G

REEN

U

NIT

 

IS

 

ON

 H

IGH

 S

PEED

T

HREE

 T

IMES

N

O

 L

IGHT

U

NIT

 

IS

 OFF

5.2 E

LECTRICAL

 C

ONNECTION

 

TO

 O

PTIONAL

 W

ALL

 C

ONTROL

For more convenience, this unit can also be controlled using an optional main wall control.

Always disconnect the unit before making any connections. Failure in disconnecting power could result in electrical 
shock or damage of the wall control or electronic module inside the unit.

Never install more than one optional main wall control per unit. Make sure that the wires do not short-circuit 
between themselves or by touching any other components on the wall control. Avoid poor wiring connections. To 
reduce electrical interference (noise) potential, do not run wall control wiring next to control contactors or near 
light dimming circuits, electrical motors, dwelling/building power or lighting wiring, or power distribution panel.

VD0278

1

2

VD0281

CAUTION

WARNING

!

Содержание 100H

Страница 1: ...O 100H PART NO 1601717 THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY NATURAL RESOURCES CANADA AND THE US EPA THEY MEET ENERGY STAR REQUIREMENTS ONLY WHEN...

Страница 2: ...ng area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicing or cleaning this unit it is recommended to we...

Страница 3: ...ACE 8 4 6 CONNECTING THE DUCTS TO THE UNIT 9 4 7 INSTALLING THE EXTERIOR HOODS 10 4 8 CONNECTING THE DRAIN 10 5 CONTROLS 11 12 5 1 INTEGRATED CONTROL 11 5 1 1 BOOT SEQUENCE 11 5 1 2 SETTING EXTENDED D...

Страница 4: ...10 20 27 17 10 20 10 15 NOTE The NOVO Performance Charts are listed on the specification sheets of these units Visit our website at www vanee ca to access those documents 2 4 DIMENSIONS 17 432 mm 17...

Страница 5: ...xhausted from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to bedrooms and principal living areas 3 TYPICAL INSTALLATIONS 3 1 FULLY DUCTED SYSTE...

Страница 6: ...aintenance and to the control panel on the side of the unit Close to an exterior wall so as to limit the length of the insulated flexible duct to and from the unit Close to a drain If no drain is clos...

Страница 7: ...herefore a 5 duct or larger is an appropriate choice for both end branches NOTE A 4 duct would have been too small because the maximum acceptable value for a 4 duct is 40 cfm 4 4 1 EXAMPLE OF CALCULAT...

Страница 8: ...ng to occupant level Never install a stale air exhaust register in a room where there is a combustion device such as a gas furnace a gas water heater or a fireplace The ductwork is intended to be inst...

Страница 9: ...f the double collar Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it completely Fasten in place the vapor barrier using the port strap included in unit pa...

Страница 10: ...e hoods An Anti Gust Intake Hood should be installed in regions where a lot of snow is expected to fall EXHAUST HOOD INTAKE HOOD 18 457 MM 18 457 MM 6 152 MM 6 1 8 M 6 1 8 M 18 457 MM OPTIONAL DUCT LO...

Страница 11: ...motorized damper position completely set the RED light turns off and the booting sequence is done NOTE No command will be taken until the unit is fully booted 5 1 2 SETTING EXTENDED DEFROST The unit i...

Страница 12: ...orrectly inserted but not wire B 5 2 1 ELECTRICALCONNECTION TO PLATINUM MAIN WALL CONTROL NO C NC I OC OL Y R G B VE0174 SMART SET MODE PREF 5 2 2 ELECTRICAL CONNECTION TO DECO TOUCH MAIN WALL CONTROL...

Страница 13: ...ECTOR NO C NC I OC OL Y R G B VE0108A Never connect a 120 volt AC circuit to the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blower contr...

Страница 14: ...optional see notes 3 4 VE0257A COLOR CODE BK BLACK BL BLUE BN BROWN GY GRAY GN GREEN Critical characteristic reed switch JU1 3 2 1 NOTES 1 For continued fire protection Use specified UL listed CSA Cer...

Страница 15: ...ncing damper until the FRESH air flow is approximately the same as the EXHAUST air flow If FRESH air flow is less than EXHAUST air flow then go back and adjust the exhaust balancing damper to equal th...

Страница 16: ...tallation sheet included with the wall control VC0117 9 2 OPTIONAL AUXILIARY CONTROLS First turn OFF the main control device before checking the optional auxiliary controls 20 40 60 MINUTE PUSH BUTTON...

Страница 17: ...e user understands how to use the controls as described in the user manual Risk of electric shocks Before performing any maintenance or servicing always disconnect the unit from its power source Do no...

Страница 18: ...3 17 Door latches and screws 00886 2 00601 4 00886 2 00601 4 18 Balancing damper 02253 02253 19 Balancing double collar port 02256 02256 Terminal connector 16416 16416 Hardware kit 20510 20510 Not sho...

Страница 19: ...integrated control LED flashes AMBER and unit is OFF Motor won t turn Clean the exterior air intake port Replace the unit thermistor Check for the proper operation of the unit damper replace if neces...

Страница 20: ...Section 7 Wiring Diagram Check if the fuse F1 is intact If all the readings correspond to the right voltage values the circuit board is not defective If one or both readings are different change the c...

Отзывы: