8.3 B

ALANCING

 P

ROCEDURE

1.

  Set the unit to high speed.

 

Make sure that the furnace/air handler blower is ON if the installation is in any way connected to the ductwork of the cold air return. If 
not, leave furnace/air handler blower OFF. If the outside temperature is below 0°C/32°F, make sure the unit is not running in defrost 
while balancing. (By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a defrost cycle.)

2.

  Place the magnehelic gauge on a level surface and adjust it to zero.

3.

 Connect tubing from gauge to EXHAUST air flow pressure taps (see diagram 

at right). Be sure to connect the tubes to their appropriate high/low fittings. If the 
gauge drops below zero, reverse the tubing connections.

 

NOTE:  It is suggested to start with the exhaust air flow reading because the 

exhaust has typically more restriction than the fresh air. 

 

Place the magnehelic gauge upright and level. Record equivalent AIR FLOW of 
the reading according to the balancing chart.

4.

 Move tubing to FRESH air flow pressure taps (see diagram). Adjust the fresh 

air balancing damper until the FRESH air flow is approximately the same as 
the EXHAUST air flow. If FRESH air flow is less than EXHAUST air flow, then 
go back and adjust the exhaust balancing damper to equal the FRESH air flow.

5.

  Secure both dampers in place with a fastening screw.

6.

 Write the required air flow information on a label and stick it near the unit for 

future reference (date, maximum speed air flows, your name, phone number 
and business address).

7.

  Install 4 pressure taps plugs (included in parts bag).

NOTES:  1.  Use conversion chart provided with the unit to convert magnehelic gauge readings to equivalent cfm values.

 

2.  The unit is considered balanced even if there is a difference of ±10% between the two air flows.

8. BALANCING 

THE UNIT

8.1 W

HAT

 

YOU

 N

EED

 

TO

 B

ALANCE

 

THE

 U

NIT

 

•   A magnehelic gauge capable of measuring 0 to 0.5 inch of water 

 

  (0 to 125 Pa) and 2 plastic tubes.

 

•   The balancing chart of the unit.

VP0009

VD0280

8.2 P

RELIMINARY

 S

TAGE

 

TO

 B

ALANCE

 

THE

 U

NIT

 

•  Seal all the unit ductwork with tape. Close all windows and doors.

 

•  Turn off all exhaust devices such as range hood, dryer and bathroom fans.

 

•  Make sure the integrated balancing dampers are fully open.

 

•  Make sure all filters are clean (if it is not the first time the unit is balanced).

VP0022

E

XHAUST

 

AIR

 

FLOW

F

RESH

 

AIR

 

FLOW

Содержание 100H

Страница 1: ...O 100H PART NO 1601717 THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY NATURAL RESOURCES CANADA AND THE US EPA THEY MEET ENERGY STAR REQUIREMENTS ONLY WHEN...

Страница 2: ...ng area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicing or cleaning this unit it is recommended to we...

Страница 3: ...ACE 8 4 6 CONNECTING THE DUCTS TO THE UNIT 9 4 7 INSTALLING THE EXTERIOR HOODS 10 4 8 CONNECTING THE DRAIN 10 5 CONTROLS 11 12 5 1 INTEGRATED CONTROL 11 5 1 1 BOOT SEQUENCE 11 5 1 2 SETTING EXTENDED D...

Страница 4: ...10 20 27 17 10 20 10 15 NOTE The NOVO Performance Charts are listed on the specification sheets of these units Visit our website at www vanee ca to access those documents 2 4 DIMENSIONS 17 432 mm 17...

Страница 5: ...xhausted from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to bedrooms and principal living areas 3 TYPICAL INSTALLATIONS 3 1 FULLY DUCTED SYSTE...

Страница 6: ...aintenance and to the control panel on the side of the unit Close to an exterior wall so as to limit the length of the insulated flexible duct to and from the unit Close to a drain If no drain is clos...

Страница 7: ...herefore a 5 duct or larger is an appropriate choice for both end branches NOTE A 4 duct would have been too small because the maximum acceptable value for a 4 duct is 40 cfm 4 4 1 EXAMPLE OF CALCULAT...

Страница 8: ...ng to occupant level Never install a stale air exhaust register in a room where there is a combustion device such as a gas furnace a gas water heater or a fireplace The ductwork is intended to be inst...

Страница 9: ...f the double collar Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it completely Fasten in place the vapor barrier using the port strap included in unit pa...

Страница 10: ...e hoods An Anti Gust Intake Hood should be installed in regions where a lot of snow is expected to fall EXHAUST HOOD INTAKE HOOD 18 457 MM 18 457 MM 6 152 MM 6 1 8 M 6 1 8 M 18 457 MM OPTIONAL DUCT LO...

Страница 11: ...motorized damper position completely set the RED light turns off and the booting sequence is done NOTE No command will be taken until the unit is fully booted 5 1 2 SETTING EXTENDED DEFROST The unit i...

Страница 12: ...orrectly inserted but not wire B 5 2 1 ELECTRICALCONNECTION TO PLATINUM MAIN WALL CONTROL NO C NC I OC OL Y R G B VE0174 SMART SET MODE PREF 5 2 2 ELECTRICAL CONNECTION TO DECO TOUCH MAIN WALL CONTROL...

Страница 13: ...ECTOR NO C NC I OC OL Y R G B VE0108A Never connect a 120 volt AC circuit to the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blower contr...

Страница 14: ...optional see notes 3 4 VE0257A COLOR CODE BK BLACK BL BLUE BN BROWN GY GRAY GN GREEN Critical characteristic reed switch JU1 3 2 1 NOTES 1 For continued fire protection Use specified UL listed CSA Cer...

Страница 15: ...ncing damper until the FRESH air flow is approximately the same as the EXHAUST air flow If FRESH air flow is less than EXHAUST air flow then go back and adjust the exhaust balancing damper to equal th...

Страница 16: ...tallation sheet included with the wall control VC0117 9 2 OPTIONAL AUXILIARY CONTROLS First turn OFF the main control device before checking the optional auxiliary controls 20 40 60 MINUTE PUSH BUTTON...

Страница 17: ...e user understands how to use the controls as described in the user manual Risk of electric shocks Before performing any maintenance or servicing always disconnect the unit from its power source Do no...

Страница 18: ...3 17 Door latches and screws 00886 2 00601 4 00886 2 00601 4 18 Balancing damper 02253 02253 19 Balancing double collar port 02256 02256 Terminal connector 16416 16416 Hardware kit 20510 20510 Not sho...

Страница 19: ...integrated control LED flashes AMBER and unit is OFF Motor won t turn Clean the exterior air intake port Replace the unit thermistor Check for the proper operation of the unit damper replace if neces...

Страница 20: ...Section 7 Wiring Diagram Check if the fuse F1 is intact If all the readings correspond to the right voltage values the circuit board is not defective If one or both readings are different change the c...

Отзывы: