background image

8

4. INSTALLATION (

CONT

D

)

4.5 I

NSTALLING

 

THE

 D

UCTWORK

 

AND

 

THE

 R

EGISTERS

S

TALE

 

AIR

 

EXHAUST

 

DUCTWORK

:

• Install registers in areas where contaminants are produced: Bathrooms, laundry room, etc.

 

• Install registers 6 to 12 inches (152 to 305 mm) from the ceiling on an interior wall OR install them in the ceiling (the duct leading 

to the register must never go through the attic).

• If a register is installed in the kitchen, it must have a washable filter and be located at least 4 feet (1.2 m) from the range.
• If possible, measure the velocity of the air flowing through the registers. If the velocity is higher than 400 ft/min. (122 m/min), then 
  the register type is too small. Replace with a larger one.

F

RESH

 

AIR

 

DISTRIBUTION

 

DUCTWORK

:

• Install registers in every bedrooms, in living room and a minimum of one per level without bedroom nor living room.

 

• Install registers high on the walls with air flow directed towards the ceiling. The horizontal draft must be perceptible at 3 ft. (910 mm) 

from register (The cooler air will then cross the upper part of the room and mix with room air before descending to occupant level.)

Never install a stale air exhaust register in a room where there is a combustion device, such as a gas furnace, a 
gas water heater or a fireplace. 

The ductwork is intended to be installed in compliance with all local and national codes that are applicable.

4.5.1 F

ULLY

 D

UCTED

 S

YSTEM

 

(

AS

 

ILLUSTRATED

 

IN

 S

ECTION

 3.1)

S

TALE

 

AIR

 

EXHAUST

 

DUCTWORK

:

Same as for Fully Ducted System, described on point 4.5.1 above)

F

RESH

 

AIR

 

DISTRIBUTION

:

4.5.2 S

YSTEM

 C

OMBINED

 

WITH

 

A

 F

URNACE

 

(

AS

 

ILLUSTRATED

 

IN

 S

ECTION

 3.2)

When performing duct connection to the furnace, installation must be done in accordance with all applicable 
codes and standards. Please refer to your local building code.

 

• Cut an opening into the furnace return duct not less than 10 feet (3.1 m) from the 

furnace (

A+B

).

 

• Connect this opening to one end of the top section of a metal T coupling (the T will 

be reversed, see shaded part in illustration at right).

 

• Connect the other end of the T coupling top section to the fresh air distribution port 

of the HRV (see illustration at right)

 

NOTE:  For this case, it is essential that the furnace blower runs when the unit is in 

operation. Synchronize the furnace blower operation with the HRV operation 
(see Section 6).

B

A

VJ0089

A+B= 

NOT

 

LESS

 

THAN

 10’ (3.1 

M

)

CAUTION

WARNING

!

WARNING

!

Содержание 100H

Страница 1: ...O 100H PART NO 1601717 THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY GUIDELINES SET BY NATURAL RESOURCES CANADA AND THE US EPA THEY MEET ENERGY STAR REQUIREMENTS ONLY WHEN...

Страница 2: ...ng area or connect directly to any appliances 8 Do not use to exhaust hazardous or explosive materials and vapors 9 When performing installation servicing or cleaning this unit it is recommended to we...

Страница 3: ...ACE 8 4 6 CONNECTING THE DUCTS TO THE UNIT 9 4 7 INSTALLING THE EXTERIOR HOODS 10 4 8 CONNECTING THE DRAIN 10 5 CONTROLS 11 12 5 1 INTEGRATED CONTROL 11 5 1 1 BOOT SEQUENCE 11 5 1 2 SETTING EXTENDED D...

Страница 4: ...10 20 27 17 10 20 10 15 NOTE The NOVO Performance Charts are listed on the specification sheets of these units Visit our website at www vanee ca to access those documents 2 4 DIMENSIONS 17 432 mm 17...

Страница 5: ...xhausted from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to bedrooms and principal living areas 3 TYPICAL INSTALLATIONS 3 1 FULLY DUCTED SYSTE...

Страница 6: ...aintenance and to the control panel on the side of the unit Close to an exterior wall so as to limit the length of the insulated flexible duct to and from the unit Close to a drain If no drain is clos...

Страница 7: ...herefore a 5 duct or larger is an appropriate choice for both end branches NOTE A 4 duct would have been too small because the maximum acceptable value for a 4 duct is 40 cfm 4 4 1 EXAMPLE OF CALCULAT...

Страница 8: ...ng to occupant level Never install a stale air exhaust register in a room where there is a combustion device such as a gas furnace a gas water heater or a fireplace The ductwork is intended to be inst...

Страница 9: ...f the double collar Pull down the vapor barrier shaded part in illustrations below over the outer ring to cover it completely Fasten in place the vapor barrier using the port strap included in unit pa...

Страница 10: ...e hoods An Anti Gust Intake Hood should be installed in regions where a lot of snow is expected to fall EXHAUST HOOD INTAKE HOOD 18 457 MM 18 457 MM 6 152 MM 6 1 8 M 6 1 8 M 18 457 MM OPTIONAL DUCT LO...

Страница 11: ...motorized damper position completely set the RED light turns off and the booting sequence is done NOTE No command will be taken until the unit is fully booted 5 1 2 SETTING EXTENDED DEFROST The unit i...

Страница 12: ...orrectly inserted but not wire B 5 2 1 ELECTRICALCONNECTION TO PLATINUM MAIN WALL CONTROL NO C NC I OC OL Y R G B VE0174 SMART SET MODE PREF 5 2 2 ELECTRICAL CONNECTION TO DECO TOUCH MAIN WALL CONTROL...

Страница 13: ...ECTOR NO C NC I OC OL Y R G B VE0108A Never connect a 120 volt AC circuit to the terminals of the furnace interlock standard wiring Only use the low voltage class 2 circuit of the furnace blower contr...

Страница 14: ...optional see notes 3 4 VE0257A COLOR CODE BK BLACK BL BLUE BN BROWN GY GRAY GN GREEN Critical characteristic reed switch JU1 3 2 1 NOTES 1 For continued fire protection Use specified UL listed CSA Cer...

Страница 15: ...ncing damper until the FRESH air flow is approximately the same as the EXHAUST air flow If FRESH air flow is less than EXHAUST air flow then go back and adjust the exhaust balancing damper to equal th...

Страница 16: ...tallation sheet included with the wall control VC0117 9 2 OPTIONAL AUXILIARY CONTROLS First turn OFF the main control device before checking the optional auxiliary controls 20 40 60 MINUTE PUSH BUTTON...

Страница 17: ...e user understands how to use the controls as described in the user manual Risk of electric shocks Before performing any maintenance or servicing always disconnect the unit from its power source Do no...

Страница 18: ...3 17 Door latches and screws 00886 2 00601 4 00886 2 00601 4 18 Balancing damper 02253 02253 19 Balancing double collar port 02256 02256 Terminal connector 16416 16416 Hardware kit 20510 20510 Not sho...

Страница 19: ...integrated control LED flashes AMBER and unit is OFF Motor won t turn Clean the exterior air intake port Replace the unit thermistor Check for the proper operation of the unit damper replace if neces...

Страница 20: ...Section 7 Wiring Diagram Check if the fuse F1 is intact If all the readings correspond to the right voltage values the circuit board is not defective If one or both readings are different change the c...

Отзывы: