4.3 Defaulting the static IP address
The static IP address can be reset to the default value of 192.168.1.60.
1. Power down the ACTpro Controller.
Ensure nothing is connected to the tamper input terminal and the tamper spring is
not pressed, otherwise the following steps will factory default the controller losing
all information.
2. Set the DHCP DIP switch 1 to
OFF
.
3. Set the DEFAULT DIP switch 2 to
ON
.
4. Re-apply power.
5. Wait approximately 5 seconds, until the controller confirms default completed by sounding the
buzzer.
6. Remove power.
7. Set the DEFAULT DIP switch 2 to
OFF
.
8. Re-apply power.
Note:
The static IP address can be changed via the web interface or using ACT Software.
4.4 Changing static IP address on the ACTpro Controller
1. Connect ACTpro Controller to the IP network.
2. Open a web browser on a PC (for example, Microsoft Internet Explorer, Google Chrome, etc.).
3. Enter http://<NetBIOS address>, e.g. http://ACT1520E-07116
4. Logon details:
Username:
installer
Password:
999999
5. Choose Communication menu and set the following:
l
Static IP Address
l
Network Mask
l
Default Gateway
6. Press
Save
.
Note:
Use the new IP address when connecting to the
controller.
ACTpro-1500/-15002A/-1500PoE Door Controller – Installation and Operating Instructions
Defaulting the Controller and IP Address
Configuration
© Vanderbilt 2019
16
A-100535-c
15.03.2019