2. Wire the fire alarm panel (A) to the ACTpro-1500 as shown:
While the 0V signal is maintained at the AUX input on Door 1, the doors in the
Fire Doors
group
maintain normal operation.
When the 0V signal is removed, the doors in the
Fire Doors
group are unlocked. The fire doors remain
unlocked until the 0V signal is restored.
3.5 Interlock/airlock configuration
To allow only one door to open at a time:
1. Wire the airlock doors.
Link OP3 and AUX I for each new door. For example, the following diagram shows how to
interlock two doors: when the first door is open, the second door is locked, and vice versa.
To interlock additional doors, continue linking OP3 and AUX I for each new door.
2. In ACT Install, for each airlock door, click
Advanced Setup > Doors >
<Door name>
>
Operations
, select the
Interlock
check box, then click
Save
.
When
Interlock
is enabled on a door, the door is locked when the AUX input is active.
When the door is open, OP3 is active and pulls Aux I low (0V) on all interlock doors.
ACTpro-1500/-15002A/-1500PoE Door Controller – Installation and Operating Instructions
Wiring