ACTpro-1500/-15002A/-1500PoE Door Controller

Installation and Operating Instructions

Document ID: A-100535-c

Edition date: 15.03.2019

Содержание ACTpro-1500

Страница 1: ...ACTpro 1500 15002A 1500PoE Door Controller Installation and Operating Instructions Document ID A 100535 c Edition date 15 03 2019 ...

Страница 2: ...ares that this equipment type is in compliance with the following EU Directives for CE marking Directive 2014 30 EU Electromagnetic Compatibility Directive Directive 2011 65 EU Restriction of the use of certain hazardous substances Directive The full text of the EU declaration of conformity is available at http van fyi Link DoC ACTpro 15002A Hereby Vanderbilt International IRL Ltd declares that th...

Страница 3: ...0 2 3 4 Tamper 10 3 Wiring 11 3 1 Typical wiring of ACTpro 1500 11 3 2 Wiring exit readers 12 3 3 Adding the OSDP EOL Jumper for OSDP Readers 12 3 4 Fire override configuration 12 3 5 Interlock airlock configuration 13 3 6 Intruder panel wiring 14 4 Defaulting the Controller and IP Address Configuration 15 4 1 Factory default the Controller DIP switch 2 15 4 2 DHCP static IP addressing DIP switch ...

Страница 4: ...x 330 x 80 Controller Weight kg 0 4 2 2 2 2 Operating Temperature 10 to 50 C 10 to 40 C 75 RH non condensing 10 to 40 C 75 RH non condensing Operating Environment Surface mounting Internal use only Surface mounting Internal use only Surface mounting Internal use only Enclosure Material ABS 1 2mm steel grey powder coated 1 2mm steel grey powder coated LED Status Indicators Yes Yes Yes PSU Fault Out...

Страница 5: ... A 150mA pk pk max N A Output Load output fuse N A F2 0A N A Output Overload N A Electronic shutdown until overload or short circuit removed Under mains power only N A 1 1 2 Relay load When used with inductive loads Maglock Strike locks the following ratings apply ACTpro 1500 ACTpro 15002A ACTpro 1500PoE Main relay 1 5A 30VDC 1 5A 50VAC 1 5A 30VDC 1 5A 50VAC 1 5A 30VDC 1 5A 50VAC Aux relay 400mA 3...

Страница 6: ...002A and ACTpro 1500PoE controllers Mains present The PSU MAINS PRESENT output when available is pre wired to the MAINS PRESENT input Output Voltage The PSU output voltage level is reported to the ACT Enterprise software and on the web browser Tamper The enclosure lid is tamper monitored ACTpro 1500 15002A 1500PoE Door Controller Installation and Operating Instructions Overview Vanderbilt 2019 6 A...

Страница 7: ... 1500 2 1 1 Mounting Mount the ACTpro Controller directly on to the wall with the supplied screws The keyed mounting hole should be screwed first to the wall to aid the mounting The unit should be installed in a ventilated area that allows for accessibility after installation 2 1 2 Power supply The ACTpro 1500 requires an external 12V DC or 24V DC power supply The supply should be connected to the...

Страница 8: ...n Mains LED is on Note Red LED may be illuminated dependent upon model to indicate that no battery has been connected This is normal 3 Verify load is operating correctly 4 Disconnect mains power 2 2 4 Standby Battery Note Ensure batteries being fitted to this unit are in good condition 1 Connect battery leads to battery ensuring correct polarity of battery connections Vanderbilt recommend using a ...

Страница 9: ... 1 Mount the boxed module securely using the enclosure mounting points in the correct orientation allowing 100mm clearance around the enclosure see diagram 2 Route cables via knockouts and or rear cable enclosure entry holes 2 3 2 Power Up 1 Attach correctly rated load cable to load equipment and fasten using cable ties Note polarity 2 Attach suitable Ethernet cable from PoE source to POE IN RJ45 ...

Страница 10: ...on of a deeply discharged battery The fault should be rectified before restoring power to the ACTpro 1500PoE If any of the fuses require replacing ensure the correct fuse rating and type is used A spare fuse is supplied with the controller Battery charging will only start after a compliant PoE power source is connected to ACTpro 1500PoE it will not start up on battery Ensure only a healthy 12V bat...

Страница 11: ... Fire override configuration 12 3 5 Interlock airlock configuration 13 3 6 Intruder panel wiring 14 3 1 Typical wiring of ACTpro 1500 Label Description Label Description A Door contact normally closed F ACT reader wire colour coding B Push to exit normally open G Ethernet RJ45 Note All IP device must have a valid IP Address Vanderbilt 2019 11 A 100535 c 15 03 2019 ...

Страница 12: ...SDP EOL Jumper for OSDP Readers When attaching OSDP readers to the ACTpro 1500 family of controllers ensure that the EOL jumper is on the last two pins EOL position on the last reader only Jumper location on ACTpro 1500 PCB Jumper position for standard operation Jumper position for OSDP operation You cannot network ACTpro 1500 controllers when OSDP readers are attached 3 4 Fire override configurat...

Страница 13: ...w door For example the following diagram shows how to interlock two doors when the first door is open the second door is locked and vice versa To interlock additional doors continue linking OP3 and AUX I for each new door 2 In ACT Install for each airlock door click Advanced Setup Doors Door name Operations select the Interlock check box then click Save When Interlock is enabled on a door the door...

Страница 14: ...lick Advanced Setup Doors door Operations select the Intruder Panel check box then click Save c In ACT Manage for each user that will be allowed to arm and disarm the panel click Manage Users User name Options select the Arm Disarm check box then click Save Note Make sure the user is enabled 4 To arm the system a user with arm disarm rights should press the tick key on the keypad then present thei...

Страница 15: ... 2 Set the DEFAULT DIP switch 2 to ON 3 Hold down the Tamper spring 4 Apply power to the ACTpro Controller 5 Wait approximately 5 seconds until the controller confirms default completed by sounding the buzzer 6 Release the Tamper 7 Power down the ACTpro Controller 8 Set the DEFAULT DIP switch to OFF 9 Re apply power 4 2 DHCP static IP addressing DIP switch 1 The ACTpro Controller is shipped with t...

Страница 16: ... 2 to OFF 8 Re apply power Note The static IP address can be changed via the web interface or using ACT Software 4 4 Changing static IP address on the ACTpro Controller 1 Connect ACTpro Controller to the IP network 2 Open a web browser on a PC for example Microsoft Internet Explorer Google Chrome etc 3 Enter http NetBIOS address e g http ACT1520E 07116 4 Logon details Username installer Password 9...

Страница 17: ...D will illuminate if the Emergency break glass switch is activated l Mains Fault ACTpro 1500 Controller will accept a mains present signal from a PSU pre wired on ACTpro 1500 This is wired into MAINS PRESENT input on the PCB When the PSU has no mains supply the fault is active l Door Station offline When one or more enabled door stations are not communicating with the ACTpro Controller the Fault L...

Страница 18: ...erbilt International Ltd Clonshaugh Business and Technology Park Clonshaugh Dublin D17 KV 84 Ireland vanderbiltindustries com contact Vanderbilt 2019 Data and design subject to change without notice Supply subject to availability Document ID A 100535 c Edition date 15 03 2019 ...