ACTpro-120

Installation and Configuration Instructions

Document ID: A-100661

Edition date: 29.06.2020

Содержание ACTpro-120

Страница 1: ...ACTpro 120 Installation and Configuration Instructions Document ID A 100661 Edition date 29 06 2020 ...

Страница 2: ...o any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered http van fyi Link ACTpro 120 Hereby Vanderbilt International IRL Ltd declares that this equipment type is in compliance with the following EU Directives for CE marking Directive 2014 30 EU Electromagnetic Compatibility Directive Directive 2014 35 EU Low Voltage Dire...

Страница 3: ...ion 7 2 1 Mounting 7 2 2 AC power up 7 2 3 AC power up USA 8 2 4 Battery insertion 8 3 Wiring 9 3 1 Wiring the ACTpro 120 9 3 2 DIP switch addressing 10 3 3 Wiring Clock Data entry and exit readers 11 3 4 Wiring Wiegand entry and exit readers 12 3 5 Wiring Door Contact 13 3 6 Wiring Push Button PB 13 3 7 Break Glass monitoring only 14 4 Monitoring 16 5 Status Indicators 17 6 LED Indicators 18 Vand...

Страница 4: ...current limiting short circuit protection l Request to exit l Door monitoring l Tamper and AC present monitoring l Status LEDs l Interlocking 1 2 Technical specification Technical specification Relay contact rating Main relay 5A 50V AC AUX relay 1A 50V AC Indoor use only Compatible with ACTpro controllers ACTpro 1500 1520 4000 1 3 Electrical specification Electrical specification Input voltage 230...

Страница 5: ... the door station and supply the battery recharge current 500mA is reserved for battery recharge and to power the door station Therefore 1 5A is available to power readers and the lock A complete access control system will require readers and a lock mechanism all of which will require power The following table should be used for calculating the power budget ACTpro reader 1030 1040 1050 1060 100mA ...

Страница 6: ...oor stations ACTpro 1500PoE V54502 C112 A100 Single door IP controller with PoE PSU ACTpro 1520 V54502 C110 A100 Controller with integrated 12V 2A DC power supply ACTpro 100 V54502 C120 A100 Door station single door ACTpro 120 V54502 C122 A100 Door station with integrated 12V 2A DC power supply single door ACTpro IOM V54506 B100 A100 IO module 8 inputs and 8 outputs ACTpro 120 Installation and Con...

Страница 7: ...ian in accordance with local national codes 2 1 Mounting Mount the ACTpro 120 door station directly onto the wall with the supplied screws The keyed mounting hole should be screwed first to the wall to aid the mounting The unit should be installed in a ventilated area that allows for accessibility after installation 2 2 AC power up 1 Attach a correctly rated AC cable and fasten using the cable tie...

Страница 8: ...oad 3 Connect the red battery lead to the battery terminal and the black lead to the terminal 4 Apply the AC power and check the AC OK green LED is illuminated 5 Remove the AC power and check that ON BATTERY amber LED is illuminated If the amber LED is illuminated the battery is now supplying the output 6 Re apply the AC power The AC OK LED will illuminate and the ON BATTERY LED will extinguish AC...

Страница 9: ...Door Contact 13 3 6 Wiring Push Button PB 13 3 7 Break Glass monitoring only 14 3 1 Wiring the ACTpro 120 Label Description Label Description A Door contact normally closed E Break glass monitoring normally closed B Push to exit normally open F Vanderbilt reader wire colour coding C From previous door controller G DIP switches for door station addressing D To next door Vanderbilt 2020 9 A 100661 2...

Страница 10: ...n the row show the required placement of each DIP switch to configure that address Notes l Door 1 is reserved for the ACTpro 1500 1520 controller l Doors 1 and 2 are reserved for all other ACTpro 4000 controller ACTpro 120 Installation and Configuration Instructions Wiring Vanderbilt 2020 10 A 100661 29 06 2020 ...

Страница 11: ...eader SENSE cable or terminal to the SENSE input pin For Exit readers do not use this input CLOCK D1 Green CLOCK D1 This is the clock or strobe signal input on the ACTpro controller or door stations Connect the reader CLOCK D1 cable or terminal on the reader to CLOCK D1 input pin DATA D0 Blue DATA D0 This is the Data input Connect the reader DATA D0 cable or terminal on the reader to DATA D0 input...

Страница 12: ...0 B Exit Reader ACTpro 1030 Proximity reader EM1030 MF1030 EV1030 Do not connect the reader to the SENSE pin on the controller For Wiegand Entry Readers Wire D0 to the DATA D0 Pin on the ACTpro controller and D1 to the CLOCK D1 pin on the ACTpro controller For Wiegand Exit readers Wire the D0 of the exit reader to the SENSE pin on the ACTpro controller and D1 to the CLOCK D1 pin on the ACTpro cont...

Страница 13: ...e reader RED Brown RED Red LED control output from the ACTpro 1520 1500 Connect the reader brown cable to the terminal marked RED on the controller GREEN Yellow GREEN Green LED control output from the ACTpro 1520 1500 Connect the reader green cable or terminal marked GREEN on the ACTpro controller 3 5 Wiring Door Contact Connect door contact between DC input and 0V 3 6 Wiring Push Button PB Push b...

Страница 14: ...to the lock the second pole for monitoring When the break glass is not activated the B GL input pin is held low at 0V When the break glass device is activated the B GL input pin will lose the 0V goes high and report a break glass event The lock should be wired such that when the break glass is activated power to the lock is removed ACTpro 120 Installation and Configuration Instructions Wiring Vand...

Страница 15: ...Label Description Label Description A Relay C Break glass monitoring B Magnetic lock ACTpro 120 Installation and Configuration Instructions Wiring Vanderbilt 2020 15 A 100661 29 06 2020 ...

Страница 16: ...ACTpro 120 door station Output Voltage The PSU output voltage level is reported to the ACT Enterprise software and on the web browser Tamper The enclosure lid is tamper monitored Note All faults including AC Present and Tamper are reported on ACT Enterprise Vanderbilt 2020 16 A 100661 29 06 2020 ...

Страница 17: ...he fault LED will illuminate if the emergency break glass switch is activated l Comms Offline Door station is offline l AC Fault ACTpro 100 door station will accept an AC present signal from a PSU pre wired on ACTpro 120 This is wired into AC PRESENT input on the PCB When the PSU has no AC supply the fault is active l Low Supply Voltage When voltage to the 12V terminal is less than 9V l Fuse Blown...

Страница 18: ...er is being supplied to the load The maximum current that the PSU can guarantee is 1 5A plus 0 5A for battery charging Beyond this the fuse will trip and the LED will stay on until the load is fully disconnected Once the load has been disconnected remove devices to reduce the current demand below 1 5A It is important to calculate the power budget adequately See Power budget on page 5 for more info...

Страница 19: ...derbilt International Ltd Clonshaugh Business and Technology Park Clonshaugh Dublin D17 KV 84 Ireland vanderbiltindustries com contact Vanderbilt 2020 Data and design subject to change without notice Supply subject to availability Document ID A 100661 Edition date 29 06 2020 ...