1 Overview
The ACTpro-120 is a door station for a single door, with an integrated 12V 2A DC power supply. It expands
any of the existing ACTpro controllers by one door.
1.1 ACTpro-120 features
l
Main relay and AUX relay
l
Supports all ACTpro readers (RFID 125KHz, MIFARE Classic, DESFire EV1)
l
Break glass monitoring
l
Voltage monitoring
l
Supports clock and data or Wiegand readers
l
Multiple entry and exit readers
l
Reader current limiting / short circuit protection
l
Request to exit
l
Door monitoring
l
Tamper and AC present monitoring
l
Status LEDs
l
Interlocking
1.2 Technical specification
Technical specification
Relay contact rating
Main relay 5A / 50V AC
AUX relay 1A / 50V AC
Indoor use only
Compatible with ACTpro controllers
ACTpro-1500, 1520, 4000
1.3 Electrical specification
Electrical specification
Input voltage
/- 10%
Frequency
47-53Hz
Input fuse
625mA 250V anti-surge fuse
Output voltage
13.65V (+/-5%)
Max load
2A @ 25°C
Electronic output fuse
Yes
Battery current
~0.5A for a battery discharged to ~10V