3.4.0.1 Terminal block wiring
Reader
Terminal
Block
Recommended
Wiring colour
Controller
Input PIN
Signal Information
SENSE
White
SENSE
For Entry readers connect the reader SENSE cable or terminal
to the SENSE input pin. For Exit readers, do not use this input.
CLOCK/D1
Green
CLOCK/D1
This is the clock or strobe signal input on the ACTpro
1520/1500.
DATA/D0
Blue
DATA/D0
This is the Data input.
+12V/24V
Red
+12V/24V
Po12V DC Supply voltage for the reader.
0V/GND
Black
0V
0V Supply Voltage for the reader.
RED
Brown
RED
Red LED control output from the ACTpro 1520/1500. Connect
the reader brown cable to the terminal marked RED on the
controller.
GREEN
Yellow
GREEN
Green LED control output from the ACTpro 1520/1500. Connect
the reader green cable or terminal marked GREEN on the
ACTpro controller.
3.5 Wiring Door Contact
Connect door contact between DC input and 0V.
3.6 Wiring Push Button (PB)
Push button is connected between PB input and 0V. When push button is pressed the main relay is
activated for the configured time.
Push button is also referred to as exit button, egress button, request to exit.