VAMP 140
Overcurrent and earth-fault relay
Operation and Configuration
VAMP Ltd
20
Vamp 24h support phone +358 (0)40 573 6316
VM140.EN011
5.
Configuration and parameter
setting
User level: CONFIGURATION
•
Choose the protection functions in the ENABLE position of
the main menu, see chapter 5.2. NOTE! Protection
functions not enabled will not be shown in the submenus.
•
Change the parameters of overcurrent, unbalance and arc
protection functions in the IL SETTING position of the
main menu, see chapter 5.3.
Change the parameters of residual current protection
functions in the Io SETTING position of the main menu,
see chapter 5.3.
•
Change the parameters of Circuit Breaker Failure
Protection function in the CBFP Set position of the main
menu, see chapter 5.3.
•
Set the current transformer scaling and residual current
scaling (e.g. CTprim, CTsec, CToprim, etc.) in the SCALING
position of the main menu, see chapter 5.4.
•
Configure the digital outputs in the DOUT position of the
main menu, see chapter 5.5.
•
Configure the interlockings in the BLOCKING position of
the main menu, see chapter 5.6.
•
Configure the digital input in the DIGITAL IN position of
the main menu, see chapter 5.7.
•
Choose and configure the communication buses in the COM
position of the main menu, see chapter 5.8.
•
Configure the analog output in the mA OUTPUT position of
the main menu, see chapter 5.9.
•
Set the Date and time in the SERVICE position of the main
menu, see chapter 5.11.
NOTE!
Some of the parameters, for instance the password, can only be
altered via the RS 232 serial communication port using a PC.