VAMP 260 

 

Power monitoring unit 

Technical description 

VAMP Ltd

 

 18

 

Vamp 24h support phone : +358 (0)20 753 3264

 

VM260.EN004

 

Setting parameters of timers: 

Parameter: Value: 

Unit: Default: Description: 

On 

hh:mm:ss 

07:00:00 Activation time of the timer 

Off hh:mm:ss 

16:00:00 De-activation time of the 

timer 

 
 

 

 

For each four timers there 

are 12 different modes 
available: 

-; - 

The timer is off and not 

running. The output is 

off i.e. 0 all the time. 

Daily;  

 The timer switches on and off 

once every day. 

Monday;  

 

The timer switches on and off 

every Monday. 

Tuesday;  

 

The timer switches on and off 

every Tuesday. 

Wednesday;

  

The timer switches on and off 

every Wednesday. 

Thursday;  

 

The timer switches on and off 

every Thursday.  

Friday;  

  The timer switches on and off 

every Friday. 

Saturday;  

 

The timer switches on and off 

every Saturday. 

Sunday;  

  The timer switches on and off 

every Sunday. 

MTWTF;  

 

The timer switches on and off 

every day except Saturdays 

and Sundays  

MTWTFS;  

 

The timer switches on and off 

every day except Sundays. 

Mode 

SatSun;  

  The timer switches on and off 

every Saturday and Sunday. 

SagOn 

On; Off 

On 

Sag on event 

SagOff 

On; Off 

On 

Sag off event 

SwelOn 

On; Off 

On 

Swell on event 

SwelOf 

On; Off 

On 

Swell off event 

2.4.

 

User averages 

The device includes 8 freely configurable user average values. 
The user can configure the monitored value and the time frame 

inside which the average of the value is calculated. The time 
can be set from 1 second to 60 hours. 
 
 
 

Содержание 260

Страница 1: ...VAMP 260 Power monitoring unit Operation and configuration instructions Technical description...

Страница 2: ...VAMP 260 Power monitoring unit Operation and configuration VAMP Ltd 2 Vamp 24h support phone 358 0 20 753 3264 VM260 EN004...

Страница 3: ...18 4 2 Operation indicators 18 4 3 Reading event register 19 4 4 Forced control Force 19 4 5 Setting range limits 20 4 6 Adjusting display contrast 21 5 Configuration and parameter setting 22 5 1 Pri...

Страница 4: ...e from VMAC 260 VAMP 260 Changed company name from Vaasa Electronics to VAMP Ltd Added disturbance recorder VM260 EN002a Many editorial changes VM260 EN003a Updated the list of screens in Function men...

Страница 5: ...unit communicates with other systems using common protocols such as the ModBus RTU ModBus TCP Profibus DP IEC 60870 5 103 and it can be connected to a fibre optic SPA bus 1 2 Operating safety The ter...

Страница 6: ...o the serial port on the front panel or on the rear panel of the unit both cannot be used simultaneously Via the remote control port on the unit rear panel 2 2 Unit front panel The figure below shows...

Страница 7: ...2 2 1 1 Sections of the LCD dot matrix display 1 Main menu column 2 Heading of active menu 3 Cursor of main menu 4 Possible navigating directions push buttons 5 Measured adjustable quantity 6 Measured...

Страница 8: ...brackets is the term used for the buttons in this manual 2 2 3 Indicators The unit is provided with eight LED indicators on the unit front panel Power Error Com Alarm Trip A B C Figure 2 2 3 1 Operati...

Страница 9: ...ow keys UP and DOWN to move up and down in the main menu 2 For moving to a submenu repeatedly push the RIGHT key until the required submenu is shown Correspondingly push the LEFT key to cancel the sel...

Страница 10: ...Ltd 10 Vamp 24h support phone 358 0 20 753 3264 VM260 EN004 Figure 3 1 1 The principles of the menu structure and navigation in the menus 6 Push the INFO key to obtain additional information about any...

Страница 11: ...ASE 1 POWER PHASE 2 COS TAN PHASE SEQUENCIES E ENERGY DECIMAL COUNT E PULSE SIZES E PULSE DURATION ENERGY DOSE I PHASE CURRENTS RMS CURRENTS ANGLE DIAGRAM SYMMETRIC CURREN HARM DISTORTION HARMONICS of...

Страница 12: ...of Uc VOLTAGE SAG SW SAG SWELL CNTR SAG LOG SWELL LOG VOLT INTERRUPTS VOLT INT SETTING Ua WAVEFORM Ub WAVEFORM Uc WAVEFORM Dema DEMAND VALUES IL1 DEMAND IL2 DEMAND IL3 DEMAND IL1 RMS DEMAND IL2 RMS DE...

Страница 13: ...enabling DI DIGITAL INPUTS DELAYs for DigIn INPUT POLARITY EVENT MASKS 1 EVENT MASKS 2 DO RELAY OUTPUTS 1 RELAY OUTPUTS 2 Active exp energy p AO ANALOG OUTPUTS AO LINKS AO1 SCALING AO1 EXCEPT CTRL AO2...

Страница 14: ...IN MAX U12 MIN MAX U23 MIN MAX U31 MIN MAX ULN MIN MAX UL1 MIN MAX UL2 MIN MAX UL3 MIN MAX Uo MIN MAX U1 MIN MAX U2 MIN MAX U2 U1 MIN MAX Ua THD MIN MAX Ub THD MIN MAX Uc THD MIN MAX Pmax P MIN MAX Q...

Страница 15: ...ne 358 0 20 753 3264 15 Alr1 4 ALARM 1 4 STATUS SET ALARM 1 4 SET ALARM 1 4 LOG ALARM 1 4 Event enabling Lgic LOGIC EVENTS CONF DEVICE SETUP SCALING DEVICE INFO DATE TIME SETUP CLOCK SYNC CLOCK SYNC 2...

Страница 16: ...ameter setting state a password must be given see 3 2 1 Closing The level is automatically closed when 10 minutes has elapsed since a key was pushed or a setting was done via the local port The level...

Страница 17: ...for the desired level The password may contain four digits The digits are supplied one by one by first moving to the position of the digit using the RIGHT key and then setting the desired digit value...

Страница 18: ...ndicator Explanation Measure Remarks Power LED lit The auxiliary power has been switched on Normal operation state Error LED lit An internal unit fault has been detected The unit attempts to reboot If...

Страница 19: ...IST appears The display contains a list of all events that have been configured to be contained in the event register event_list_VAMP260 EVENT LIST Alarm5 on 910 A 2002 02 15 00 17 37 530 18 I I Figur...

Страница 20: ...trolled by force 8 Push the UP or DOWN key to change the selection from 0 not alert to 1 alert or vice versa 9 Push the ENTER key to execute the forced control operation of the selected function e g m...

Страница 21: ...21 Figure 4 5 1 Display of allowed setting ranges 2 Push the CANCEL key to return to the setting mode 4 6 Adjusting display contrast The readability of the LCD varies with the brightness and the tempe...

Страница 22: ...f the main menu NOTE Some of the parameters can only be altered via the RS 232 serial port using a PC e g changing the password 5 1 Principle of parameter setting 1 Move to the setting state of the de...

Страница 23: ...key Figure 5 1 1 Changing parameters 5 2 Disturbance recorder menu DR Via the submenus of the disturbance recorder menu the following functions and features can be read and set DISTURBANCE RECO Recor...

Страница 24: ...INPUTS Operation delay DELAYs for DigIn Polarity of the input signal INPUT POLARITY either normally open NO or normally closed NC circuit Selection to event register EVENT MASK1 and EVENT MASK2 5 4 C...

Страница 25: ...AO1 AO4 SCALING the configurations of the analogue outputs can be set 3 In the sub menus AO1 AO4 EXCEPT CTRL the configurations of the exceptional analogue outputs can be set Note AOx SCALING and AOx...

Страница 26: ...Uline Uphase DI DO 5 7 Setting alarm stage parameters The settings of the selected alarm stages can be read and set separately in the Alrm submenus There are 8 different alarm stages which can be sep...

Страница 27: ...ber at Modbus Master Protocol Addr Modbus transfer rate bit s ModBus parity check Parity SPABUS SLAVE Slave number Addr when unit connected to SPA Bus SPA Bus transfer rate bit s Event mode Emode Prof...

Страница 28: ...secondary Usec Voltage Meas Mode Umode Rated CT primary current Inom Rated CT secondary current Isec DEVICE INFO only display Unit type Type VAMP 260 Serial number SerN Software version PrgVer DATE TI...

Страница 29: ...260 VM260 EN004 Vamp 24h support phone 358 0 20 753 3264 29 Recalculate counter RCC Adjust counter AdjC Adjust interval AdjInt Ave sign Adjust save counter ASC Big deviations ext s ESBD Big deviation...

Страница 30: ...tion cable only the port on the front panel will be active To connect a PC to a serial port use a connection cable of type VX 003 3 6 1 1 Using the VAMPSET program See separate user s manual for the V...

Страница 31: ...urrent Isec Transform ratio of VTs CONF SCALING Primary voltage Unom secondary voltage Usec volt measurem mode Umode Scaling and settings of analog outputs AO AO1 AO4 SCALING Pri value for min output...

Страница 32: ...l time Run hours Runh number of starts Compensating wiring errors P PHASE SEQUENCY Swap current direction Idir Settings of user s averages Mean MEAN VALUE 1 8 Time of user s mean 1 8 Time time unit fo...

Страница 33: ...2 2 12 Min Max values 16 2 3 Timers 16 2 4 User averages 18 2 5 Logic functions 19 2 6 Programmable alarm functions 19 2 7 Communication 20 2 7 1 PC port 20 2 7 2 Remote control connection 21 2 8 Self...

Страница 34: ...6 Local serial communication port 38 5 1 7 Remote control connection 38 5 1 8 Analogue output connections option 38 5 2 Tests and environmental conditions 39 5 2 1 Disturbance tests EN 50263 39 5 2 2...

Страница 35: ...ag swell Voltage interruptions Demand values Timers Min Max values and Logic functions Added 24h support number and analogue outputs as optional Editorial changes 1 1 Application The power monitoring...

Страница 36: ...t Recording of events and fault values into an event register from which data can be read via the key pad and the display or by means of the PC based VAMPSET user interface Handy configuration paramet...

Страница 37: ...er transformation FFT in which the number of calculations multiplications and additions required to filter out the measuring quantities remains reasonable By using synchronized sampling of the measure...

Страница 38: ...monitored and stored see chapter 2 2 12 Phase currents IL1 IL2 IL3 Measuring range 0 5 x In In 1 A or 5 A Frequency The frequency is measured from the voltage input The minimum and maximum value of t...

Страница 39: ...er calculation for one phase sin 1 1 1 L L L I U Q where UL1 Measured L1 phase voltage IL1 Measured L1 current Angle between UL1 and IL1 Active reactive and apparent power are calculated as follows S...

Страница 40: ...ted to voltage Power direction cosfii Power factor inductive Lags Forward capacitive Leads Forward inductive Leads Reverse capacitive Lags Reverse 2 2 3 Energy calculations Calculated energy measures...

Страница 41: ...imported energy Each channel can be connected to any combination of the nine output relays The connection is configured in the output matrix The parameters for the energy pulses can be found in the E...

Страница 42: ...400 kWh The average pulse frequency will be 100 0 400 250 pulses h The peak pulse frequency will be 800 0 400 2000 pulses h Set pulse length to 3600 2000 0 2 1 6 s or less The trip relay lifetime will...

Страница 43: ...ion example of wiring the energy pulse outputs to a PLC having common minus and using an external wetting voltage Figure 2 2 4 4 Application example of wiring the energy pulse outputs to a PLC having...

Страница 44: ...pter 2 2 12 2 15 2 2 2 1 f f f rms I I I I RMS voltages PMU calculates the RMS value of each voltage input The minimum and the maximum of RMS values are recorded and stored see chapter 2 2 12 2 15 2 2...

Страница 45: ...SagOff On Off On Sag off event SwelOn On Off On Swell on event SwelOf On Off On Swell off event Recorded values of sags and swells monitoring Parameter Value Unit Description Count Cumulative sag coun...

Страница 46: ...me are stored as previous values The interruption counter and the total time are cleared for a new period The pre previous values are overwritten The voltage interruption is based on the value of the...

Страница 47: ...eter Value Unit Description Voltage LOW OK Current voltage status Measured value U1 Measured positive sequence voltage Count Number of voltage sags during the current observation period Prev Number of...

Страница 48: ...manually by editing the value from the local panel or through a remote user interface IL IL1 IL2 IL3 ILRMS IL1RMS IL2RMS IL3RMS ILTHD IL1THD IL2THD IL3THD ILda IL1da IL2da IL3da Io I1 I2 I1 I2 UL UL1...

Страница 49: ...er which is in use on or off The forcing is done by writing a new status value No forcing flag is needed as in forcing i e the output relays The forced time is valid until the next forcing or until th...

Страница 50: ...on and off every Wednesday Thursday The timer switches on and off every Thursday Friday The timer switches on and off every Friday Saturday The timer switches on and off every Saturday Sunday The time...

Страница 51: ...abled alarm stages have the following programmable parameters Link_ link to a measured or calculated value see table below Cmp_ mode or Set_ alarm limit of stage_ setting range depends on the signal t...

Страница 52: ...In Ref Mode A1 Start Delay In Ref Mode A6 RESET Latches Figure 2 6 2 Alarm output matrix Alarm functions can also be activated using the Force setting of each alarm stage ALARM STAGE _b Force ON OFF...

Страница 53: ...se see the corresponding documentation for more details Option modules Standards interface Internal Internal Internal External Protocol RS 232 VX004 M3 or VX008 4 Plastic or Glass RS 485 ProfiBus Ethe...

Страница 54: ...60 EN004 Also the internal supply voltage is supervised Should the auxiliary supply of the unit disappear an IF alarm is automatically given because the IF output relay functions on the working curren...

Страница 55: ...nt transmission network connection Industrial distribution networks Transforming station infeeder measurements Distribution feeder measurements High voltage motor measurements Capacitor bank measureme...

Страница 56: ...6 7 8 1 X2 1 2 3 4 5 6 7 8 9 X3 15 14 13 12 T1 T2 A1 A2 A3 IF 10 11 15 14 11 12 18 17 X2 9 13 10 16 48 V DI1 DI2 DI3 DI4 DI5 DI6 Remote SPABus ModBus ProfiBus TCP IP IEC 103 Local RS232 AO AO1 AO2 AO3...

Страница 57: ...4 5 6 7 8 1 X2 1 2 3 4 5 6 7 8 9 X3 15 14 13 12 10 11 15 14 11 12 18 17 X2 9 13 10 16 48 V DI1 DI2 DI3 DI4 DI5 DI6 Remote SPABus ModBus ProfiBus TCP IP IEC 103 Local RS232 AO AO1 AO2 AO3 AO4 AO1 AO2...

Страница 58: ...AO3 AO4 L1 L2 L3 P2 P1 40 265 V ac dc 18 36 V dc Processing Measured values Calculated values Alarm settings Etc example3 VAMP 260 T1 T2 A1 A2 A3 IF X1 1 2 3 4 5 6 X3 17 18 X1 11 12 13 14 15 16 X3 2 3...

Страница 59: ...nergy Management System Serial communication Energy pulses Meteringex Power Error Com Alarm Trip A B C VAMP260 PowerMonitoringUnit Power Error Com Alarm Trip A B C VAMP260 PowerMonitoringUnit Figure 3...

Страница 60: ...r monitoring unit Technical description VAMP Ltd 28 Vamp 24h support phone 358 0 20 753 3264 VM260 EN004 3 5 Power Monitoring Unit in a 400 V network Figure 3 5 1 Example of VAMP 260 voltage measureme...

Страница 61: ...X1 1 6 Line voltages Ua Ub and Uc terminals X1 11 16 4 1 Digital inputs Further the measuring unit can collect status information and alarm signals via six digital inputs terminals X3 2 7 The digital...

Страница 62: ...Self supervision system output relay IF terminals X2 16 18 4 4 Serial communication connection X4 RS 232 serial communication connection for computers connector LOCAL RS 232 connectors on front panel...

Страница 63: ...ted together 4 5 1 mA scaling examples In this chapter there are three example configurations of scaling the transducer mA outputs Example 1 Coupling IL Scaled minimum 0 A Scaled maximum 300 A Analogu...

Страница 64: ...ng Uline Scaled minimum 0 V Scaled maximum 15000 V Analogue output minimum value 4 mA Analogue output maximum value 20 mA ULINE V mA Analogue output 4 8 12 16 20 15000 mAscaling_2 Figure 4 5 1 2 Examp...

Страница 65: ...ctional power At 2000 kVar the transducer output is 4 mA at 0 kVar it is 8 mA and at 6000 kVar the output is 20 mA 4 5 2 Exception control of analogue outputs Each channel AO1 AO4 has a possibility to...

Страница 66: ...VAMP 260 Power monitoring unit Technical description VAMP Ltd 34 Vamp 24h support phone 358 0 20 753 3264 VM260 EN004 4 6 Block diagram Figure 4 6 1 Block diagram of the power monitoring unit VAMP 260...

Страница 67: ...VAMP Ltd Power monitoring unit Technical description VAMP 260 VM260 EN004 Vamp 24h support phone 358 0 20 753 3264 35 Figure 4 6 2 Block diagram of the power monitoring unit VAMP 260 with mA option...

Страница 68: ...VAMP 260 Power monitoring unit Technical description VAMP Ltd 36 Vamp 24h support phone 358 0 20 753 3264 VM260 EN004 4 7 Connection diagram Figure 4 7 1 VAMP 260 connection diagram...

Страница 69: ...e dimension Solid or stranded wire 4 mm2 10 12 AWG 5 1 2 Auxiliary voltage Type A standard Type B option Rated voltage Uaux 40 265 V ac dc 18 36 V dc 110 120 220 240 V ac 24 V dc 48 60 110 125 220 V d...

Страница 70: ...2 000 VA Contact material AgNi 0 15 gold plated Terminal block Maximum wire dimension Phoenix MVSTBW or equivalent 2 5 mm2 13 14 AWG 5 1 6 Local serial communication port Number of ports 1 on front a...

Страница 71: ...EN 61000 4 3 80 1000 MHz 10 V m 80 AM 1 kHz GSM test EN 61000 4 3 900 MHz 10 V m pulse modulated 1 MHz burst IEC 60255 22 1 1 kV differential mode 2 5 kV common mode Voltage interruption IEC 60255 11...

Страница 72: ...Weight Relay Package and Manual 5 2 kg 5 3 Disturbance recorder DR The operation of Disturbance recorder depends on the following settings The recording time and number of records depend on the time s...

Страница 73: ...VM260 EN004 Vamp 24h support phone 358 0 20 753 3264 41 6 Construction 6 1 Dimensional drawing 208 0 155 0 27 0 181 0 28 0 137 0 190 0 193 0 20 0 1 0 10 0 139 0 P200_ulkomitat_kannella PANEL CUT OUT...

Страница 74: ...64 VM260 EN004 6 2 Panel mounting Figure 6 2 1 Flush mounting of protection unit in panel 6 3 Semi flush mounting 27 0 181 0 28 0 137 0 P200_semi flush b a 21 0 Figure 6 3 1 Semi flush mounting of pro...

Страница 75: ...ass Tx Plastic Optic Interface Analog Outputs A 4pcs B None Accessories Order Code Explanation Note VEA 3 CG Ethernet Interface Module VAMP Ltd VPA 3 CG Profibus Interface Module VAMP Ltd VMA 3 CG RS4...

Страница 76: ...VAMP Ltd P O Box 810 FIN 65101 Vaasa Finland Visiting address Yritt j nkatu 15 Phone 358 0 20 753 3200 Fax 358 0 20 753 3205 Email vamp vamp fi URL http www vamp fi Service VAMP Ltd P O Box 810 FIN 65...

Страница 77: ...VAMP Ltd Power monitoring unit Technical description VAMP 260 VM260 EN004 Vamp 24h support phone 358 0 20 753 3264 45...

Страница 78: ...erve the rights to changes without prior notice VAMP Ltd Street address Yritt j nkatu 15 Phone 358 20 753 3200 Post address Fax 358 20 753 3205 P O Box 810 FIN 65101 Vaasa Intenet www vamp fi Finland...

Отзывы: