31
7.
Commissioning configuration
7.1.
Factory settings
When delivered from the factory, the unit has been given
factory default settings or settings defined by the customer.
The actual configuration can be read from the workshop test
report or from the final test report.
7.1.1.
Configuration during commissioning
The settings of the power monitoring unit VAMP 260 can be
defined and checked during commissioning in accordance with
the instructions given in chapter 5 of this manual.
Basic parameters of VAMP 260:
Parameter:
Main/submenu:
Values to be set:
Transform ratio
of CTs
CONF/SCALING Primary current: Inom,
secondary current: Isec
Transform ratio
of VTs
CONF/SCALING Primary voltage: Unom,
secondary voltage: Usec
volt. measurem. mode: Umode
Scaling and
settings of
analog outputs
AO/AO1-AO4
SCALING
Pri. value for min output: min,
pri. value for max output: max, AO1
- 4 links: Lnk1-4
analog output min: AO1-4 min
analog output max: AO1-4 max
AO/AO1-AO4
EXEPT.CTRL
AO1-4 exception link: Exc1-4
AO1-4 except. cond: Cond1-4
AO1-4 exception limit: Lim1-4 AO1-
4 except. value: ExVal1-4
Delays for digital
inputs
DI/DELAYs for
DigIn
Delay time for 1dly - 6dly
Input polarity fo
digital inputs
DI/INPUT
POLARITY
Polarity DI1pol – DI6pol
Alarm routing to
LEDs and alarm
relays
DO/(output
matrix)
Alarm signals to LEDs A, T, L, L, L
Alarm signals to relays T, T, A, A, A:
- Connected/Latched
Initial values of
energy counters
E
Exported & imported energy E+, E-
exp. & imported reactive energy
Eq+, Eq-
DI_ total time counter: Runh
Decimals for
energy counters
E/DECIMAL
COUNT
Number of decimals for E+, Eq, E-
and Ed