background image

5

2.2.3

 

To a fireplace that has a precast concrete or clay
flue block system conforming to BS1289. The
appliance is suitable for installations conforming
to older versions of BS1289 as well as the current
edition. The flue blocks must have a minimum
width not less than 63mm and a cross-sectional
area not less than 13,000mm

2

.

 Older editions of

BS1289 required a cross-sectional area of
13,000mm

2

. The current revision of the standard

requires 16,500mm

2

. This appliance is suitable in

both cases. The total depth of the opening
measured from the finished front of the fireplace
(Including plaster, surround etc) must be 

not less

than 100mm.

The current version of BS1289 recommends that
there should be an air space or insulation between
the flue blocks and the plaster because heat
transfer may cause cracking on directly plastered
flues. However, generally this appliance is suitable
for installations under all circumstances unless
there is a history of cracking problems.

Remember that faults such as cracking may be

caused by poorly built and restrictive flues, e.g.
mortar extrusions, too many bends, flue heights
below three metres, restrictive terminations, etc.

2.2.4

To a builder’s opening within the dimensions
shown in figure 1a.

2.3

Suitable flues and minimum flue sizes are as
follows: -

a. 225mm x 225mm conventional brick flue.
b. 175mm diameter lined brick or stone flue.
c. 200mm diameter factory made insulated flue

manufactured to BS 4543.

d. 175mm diameter flue pipe (see B.S 6461 part 1

for suitable materials).

e. Single wall, twin wall or flexible flue liner of

minimum diameter 125mm.  The materials to
be used are stainless steel or aluminium as
specified in B.S 715.

 f. A properly constructed precast concrete or

clay flue system conforming to BS 1289 Part 1
or 2.
It should be noted that, sharp bends or
horizontal runs in metal flues at the top of the
system could be a cause of problems in these
types of installation.

2.4

The minimum effective height of the flue must be
3m.

2.5

The flue must not be used for any other appliance
or application.

2.6

Any chimney dampers or restrictors should be
removed.  If removal is not possible they must be
fixed in the open position.

2.7

If the appliance is intended to be installed to a
chimney which was previously used for solid fuel,
the flue must be swept clean prior to installation.
All flues should be inspected for soundness and
freedom from blockages.

2.8

If the fireplace opening is of underfloor draught
type, it must be sealed to stop any draughts.

2.9

The appliance must be mounted behind a non-
combustible hearth (n.b conglomerate marble
hearths are considered as non-combustible).  The

appliance can be fitted to a purpose made
proprietary class “O” 150°C surround.  The
hearth material must be at least 12mm thick.  The
periphery of the hearth (or fender) should be at
least 50mm above floor level to discourage the
placing of carpets or rugs over it.

The surface of the hearth must be sufficiently flat
to enable the bottom of the front surround, the
burner bracket and the bottom front cover casting
to be aligned horizontally. Any excessive
unevenness (uneven tiles, Cotswold stone, etc.)
should be rectified.

The appliance must not  stand on combustible

materials or carpets.

The appliance must not be fitted directly against a
combustible wall. 

If the appliance is to be fitted

against a wall with combustible cladding, the
cladding must be removed from the area covered
by the outer surround 

 

(see figure 1c). We suggest

that the actual surround is used as a template to
mark the area for combustible cladding removal.

2.10

The minimum allowable distance to a corner wall
from the outside edge at either side of the front
surround is 178mm.

2.11

The front face of the fireplace should be
reasonably flat over the area covered by the
convection box top and side flange seals to ensure
good sealing.  These faces should be made good if
necessary.
The fireplace floor should be reasonably flat to
ensure that a good seal with the convection box
can be made (see fig.15).

2.12

The minimum height from the top surface of the
hearth to the underside of any shelf made from
wood or other combustible materials is as follows:
-

For a shelf up to 150mm deep

Minimum height = 750mm.

For a shelf deeper than 150mm

Minimum height = 750mm + 12.5mm for every
25mm depth over 150mm.

2.13

Note that soft wall coverings (e.g. embossed vinyl,
etc.) are easily affected by heat. They may scorch
or become discoloured when close to a heating
appliance.  Please bear this in mind when
installing.

2.14

The appliance must not be installed in any room,
which contains a bath, or shower or where steam
is regularly present

.

2.15

An extractor fan may only be used in the same
room as this appliance, or in any area from which
ventilation for the appliance is taken, if it does not
affect the safe performance of the appliance. Note
the spillage test requirements detailed further on
in this manual. If the fan is likely to affect the
appliance, the appliance must not be installed
unless the fan is permanently disconnected.

2.16

I

n the United Kingdom (GB)

 

no special

ventilation bricks or vents are required in the
room for this appliance

.

In the Republic of Ireland (IE), permanent
ventilation must comply with the regulations
currently in force.

Содержание BR

Страница 1: ...06 02 MODEL BR417 G C 3 2 0 3 2 0 7 I n s e t L i v e F u e l E f f e c t G a s F i r e with U l t i m a t e or Superflame Front I N S T A L L E R G U I D E Please keep in a safe place for future refe...

Страница 2: ...all rates apply As supplied this appliance is for use with natural gas G20 When converted using Valor conversion kit no 591149 this appliance is for use with propane gas G31 These appliances are for u...

Страница 3: ...pipe installation 11 Preliminary burner checks 11 Reference pressure check 11 Ceramic coals walls installation 12 Full operating checks 13 Control settings check 13 Flue spillage check 13 Flame super...

Страница 4: ...nstallers CORGI requires its members to work to recognised standards The Confederation for the Registration of Gas Installers CORGI requires its members to work to recognised standards The installatio...

Страница 5: ...must be mounted behind a non combustible hearth n b conglomerate marble hearths are considered as non combustible The appliance can be fitted to a purpose made proprietary class O 150 C surround The...

Страница 6: ...r sealing tape 1 Flue restrictor plate 6 Fibre plugs 4 Woodscrews 2 Fire retaining cables 2 Cable clamps 4 Eyebolts 1 Installation template 1 Smoke match tube 1 Fire front casting 1 Bottom front cover...

Страница 7: ...or are sound enough to take the eyebolts and screws If these areas have deteriorated due to prolonged use they should be made sound with a suitable cement 4 2 3 Installations using a metal flue box Th...

Страница 8: ...and through a cut out at either rear bottom corner of the fire front casting For side connection final installation of the supply pipe should be left until the appliance is installed in the fireplace...

Страница 9: ...a concealed connection is being used insert the convection box into the fireplace feeding the supply pipe through the pierced hole in the rear seal 7 1 2 Mark the fireplace front surround through the...

Страница 10: ...10...

Страница 11: ...ainer over the bottom end of each cable 7 2 8 Pull each cable taut Push the cable retainers hard up against the V brackets Tighten the screws in the retainers so that they clamp the cables in position...

Страница 12: ...ition has been achieved keep the control knob depressed for approximately ten seconds to allow the thermocouple probe to warm up and then release it If the pilot does not remain alight ensure that the...

Страница 13: ...marked at the rear bottom corners L Left side R Right side Place the side walls against the sides of the fire box and in the recesses at the sides of the base coals The markings L R should be at the...

Страница 14: ...of the cross member figure 23 Keeping the neck of flared end in contact with the edge of the cross member slide the tube to the left until you feel it enter the notch in the edge of the cross member...

Страница 15: ...om of the appliance 11 6 Explain to the customer that the appliance has a flame failure spillage monitoring system Point out the explanation of this system shown in the owner s guide under Operating t...

Страница 16: ...hand plaque in position The left side of the plaque must touch the inside edge of the retaining flange at the left side of the burner well 12 1 6 Place the new right hand plaque in position Make sure...

Страница 17: ...12 4 6 Remove the second screw securing the pilot unit to the burner Remove the pilot unit and place it aside 12 4 7 Refit in the reverse order Note 1 The pilot unit must be replaced as a whole assemb...

Страница 18: ...are correctly engaged Check the operation of the tap 12 7 8 Refit the piezo generator 12 8 TO REMOVE THE MAIN BURNER INJECTOR 12 8 1 Remove the burner unit See section 12 3 12 8 2 Disconnect the main...

Страница 19: ...l knob 1 545979 E Pilot unit For Natural Gas Appliances 1 540979 Pilot unit For Propane Appliances 544929 F Burner plaque gasket set 1 569439 G Ceramic rear wall 1 545999 H Front coal halves 1 569449...

Страница 20: ...ards Valor is a member of the Society of British Gas Industries which works to ensure high standards of safety quality and performance Careful Installation Valor is a Corgi registered company All our...

Отзывы: